Performance Data 20, 25 Ton
Table 38-1 Supply Fan 20 and 25 Ton
| Cfm
Std Air |
Total
Static Pressure |
| ,250 |
,500 |
,750 |
1.000 |
1.250 |
1.500 |
1.750 |
2.000 |
| RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
| 4000 |
387 |
.37 |
514 |
.65 |
621 |
.99 |
712 |
1.37 |
791 |
1.78 |
861 |
2.22 |
925 |
2.67 |
983 |
3.13 |
| 5000 |
420 |
.55 |
530 |
.85 |
631 |
1.22 |
721 |
1.62 |
800 |
2.06 |
872 |
2.54 |
939 |
3.05 |
1000 |
3.57 |
| 6000 |
469 |
.82 |
557 |
1.13 |
646 |
1.51 |
730 |
1.95 |
810 |
2.43 |
881 |
2.92 |
947 |
3.45 |
1009 |
4.01 |
| 7000 |
526 |
1.21 |
591 |
1.50 |
673 |
1.92 |
748 |
2.36 |
819 |
2.85 |
892 |
3.40 |
958 |
3.96 |
1018 |
4.54 |
| 8000 |
586 |
1.72 |
638 |
2.02 |
702 |
2.41 |
775 |
2.90 |
841 |
3.41 |
903 |
3.94 |
967 |
4.54 |
1029 |
5.17 |
| 9000 |
647 |
2.37 |
692 |
2.68 |
742 |
3.05 |
803 |
3.53 |
868 |
4.10 |
928 |
4.67 |
983 |
5.24 |
1038 |
5.87 |
| 10000 |
708 |
3.15 |
750 |
3.51 |
792 |
3.88 |
840 |
4.33 |
895 |
4.88 |
954 |
5.50 |
1010 |
6.14 |
1060 |
6.77 |
| 11000 |
769 |
4.10 |
809 |
4.51 |
846 |
4.90 |
886 |
5.33 |
931 |
5.85 |
982 |
6.46 |
1036 |
7.14 |
1088 |
7.85 |
| Cfm
Std Air |
Total
Static Pressure |
| 2.250 |
2.500 |
2.750 |
3.000 |
3.250 |
3.500 |
3.750 |
4.000 |
| RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
| Air |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
| 4000 |
1037 |
3.61 |
1087 |
4.09 |
1135 |
4.59 |
1180 |
5.11 |
1224 |
5.63 |
1265 |
6.16 |
1305 |
6.70 |
1343 |
7.26 |
| 5000 |
1056 |
4.12 |
1109 |
4.67 |
1159 |
5.24 |
1206 |
5.82 |
1251 |
6.40 |
1293 |
7.00 |
1334 |
7.61 |
1374 |
8.23 |
| 6000 |
1067 |
4.60 |
1122 |
5.21 |
1174 |
5.84 |
1223 |
6.48 |
1269 |
7.14 |
1314 |
7.80 |
1356 |
8.48 |
1397 |
9.16 |
| 7000 |
1076 |
5.14 |
1131 |
5.78 |
1183 |
6.45 |
1233 |
7.13 |
1281 |
7.84 |
1327 |
8.56 |
1371 |
9.29 |
1413 |
10.04 |
| 8000 |
1086 |
5.82 |
1140 |
6.47 |
1192 |
7.14 |
1241 |
7.85 |
1289 |
8.58 |
1335 |
9.34 |
1380 |
10.11 |
1423 |
10.90 |
| 9000 |
1095 |
6.56 |
1151 |
7.27 |
1203 |
8.00 |
1252 |
8.72 |
1299 |
9.47 |
1344 |
10.23 |
1388 |
11.02 |
1431 |
11.84 |
| 10000 |
1109 |
7.43 |
1160 |
8.14 |
1211 |
8.90 |
1262 |
9.70 |
1310 |
10.50 |
1355 |
11.30 |
1399 |
12.12 |
1441 |
12.94 |
| 11000 |
1136 |
8.54 |
1181 |
9.24 |
1225 |
9.97 |
1271 |
10.75 |
1318 |
11.58 |
1364 |
12.45 |
1409 |
13.33 |
1452 |
14.21 |
| Cfm
Std Air |
Total
Static Pressure |
| 4.250 |
4.500 |
4.750 |
5.000 |
5.250 |
5.500 |
5.750 |
6.000 |
| RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
| Air |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
| 4000 |
1380 |
7.82 |
1416 |
8.39 |
1450 |
8.97 |
1484 |
9.56 |
1517 |
10.16 |
1549 |
10.77 |
1580 |
11.38 |
1611 |
12.01 |
| 5000 |
1412 |
8.85 |
1449 |
9.49 |
1484 |
10.13 |
1519 |
10.78 |
1552 |
11.44 |
1585 |
12.11 |
1617 |
12.79 |
1648 |
13.47 |
| 6000 |
1436 |
9.85 |
1474 |
10.55 |
1511 |
11.26 |
1547 |
11.98 |
1581 |
12.70 |
1615 |
13.44 |
1647 |
14.18 |
|
|
| 7000 |
1453 |
10.80 |
1493 |
11.57 |
1531 |
12.34 |
1567 |
13.13 |
1603 |
13.92 |
1638 |
14.72 |
|
|
|
|
| 8000 |
1465 |
11.71 |
1505 |
12.54 |
1544 |
13.37 |
1582 |
14.22 |
1618 |
15.07 |
1654 |
15.94 |
|
|
|
|
| 9000 |
1473 |
12.68 |
1514 |
13.53 |
1553 |
14.41 |
1591 |
15.30 |
1629 |
16.20 |
|
|
|
|
|
|
| 10000 |
1482 |
13.79 |
1522 |
14.66 |
1561 |
15.55 |
1600 |
16.46 |
1637 |
17.40 |
|
|
|
|
|
|
| 11000 |
1493 |
15.10 |
1533 |
15.99 |
1572 |
16.89 |
1609 |
17.82 |
1646 |
18.76 |
|
|
|
|
|
|
Notes:
1. Fan performance for 20 and 25 ton rooftops is identical.
However, note maximum motor hp size for each size. Contact your local Trane representative
for information on oversized motors.
2. Shaded areas at table extremes note non-standard Bhp or
Rpm selection. Contact your local Trane representative for more information.
3. Supply fan performance table includes internal
resistance of rooftop. For total static pressure determination, system external static
must be added to appropriate component static pressure drops (evaporator coil, filters,
optional economizer, optional exhaust fan, optional heating system, optional cooling only
extended casing, optional roof curb).
4. Maximum Cfm (for UL approval) as follows:
20 Ton 9,000 Cfm
25 Ton 11,000 Cfm
5. Minimum motor horsepower is 3 hp.
6. Maximum motor horsepower as follows:
20 Ton 10 hp
25 Ton 15 hp
7. Maximum 3 hp and 5 hp motor Rpm is 1,100, maximum 7.5 hp
through 15 hp motor Rpm is 1655.
8. See RT-EB-104 for further details

|
| Important:Maximum static
pressure leaving the rooftop is 4.0" H2O positive .The ststic pressure