Trane Company (The) Packaged Rooftop Air Conditioners -RT-DS-9 Packaged Rooftop Air Conditioners - RT-DS-9 - Page 910
| General Data
Table 11-1 General Data 35-40 Tons
| |
35
Ton |
40
Ton |
| Cooling Performance 1 |
|
|
| Nominal Gross
Capacity |
420,000
|
480,000 |
| Natural Gas Heat 2 |
Low |
High |
Low |
High |
| Heating Input (BTUH) |
350,000 |
600,000 |
400,000 |
800,000 |
| First
Stage |
250,000 |
425,000 |
300,000 |
600,000 |
| Heating Output (BTUH)
|
283,500 486,000 |
486,000 |
324,000 |
648,000 |
| First
Stage |
202,500 344,500 |
344,500 |
243,000 |
486,000 |
| Steady State
Efficiency (%)3 |
81.00 |
81.00 |
81.00 |
81.00 |
| No. Burners |
1 |
2 |
1 |
2 |
| No. Stages |
2 |
2 |
2 |
2 |
| Gas Connection Pipe
Size (in.) |
3 /4 |
1 |
3 /4 |
1 |
| Electric Heat |
|
|
|
|
| KW Range5 |
27-90 |
47-108 |
| Capacity Steps |
2 |
2 |
| Compressor |
|
|
| Number/Type |
2/Scroll |
3/Scroll |
| Size (Nominal) |
15 |
15/15/10 |
| Unit Capacity Steps (%) |
100/50 |
100/60/40 |
| Motor RPM |
3450 |
3450 |
| Outdoor Coil Type |
Lanced |
Lanced |
| Tube Size (in.) OD |
3
/8 |
3
/8 |
| Face Area (sq ft) |
51.33 |
69.79 |
| Rows/Fins Per Inch |
2/16 |
2/16 |
| Indoor Coil Type |
Hi-Performance |
Hi-Performance |
| Tube Size (in.) OD |
1
/2 |
1
/2 |
| Face Area |
31.67 |
37.50 |
| Rows/Fins Per Inch |
3/15 |
2/14 |
| Refrigerant Control |
TXV |
TXV |
| No. of Circuits |
1 |
2 |
| Drain Connection No./Size (in) |
1/1.25 |
1/1.25 |
| Type |
PVC |
PVC |
| Outdoor Fan Type |
Propeller |
Propeller |
| No. Used/Diameter |
3/28.00 |
4/28.00 |
| Drive Type/No. Speeds |
Direct/1 |
Direct/1 |
| CFM |
24,800 |
31,700 |
| No. Motors/HP/RPM |
3/1.10/1125 |
4/1.10/1125 |
| Indoor Fan Type |
FC |
FC |
| No. Used |
1 |
1 |
| Diameter/Width (in) |
22.38/22.00 |
25.00/25.00 |
| Drive Type/No. Speeds |
Belt/1 |
Belt/1 |
| No. Motors/HP |
1/7.50/10.00/15.00 |
1/10.00/15.00 |
| Motor RPM |
1760 |
1760 |
| Motor Frame Size |
213/215/254T |
215/254T |
| Exhaust Fan Type |
Propeller |
Propeller |
| No. Used/Diameter
(in) |
2/26.00 |
2/26.00 |
| Drive Type/No. Speeds/Motors |
Direct/2/2 |
Direct/2/2 |
| Motor HP/RPM |
1.0/1075 |
1.0/1075 |
| Motor Frame Size |
48 |
48 |
| Filters Type
Furnished |
Throwaway |
Throwaway |
| No./ Recommended Size (in)6 |
16/16
x 20 x 2 |
17/16
x 20 x 2 |
| Refrigerant Charge (Lbs of
R-22) 4 |
51.50 |
24.50/42.50
per circuit |
| Minimum Outside Air
Temperature For Mechanical Cooling |
0 F |
0 F |
Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering
wet bulb. Gross capacity does not include the effect of fan motor heat. Tested in
accordance with ARI Standard 360.
2. Heating Performance limit settings and rating data were established and approved
under laboratory test conditions using American National Standards Institute standards.
Ratings shown are for elevations up to 4,500 feet.
3. Steady State Efficiency is rated in accordance with DOE test procedures.
4. Refrigerant charge is an approximate value. For a more precise value, see unit
nameplate and service instructions.
5. Maximum KW @ 208V = 41, @ 240V = 54.
6. Filter dimensions listed are nominal. For actual filter and rack sizes see the Unit
Installation, Operation, Maintenance Guide. |
Copyright © 1996–2010 AECinfo.com
|