 |
Controls |
Variable Air Volume |
VAV Units Only
Sequence Of Operation
NOTE: When noted in this sequence
"Human Interface Panel," the reference is to both the unit mounted and remote mounted Human Interface Panel. All setpoint
adjustments can be accomplished at the unit or Remote
Human Interface Panel.
1
Supply Air Pressure Control
- Inlet Guide Vanes Control
Inlet guide vanes are driven by a modulating 0-10 vdc signal from the Rooftop
Module (RTM). A pressure transducer measures duct
static pressure, and the inlet guide vanes are modulated to maintain the supply air static pressure within an adjustable user-defined
range. The range is determined by the supply air
pressure setpoint and supply air pressure deadband, which are set through the Human Interface Panel.
Inlet guide vane assemblies installed
on the supply fan inlets regulate fan capacity and limit horsepower at lower system air requirements. When in any position
other than full open, the vanes pre-spin intake air in
the same direction as supply fan rotation. As the vanes
approach the full-closed position, the amount of "spin" induced by the vanes increases at the same time that intake airflow and fan horsepower diminish. The inlet
guide vanes will close when the supply fan is shut
down, except during night setback.
- Variable Frequency Drive (VFD)
Control
Variable frequency drives are driven by a modulating 0-10 vdc signal from the Rooftop Module (RTM). A pressure transducer
measures duct static pressure, and the VFD is modulated
to maintain the supply air static pressure within an adjustable user-defined range.
The range is determined by the supply air pressure
setpoint and supply air pressure deadband, which are
set through the Human Interface Panel.
Variable frequency drives provide
supply fan motor speed modulation. The drive will accelerate or decelerate as
required to maintain the supply static pressure
setpoint. When subjected to high ambient return conditions the VFD shall reduce its output frequency to maintain operation. Bypass
control is offered to provide full nominal airflow in
the event of drive failure.
- Supply Air Static Pressure Limit
The opening of the inlet guide vanes and VAV boxes are coordinated during unit
start up and transition to/from Occupied/Unoccupied
modes to prevent overpressurization of the supply air ductwork. However, if for any reason the supply air pressure exceeds the
user-defined supply air static pressure limit that was
set at the Human Interface Panel, the supply fan/
VFD is shut down and the inlet guide vanes (if included) are closed. The unit is
then allowed to restart three times. If the
overpressurization condition occurs on the third time,
the unit is shut down and a manual reset diagnostic is
set and displayed at the Human Interface Panel.
2
Supply Air Temperature Controls
- Cooling/Economizer During Occupied cooling mode of operation,
the economizer (if available) and mechanical cooling
are used to control the supply air temperature. The
supply air temperature setpoint and deadband are user-defined at the Human
Interface Panel. If the enthalpy of the outside air is
appropriate to use "free cooling," the
economizer will be used first to attempt to satisfy the
supply air setpoint; then if required the mechanical cooling will be staged on to maintain supply air temperature setpoint.
Minimum On/Off timing of the mechanical cooling
prevents rapid cycling.
On units with economizer, a call for
cooling will modulate the fresh air dampers open. The rate of economizer modulation
is based on deviation of the discharge temperature from
setpoint, i.e., the further away from setpoint, the
faster the fresh air damper will open. First stage of cooling will be allowed to start after the economizer reaches full open.
Note that the economizer is only
allowed to function freely if ambient conditions are below the enthalpy control
setting or below the return air enthalpy if unit has
comparative enthalpy installed. If outside air is not
suitable for "economizing," the fresh air dampers drive to the minimum open position.
A field adjustable, factory default setting in the
Human Interface Panel or TracerŪ or a remote potentiometer can provide the input to establish the minimum damper position.
At outdoor air conditions above the
enthalpy control setting, mechanical cooling only is used and the fresh air dampers
remain at minimum position.
If the unit does not include an
economizer, mechanical cooling only is used to satisfy cooling requirements.
Outdoor air dampers may be set manually for a maximum
of 25 percent outdoor air, if rooftop is equipped with 0 to 25 percent manual
fresh air damper.
- Heating: Hot Water or Steam
On units with hot water or steam heating, the supply air temperature can be
controlled to a heating set point during the Occupied
mode. The supply air temperature heating set point and deadband are user-defined at the Human Interface Panel. VAV Occupied
heating on hot water and steam heat units is enabled by
closing a field-supplied switch or contacts connected to an changeover input on
the RTM.
- Heating: Modulating Gas Upon a call for heating, the UCM closes
the heating contacts, beginning the firing sequence.
First, the heat exchanger combustion blower begins operation. Upon positive
proving of combustion airflow, a pre-purge cycle is
executed. Then the ignition sequence takes place.
If ignition is not proven, the
ignition transformer is de-energized. After a time delay, another pre-purge cycle takes place, followed by another attempt to
ignite. If ignition fails a second time, the heating
section will be shut down and locked out until manually reset at the unit mounted Human Interface Panel.
As additional heat is required, the
air damper opens, increasing the firing rate.
During heating operation, an electronic flame safety control provides
continuous flame supervision. If combustion should
become unstable for any reason, heating will automatically shut down. After
one minute, another 60 second pre-purge and ignition
cycle begins.
As the heating requirement is satisfied, the UCM will reduce the combustion air and the firing rate will lower
to maintain the desired outlet temperature. When the
requirement is fully satisfied, the heating contacts
|