Packaged Rooftop Air Conditioners - RT-DS-9 - Page 911
Packaged Rooftop Air Conditioners -RT-DS-9
| General Data
Table 12-1 General Data 50 Ton
| |
50 Ton |
| Cooling Performance 1 |
|
| Nominal Gross Capacity |
587,000 |
| Natural Gas Heat 2 |
Low |
High |
| Heating Input (BTUH) |
400,000 |
800,000 |
| First Stage |
300,000 |
600,000 |
| Heating Output (BTUH) |
324,000 |
648,000 |
| First Stage |
243,000 |
486,000 |
| Steady State
Efficiency (%)3 |
81.00 |
81.00 |
| No. Burners |
1 |
2 |
| No. Stages |
2 |
2 |
| Gas Connection Pipe
Size (in.) |
3 /4 |
1 |
| Electric Heat |
|
|
| KW Range5 |
41-108 |
| Capacity Steps |
2 |
| Compressor |
|
| Number/Type |
3/Scroll |
| Size (Nominal) |
15 |
| Unit Capacity Steps
(%) |
100/67/33 |
| Motor RPM |
3450 |
| Outdoor Coil
Type |
Lanced |
| Tube Size (in.) OD |
3 /8 |
| Face Area (sq
ft) |
69.79 |
| Rows/Fins Per Inch |
2/16 |
| Indoor Coil
Type |
Hi-Performance |
| Tube Size (in.) OD |
1 /2 |
| Face Area |
37.50 |
| Rows/Fins Per Inch |
3/13 |
| Refrigerant Control |
TXV |
| No. of Circuits |
2 |
| Drain Connection
No./Size (in) |
1/1.25 |
| Type |
PVC |
| Outdoor Fan Type |
Propeller |
| No. Used/Diameter |
4/28.00 |
| Drive Type/No. Speeds |
Direct/1 |
| CFM |
31,700 |
| No. Motors/HP/RPM |
4/1.10/1125 |
| Indoor Fan Type |
FC |
| No. Used |
1 |
| Diameter/Width (in) |
25.00/25.00 |
| Drive Type/No. Speeds |
Belt/1 |
| No. Motors/HP |
1/10.00/15.00/20.00 |
| Motor RPM |
1760 |
| Motor Frame Size |
215/256T |
| Exhaust Fan Type |
Propeller |
| No. Used/Diameter (in) |
2/26.00 |
| Drive Type/No.
Speeds/Motors |
Direct/2/2 |
| Motor HP/RPM |
1.0/1075 |
| Motor Frame Size |
48 |
| Filters
Type Furnished |
Throwaway |
| No./ Recommended Size
(in)6 |
17/16 x 20 x 2 |
| Refrigerant Charge (Lbs
of R-22) 4 |
23.90/49.50 per circuit |
| Minimum Outside Air
Temperature For Mechanical Cooling |
0 F |
Notes:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering
wet bulb. Gross capacity does not include the effect of fan motor heat. Tested in
accordance with ARI Standard 360.
2. Heating Performance limit settings and rating data were established and approved
under laboratory test conditions using American National Standards Institute standards.
Ratings shown are for elevations up to 4,500 feet.
3. Steady State Efficiency is rated in accordance with DOE test procedures.
4. Refrigerant charge is an approximate value. For a more precise value, see unit
nameplate and service instructions.
5. Maximum KW @ 208V = 41, @ 240V = 54.
6. Filter dimensions listed are nominal. For actual filter and rack sizes see the Unit
Installation, Operation, Maintenance Guide. |