Performance Data 30 Ton
Table 39 1
Supply Fan Performance With VARIABLE FREQUENCY DRIVE or WITHOUT INLET VANES
30 Ton
Cfm Std Air |
Total Static Pressure |
.250 |
.500 |
,750 |
1.000 |
1.250 |
1.500 |
1.750 |
2.000 |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
6000 |
316 |
.50 |
426 |
.89 |
519 |
1.36 |
598 |
1.88 |
666 |
2.42 |
728 |
2.99 |
784 |
3.59 |
835 |
4.22 |
7000 |
334 |
.65 |
430 |
1.05 |
521 |
1.56 |
600 |
2.12 |
669 |
2.71 |
731 |
3.32 |
788 |
3.97 |
841 |
4.64 |
8000 |
354 |
.85 |
440 |
1.27 |
523 |
1.78 |
602 |
2.37 |
671 |
3.01 |
733 |
3.67 |
791 |
4.36 |
844 |
5.08 |
9000 |
376 |
1.09 |
456 |
1.54 |
530 |
2.06 |
603 |
2.66 |
673 |
3.33 |
736 |
4.04 |
793 |
4.78 |
846 |
5.54 |
10000 |
399 |
1.38 |
474 |
1.87 |
542 |
2.40 |
609 |
3.00 |
674 |
3.69 |
737 |
4.43 |
795 |
5.22 |
849 |
6.02 |
11000 |
424 |
1.73 |
493 |
2.25 |
558 |
2.82 |
619 |
3.43 |
679 |
4.11 |
739 |
4.86 |
797 |
5.68 |
851 |
6.53 |
12000 |
450 |
2.13 |
515 |
2.70 |
576 |
3.30 |
633 |
3.93 |
688 |
4.62 |
744 |
5.37 |
798 |
6.19 |
852 |
7.07 |
13000 |
475 |
2.59 |
537 |
3.21 |
595 |
3.85 |
649 |
4.52 |
701 |
5.22 |
753 |
5.98 |
804 |
6.79 |
854 |
7.67 |
13500 |
488 |
2.85 |
549 |
3.50 |
605 |
4.15 |
658 |
4.83 |
709 |
5.55 |
758 |
6.32 |
808 |
7.13 |
856 |
8.01 |
Cfm Std Air |
Total Static Pressure |
2.250 |
2.500 |
2.750 |
3.000 |
3.250 |
3.500 |
3.750 |
4.000 |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
6000 |
883 |
4.86 |
927 |
5.51 |
968 |
6.18 |
1007 |
6.86 |
1043 |
7.54 |
1078 |
8.24 |
1111 |
8.94 |
1143 |
9.65 |
7000 |
890 |
5.33 |
936 |
6.04 |
979 |
6.78 |
1020 |
7.52 |
1059 |
8.28 |
1095 |
9.05 |
1130 |
9.83 |
1164 |
10.62 |
8000 |
894 |
5.82 |
941 |
6.57 |
985 |
7.35 |
1027 |
8.15 |
1067 |
8.97 |
1105 |
9.80 |
1142 |
10.65 |
1177 |
11.51 |
9000 |
896 |
6.32 |
944 |
7.13 |
989 |
7.95 |
1031 |
8.79 |
1072 |
9.66 |
1111 |
10.54 |
1149 |
11.43 |
1185 |
12.35 |
10000 |
899 |
6.85 |
946 |
7.70 |
991 |
8.57 |
1034 |
9.46 |
1075 |
10.37 |
1115 |
11.29 |
1153 |
12.24 |
1189 |
13.20 |
11000 |
901 |
7.41 |
949 |
8.30 |
994 |
9.22 |
1037 |
10.15 |
1078 |
11.11 |
1118 |
12.08 |
1156 |
13.07 |
1193 |
14.07 |
12000 |
903 |
7.99 |
951 |
8.94 |
996 |
9.90 |
1039 |
10.88 |
1080 |
11.88 |
1120 |
12.89 |
1158 |
13.93 |
1195 |
14.98 |
13000 |
904 |
8.61 |
952 |
9.60 |
998 |
10.61 |
1041 |
11.63 |
1083 |
12.68 |
1122 |
13.74 |
1161 |
14.82 |
1198 |
15.91 |
13500 |
905 |
8.95 |
953 |
9.94 |
998 |
10.97 |
1042 |
12.02 |
1084 |
13.09 |
1123 |
14.18 |
1162 |
15.28 |
1199 |
16.40 |
Cfm Std Air |
Total Static Pressure |
4.250 |
4.500 |
4.750 |
5.000 |
5.250 |
5.500 |
5.750 |
6.000 |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
6000 |
1174 |
10.37 |
1203 |
11.10 |
1231 |
11.83 |
1259 |
12.57 |
1285 |
13.32 |
1311 |
14.08 |
1336 |
14.85 |
1361 |
15.62 |
7000 |
1196 |
11.41 |
1227 |
12.22 |
1256 |
13.03 |
1285 |
13.85 |
1313 |
14.68 |
1340 |
15.51 |
1366 |
16.35 |
|
|
8000 |
1210 |
12.38 |
1243 |
13.26 |
1274 |
14.14 |
1304 |
15.04 |
1333 |
15.94 |
1361 |
16.85 |
|
|
|
|
9000 |
1219 |
13.28 |
1253 |
14.22 |
1285 |
15.18 |
1316 |
16.14 |
1347 |
17.11 |
1376 |
18.10 |
|
|
|
|
10000 |
1225 |
14.17 |
1259 |
15.16 |
1292 |
16.17 |
1324 |
17.19 |
1355 |
18.23 |
|
|
|
|
|
|
11000 |
1228 |
15.09 |
1263 |
16.13 |
1297 |
17.18 |
1329 |
18.25 |
1361 |
19.33 |
|
|
|
|
|
|
12000 |
1231 |
16.04 |
1266 |
17.13 |
1300 |
18.22 |
1333 |
19.33 |
1365 |
20.46 |
|
|
|
|
|
|
13000 |
1234 |
17.03 |
1268 |
18.15 |
1302 |
19.30 |
1335 |
20.45 |
1368 |
21.62 |
|
|
|
|
|
|
13500 |
1235 |
17.53 |
1270 |
18.68 |
1303 |
19.85 |
1337 |
21.03 |
1369 |
22.22 |
|
|
|
|
|
|
Notes:
1. Shaded areas at table extremes note non-standard Bhp or
Rpm selection. Contact your local Trane representative for more information.
2. Supply fan performance table includes internal
resistance of rooftop. For total static pressure determination, system external static
must be added to appropriate component static pressure
drops (evaporator coil, filters, optional economizer,
optional exhaust fan, optional heating system, optional cooling only extended casing,
optional roof curb).
3. Minimum motor horsepower is 5 hp, maximum motor
horsepower is 20 hp. Maximum RPM is 1379.
4. Max Cfm (for UL approval) as follows: 30 Ton-13,500 Cfm.
5. See RT-EB-104 for further details.

Important: Maximum static pressure
leaving the roof top is 4.0" H 2O
positive.The static pressure drops from the supply fan to the space cannot exceed
4.0"H2O. |