Performance Data 40, 50, 55
Ton
Table 41-1 Supply Fan Performance With VARIABLE
FREQUENCY DRIVE or WITHOUT INLET VANES 40, 50 and 55 Ton
Cfm Std Air |
Total Static Pressure |
.250 |
.500 |
,750 |
1.000 |
1.250 |
1.500 |
1.750 |
2.000 |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
| 8000 |
290 |
.66 |
396 |
1.27 |
479 |
1.95 |
550 |
2.67 |
613 |
3.44 |
671 |
4.23 |
723 |
5.05 |
770 |
5.90 |
| 9000 |
298 |
.77 |
400 |
1.44 |
482 |
2.16 |
553 |
2.93 |
616 |
3.75 |
673 |
4.61 |
725 |
5.49 |
774 |
6.39 |
| 10000 |
311 |
.94 |
404 |
1.61 |
486 |
2.38 |
556 |
3.20 |
618 |
4.07 |
675 |
4.99 |
727 |
5.93 |
776 |
6.89 |
| 11000 |
329 |
1.16 |
409 |
1.79 |
490 |
2.63 |
559 |
3.50 |
621 |
4.41 |
677 |
5.37 |
729 |
6.37 |
778 |
7.40 |
| 12000 |
349 |
1.43 |
414 |
2.00 |
494 |
2.89 |
563 |
3.81 |
624 |
4.77 |
680 |
5.78 |
731 |
6.82 |
780 |
7.90 |
| 13000 |
370 |
1.75 |
424 |
2.26 |
499 |
3.16 |
567 |
4.15 |
628 |
5.16 |
683 |
6.21 |
734 |
7.30 |
782 |
8.43 |
| 14000 |
391 |
2.12 |
438 |
2.60 |
504 |
3.44 |
571 |
4.49 |
632 |
5.57 |
687 |
6.67 |
737 |
7.80 |
785 |
8.97 |
| 15000 |
413 |
2.54 |
455 |
3.01 |
510 |
3.77 |
576 |
4.86 |
636 |
5.99 |
690 |
7.15 |
741 |
8.33 |
789 |
9.55 |
| 16000 |
435 |
3.02 |
474 |
3.50 |
520 |
4.18 |
581 |
5.24 |
640 |
6.43 |
695 |
7.65 |
745 |
8.89 |
792 |
10.16 |
| 17000 |
457 |
3.54 |
494 |
4.06 |
534 |
4.68 |
586 |
5.65 |
645 |
6.89 |
699 |
8.17 |
749 |
9.47 |
796 |
10.79 |
| 18000 |
479 |
4.13 |
515 |
4.68 |
550 |
5.29 |
595 |
6.15 |
650 |
7.37 |
703 |
8.71 |
753 |
10.07 |
800 |
11.46 |
| 19000 |
501 |
4.78 |
536 |
5.38 |
569 |
5.98 |
607 |
6.76 |
656 |
7.89 |
708 |
9.27 |
758 |
10.70 |
804 |
12.14 |
| 20000 |
524 |
5.49 |
558 |
6.15 |
588 |
6.75 |
622 |
7.49 |
664 |
8.50 |
713 |
9.85 |
762 |
11.34 |
809 |
12.84 |
| 21000 |
546 |
6.28 |
580 |
7.00 |
608 |
7.61 |
639 |
8.32 |
676 |
9.25 |
719 |
10.49 |
767 |
12.00 |
813 |
13.57 |
| 22000 |
569 |
7.14 |
602 |
7.92 |
629 |
8.55 |
658 |
9.26 |
690 |
10.12 |
728 |
11.25 |
773 |
12.70 |
818 |
14.32 |
| 22500 |
580 |
7.60 |
613 |
8.40 |
640 |
9.05 |
667 |
9.76 |
698 |
10.60 |
734 |
11.68 |
776 |
13.07 |
820 |
14.70 |
| 23000 |
591 |
8.08 |
624 |
8.90 |
651 |
9.58 |
677 |
10.29 |
706 |
11.11 |
740 |
12.15 |
780 |
13.48 |
823 |
15.09 |
| 24000 |
614 |
9.10 |
646 |
9.97 |
672 |
10.70 |
697 |
11.41 |
724 |
12.22 |
754 |
13.19 |
789 |
14.41 |
829 |
15.93 |
Cfm Std Air |
Total Static Pressure |
2.250 |
2.500 |
2.750 |
3.000 |
3.250 |
3.500 |
3.750 |
4.000 |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
| 8000 |
814 |
6.80 |
854 |
7.73 |
892 |
8.69 |
927 |
9.67 |
961 |
10.66 |
993 |
11.67 |
1023 |
12.69 |
1053 |
13.71 |
| 9000 |
819 |
7.32 |
861 |
8.28 |
901 |
9.27 |
938 |
10.31 |
972 |
11.37 |
1006 |
12.45 |
1037 |
13.55 |
1068 |
14.67 |
| 10000 |
822 |
7.88 |
865 |
8.89 |
906 |
9.92 |
944 |
10.98 |
980 |
12.07 |
1015 |
13.20 |
1048 |
14.35 |
1079 |
15.53 |
| 11000 |
824 |
8.45 |
867 |
9.52 |
908 |
10.61 |
948 |
11.72 |
985 |
12.85 |
1021 |
14.00 |
1055 |
15.18 |
1087 |
16.40 |
| 12000 |
826 |
9.01 |
869 |
10.15 |
910 |
11.30 |
950 |
12.47 |
988 |
13.66 |
1024 |
14.87 |
1059 |
16.09 |
1092 |
17.34 |
| 13000 |
828 |
9.59 |
871 |
10.78 |
912 |
11.99 |
952 |
13.23 |
989 |
14.48 |
1026 |
15.75 |
1061 |
17.04 |
1095 |
18.34 |
| 14000 |
830 |
10.18 |
873 |
11.42 |
914 |
12.69 |
954 |
13.98 |
991 |
15.30 |
1028 |
16.63 |
1063 |
17.98 |
1097 |
19.35 |
| 15000 |
833 |
10.80 |
876 |
12.09 |
917 |
13.40 |
956 |
14.75 |
994 |
16.12 |
1030 |
17.51 |
1065 |
18.92 |
1099 |
20.35 |
| 16000 |
837 |
11.46 |
879 |
12.78 |
920 |
14.14 |
958 |
15.54 |
996 |
16.96 |
1032 |
18.40 |
1067 |
19.87 |
1101 |
21.36 |
| 17000 |
840 |
12.14 |
882 |
13.52 |
923 |
14.92 |
961 |
16.36 |
999 |
17.82 |
1035 |
19.32 |
1069 |
20.83 |
1103 |
22.38 |
| 18000 |
844 |
12.86 |
886 |
14.28 |
926 |
15.73 |
964 |
17.21 |
1002 |
18.72 |
1037 |
20.26 |
1072 |
21.82 |
1106 |
23.41 |
| 19000 |
848 |
13.60 |
890 |
15.08 |
930 |
16.58 |
968 |
18.11 |
1005 |
19.66 |
1040 |
21.24 |
1075 |
22.85 |
1108 |
24.48 |
| 20000 |
852 |
14.36 |
894 |
15.90 |
934 |
17.46 |
972 |
19.04 |
1008 |
20.64 |
1044 |
22.27 |
1078 |
23.92 |
1111 |
25.60 |
| 21000 |
857 |
15.15 |
898 |
16.75 |
938 |
18.37 |
976 |
20.00 |
1012 |
21.66 |
1047 |
23.33 |
1081 |
25.03 |
1114 |
26.75 |
| 22000 |
861 |
15.96 |
902 |
17.63 |
942 |
19.30 |
980 |
20.99 |
1016 |
22.70 |
1051 |
24.43 |
1085 |
26.18 |
1118 |
27.95 |
| 22500 |
864 |
16.38 |
905 |
18.07 |
944 |
19.78 |
982 |
21.50 |
1018 |
23.24 |
1053 |
25.00 |
1087 |
26.77 |
1120 |
28.57 |
| 23000 |
866 |
16.80 |
907 |
18.52 |
946 |
20.26 |
984 |
22.01 |
1020 |
23.78 |
1055 |
25.57 |
1089 |
27.37 |
1122 |
29.19 |
| 24000 |
871 |
17.66 |
912 |
19.45 |
951 |
21.25 |
988 |
23.06 |
1024 |
24.89 |
1059 |
26.73 |
1093 |
28.59 |
1125 |
30.47 |
|
Cfm Std Air |
Total Static Pressure |
4.250 |
4.500 |
4.750 |
5.000 |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
RPM |
BHP |
| 8000 |
1081 |
14.75 |
1108 |
15.78 |
1134 |
16.83 |
1160 |
17.88 |
| 9000 |
1097 |
15.80 |
1125 |
16.94 |
1152 |
18.08 |
|
|
| 10000 |
1109 |
16.73 |
1138 |
17.95 |
1166 |
19.18 |
|
|
| 11000 |
1118 |
17.64 |
1148 |
18.91 |
|
|
|
|
| 12000 |
1124 |
18.61 |
1155 |
19.91 |
|
|
|
|
| 13000 |
1128 |
19.65 |
1159 |
20.99 |
|
|
|
|
| 14000 |
1130 |
20.73 |
1162 |
22.12 |
|
|
|
|
| 15000 |
1132 |
21.80 |
1164 |
23.26 |
|
|
|
|
| 16000 |
1134 |
22.86 |
1166 |
24.39 |
|
|
|
|
| 17000 |
1136 |
23.94 |
1168 |
25.52 |
|
|
|
|
| 18000 |
1138 |
25.03 |
1170 |
26.66 |
|
|
|
|
| 19000 |
1141 |
26.15 |
|
|
|
|
|
|
| 20000 |
1144 |
27.30 |
|
|
|
|
|
|
| 21000 |
1147 |
28.50 |
|
|
|
|
|
|
| 22000 |
1150 |
29.74 |
|
|
|
|
|
|
| 22500 |
1152 |
30.38 |
|
|
|
|
|
|
| 23000 |
1153 |
31.03 |
|
( See
the following page for Fan Performance Chart ) |
| 24000 |
1157 |
32.36 |
|
|
|
|
|
|
Note :
1. Fan performance for 40, 50, and 55 ton rooftops is
identical. However, note maximum motor hp size for each size. Contact your local Trane
representative for information on oversized motors.
2. Shaded areas at table extremes note non-standard Bhp or
Rpm selection. Contact your local Trane representative for more information.
3. Supply fan performance table includes internal
resistance of rooftop. For total static pressure determination, system external static
must be added to appropriate component static pressure drops (evaporator coil, filters,
optional economizer, optional exhaust fan, optional heating system, optional cooling only
extended casing, optional roof curb).
4. Maximum Cfm (for UL approval) as follows:
| 40 Ton |
18,000 Cfm |
| 50 Ton |
22,500 Cfm |
| 55 Ton |
24,000 Cfm |
5. Minimum motor horsepower is 7.5 hp.
6. Maximum motor horsepower as follows:
| 40 Ton |
30 hp |
| 50 Ton |
30 hp |
| 55 Ton |
30 hp |
7. Maximum 7.5 hp through 15 hp motor Rpm is
1,141 Rpm, maximum 20 hp through 30 hp motor Rpm is 1,170 Rpm.
8. See RT-EB-104 for further details. |