General Data

 

Table 11-1 — General Data — 35-40 Tons

 

35 Ton

40 Ton

Cooling Performance 1    
  Nominal Gross Capacity

420,000

480,000

Natural Gas Heat 2 Low High Low High
  Heating Input (BTUH) 350,000 600,000 400,000 800,000
    First Stage 250,000 425,000 300,000 600,000
  Heating Output (BTUH) 283,500 486,000 486,000 324,000 648,000
    First Stage 202,500 344,500 344,500 243,000 486,000
  Steady State Efficiency (%)3 81.00 81.00 81.00 81.00
  No. Burners 1 2 1 2
  No. Stages 2 2 2 2
  Gas Connection Pipe Size (in.) 3 /4 1 3 /4 1
Electric Heat        
  KW Range5

27-90

47-108

Capacity Steps

2

2

Compressor    
Number/Type

2/Scroll

3/Scroll

Size (Nominal)

15

15/15/10

Unit Capacity Steps (%)

100/50

100/60/40

Motor RPM

3450

3450

Outdoor Coil — Type

Lanced

Lanced

Tube Size (in.) OD

3 /8

3 /8

  Face Area (sq ft)

51.33

69.79

Rows/Fins Per Inch

  2/16

2/16

Indoor Coil — Type

Hi-Performance

Hi-Performance
Tube Size (in.) OD

1 /2

  1 /2
Face Area

31.67

  37.50
Rows/Fins Per Inch

3/15

2/14
Refrigerant Control

TXV

  TXV
No. of Circuits

1

2
Drain Connection No./Size (in)

1/1.25

1/1.25
Type

PVC

  PVC
Outdoor Fan Type

Propeller

Propeller
No. Used/Diameter

3/28.00

4/28.00
  Drive Type/No. Speeds

Direct/1

Direct/1
CFM

  24,800

31,700
No. Motors/HP/RPM

3/1.10/1125

4/1.10/1125
Indoor Fan Type

FC

FC
No. Used

1

1
Diameter/Width (in)

22.38/22.00

25.00/25.00
Drive Type/No. Speeds

Belt/1

Belt/1
No. Motors/HP

1/7.50/10.00/15.00

1/10.00/15.00
Motor RPM

1760

  1760
  Motor Frame Size

213/215/254T

215/254T
Exhaust Fan Type

Propeller

Propeller
  No. Used/Diameter (in)

2/26.00

2/26.00
Drive Type/No. Speeds/Motors

  Direct/2/2

Direct/2/2
Motor HP/RPM

1.0/1075

1.0/1075
Motor Frame Size

48

48
Filters — Type Furnished

Throwaway

Throwaway
No./ Recommended Size (in)6

16/16 x 20 x 2

17/16 x 20 x 2
Refrigerant Charge (Lbs of R-22) 4

51.50

  24.50/42.50 per circuit
Minimum Outside Air Temperature For Mechanical Cooling

0 F

0 F

  Notes:

1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. Tested in accordance with ARI Standard 360.

2. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 4,500 feet.

3. Steady State Efficiency is rated in accordance with DOE test procedures.

4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

5. Maximum KW @ 208V = 41, @ 240V = 54.

6. Filter dimensions listed are nominal. For actual filter and rack sizes see the Unit Installation, Operation, Maintenance Guide.

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com