   Trane Company (The)  Packaged Rooftop Air Conditioners -RT-DS-9  

Packaged Rooftop Air Conditioners - RT-DS-9 - Page 911

 

 

General Data

 

Table 12-1 — General Data — 50 Ton

  50 Ton
Cooling Performance 1  
 Nominal Gross Capacity 587,000
Natural Gas Heat 2 Low High
Heating Input (BTUH) 400,000 800,000
First Stage 300,000 600,000
Heating Output (BTUH) 324,000 648,000
First Stage 243,000 486,000
Steady State Efficiency (%)3 81.00 81.00
No. Burners 1 2
No. Stages 2 2
Gas Connection Pipe Size (in.) 3 /4 1
Electric Heat  
  KW Range5 41-108
Capacity Steps 2
Compressor  
Number/Type 3/Scroll
Size (Nominal) 15
Unit Capacity Steps (%) 100/67/33
Motor RPM 3450
Outdoor Coil — Type Lanced
Tube Size (in.) OD 3 /8
 Face Area (sq ft) 69.79
Rows/Fins Per Inch 2/16
Indoor Coil — Type Hi-Performance
Tube Size (in.) OD 1 /2
Face Area 37.50
Rows/Fins Per Inch 3/13
Refrigerant Control TXV
No. of Circuits 2
Drain Connection No./Size (in) 1/1.25
Type PVC
Outdoor Fan Type Propeller
No. Used/Diameter 4/28.00
Drive Type/No. Speeds Direct/1
CFM 31,700
No. Motors/HP/RPM 4/1.10/1125
Indoor Fan Type FC
No. Used 1
Diameter/Width (in) 25.00/25.00
Drive Type/No. Speeds Belt/1
No. Motors/HP 1/10.00/15.00/20.00
Motor RPM  1760
Motor Frame Size 215/256T
Exhaust Fan Type Propeller
No. Used/Diameter (in) 2/26.00
Drive Type/No. Speeds/Motors Direct/2/2
Motor HP/RPM 1.0/1075
Motor Frame Size 48
Filters — Type Furnished Throwaway
No./ Recommended Size (in)6 17/16 x 20 x 2
Refrigerant Charge (Lbs of R-22) 4 23.90/49.50 per circuit
Minimum Outside Air Temperature For Mechanical Cooling 0 F

  Notes:

1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. Tested in accordance with ARI Standard 360.

2. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 4,500 feet.

3. Steady State Efficiency is rated in accordance with DOE test procedures.

4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

5. Maximum KW @ 208V = 41, @ 240V = 54.

6. Filter dimensions listed are nominal. For actual filter and rack sizes see the Unit Installation, Operation, Maintenance Guide.

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com