Homepage  
Search
find:
search for:
   
 
Site Navigation
News / Publications
Jobs
Service
   Add this page to Google Bookmarks
   Add this page to Mister Wong
   Add this page to del.icio.us
 
   Trane Company (The)  Packaged Rooftop Air Conditioners -RT-DS-8  

Packaged Rooftop Air Conditioners - RT-DS-8 - Page 817

 

 

Selection Procedure

This section outlines a step-by-stepprocedure that may be used to select a Trane single-zone air conditioner. The sample selection is based on the following conditions:

  • Summer outdoor design conditions — 95 DB/76 WB ambient temperature
  • Summer room design conditions — 78 DB/65 WB
  • Total cooling load — 430 MBh (35.8 tons)
  • Sensible cooling load — 345 MBh (28.8 tons)
  • Outdoor air ventilation load — 66.9 MBh
  • Return air temperature — 80 DB/65 WB

Winter Design:

  • Winter outdoor design conditions — 0 F
  • Return air temperature — 70 F
  • Total heating load — 475 MBh
  • Winter outdoor air ventilation load — 133 MBh

Air Delivery Data:

  • Supply fan cfm — 17,500 cfm
  • External static pressure — 1.2 in wg
  • Minimum outdoor air ventilation — 1,750 cfm
  • Exhaust fan cfm — 12,000 cfm
  • Return air duct negative static pressure — 0.65 in wg

Electrical Characteristics:

  • Voltage/cycle/phase — 460/60/3

Unit Accessories:

  • Gas fired heat exchanger — high heat module
  • Throwaway filters
  • Economizer
  • Modulating 100 percent exhaust/ return fan

COOLING CAPACITY SELECTION

Step 1 — Nominal Unit Size Selection

A summation of the peak cooling load and the outside air ventilation load shows: 430 MBh + 66.9 MBh = 496.9 MBh required unit capacity. From Table 26-1, a 50-ton unit capacity with standard capacity evaporator coil at 80 DB/65 WB, 95 F outdoor air temperature and 17,500 total supply cfm is 551 MBh total and 422 MBh sensible. Thus, a nominal 50-ton unit with standard capacity evaporator coil is selected.

Step 2 — Evaporator Coil Entering Conditions

Mixed air dry bulb temperature determination: Using the minimum percent of OA (1,750 cfm ÷ 17,500 cfm = 10 percent), determine the mixture dry bulb to the evaporator. RADB + % OA (OADB - RADB) = 80 + (0.10) (95 - 80) = 80 + 1.5 = 81.5 F Approximate wet bulb mixture temperature: RAWB + % OA (OAWB - RAWB) = 65 + (0.10) (76 - 65) = 65 + 1.1 = 66.1 F

Step 3 — Determine Supply Fan Motor Heat Gain

Having selected a nominal 50-ton unit, the supply fan bhp can be calculated. The supply fan motor heat gain must be considered in final determination of unit capacity.

Supply Air Fan

Determine unit total static pressure at design supply cfm:

External Static Pressure 1.2  inches
Evaporator Coil   (Table 57-1) 0.25 inches
Return Duct Negative   Static Pressure 0.65 inches
Heat Exchanger   (Table 57-1) 0.31 inches
Throwaway Filter   (Table 57-1) 0.10 inches
Economizer w/Exhaust Fan   (Table 57-1) 0.12 inches
Trane Roof Curb   (Table 57-1) 0.13 inches
Unit Total Static Pressure 2.76 inches

Using total of 17,500 cfm and total static pressure of 2.76 inches, enter Table 41-1. Table 41-1 shows 15.3 bhp with 924 rpm.

From Chart 19-1 supply fan motor heat gain = 46.0 MBh. Selection Procedure

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com