Trane Company (The)
Packaged Rooftop Air Conditioners -RT-DS-9
Packaged Rooftop Air Conditioners - RT-DS-9 - Page 914
Packaged Rooftop Air Conditioners -RT-DS-9
Selection of Trane commercial air conditioners is divided into five basic areas: 1 Cooling capacity 2 Heating capacity 3 Air delivery 4 Unit electrical requirements 5 Unit designation Factors Used In Unit Cooling Selection: 1 Summer design conditions 95 DB/76 WB, 95 F entering air to condenser. 2 Summer room design conditions 76 DB/66 WB. 3 Total peak cooling load 321 MBh (27.75 tons). 4 Total peak supply cfm 12,000 cfm. 5 External static pressure 1.0 inches. 6 Return air temperatures 80 DB/66 WB. 7 Return air cfm 4250 cfm. 8 Outside air ventilation cfm and load 1200 cfm and 18.23 MBh (1.52 tons). 9 Unit accessories include: a Aluminized heat exchanger high heat module. b 2" Hi-efficiency throwaway filters. c Exhaust fan. d Economizer cycle.
Step 1 A summation of the peak cooling load and the outside air ventilation load shows: 27.75 tons + 1.52 tons = 29.27 required unit capacity. From Table 18-2, 30-ton unit capacity at 80 DB/67 WB, 95 F entering the condenser and 12,000 total peak supply cfm, is 30.0 tons. Thus, a nominal 30-ton unit is selected. Step 2 Having selected a nominal 30-ton unit, the supply fan and exhaust fan motor bhp must be determined. Supply Air Fan: Determine unit static pressure at design supply cfm: External static pressure 1.20inches Heat exchanger (Table 24-1) .14inches High efficiency filter 2" (Table24-1) .09inches Economizer (Table24-1) .076inches Unit total static pressure 1.50 inches Using total cfm of 12,000 and total static pressure of 1.50 inches, enter Table 22-1. Table 22-1 shows 7.27 bhp with 652 rpm. Step 3 Determine evaporator coil entering air conditions. Mixed air dry bulb temperature determination. Using the minimum percent of OA (1,200 cfm ÷ 12,000 cfm = 10 percent), determine the mixture dry bulb to the evaporator. RADB + %OA (OADB -RADB) = 80 + (0.10) (95 - 80) = 80 + 1.5 = 81.5F Approximate wet bulb mixture temperature: RAWB + OA (OAWB - RAWB) = 66 + (0.10) (76-66) = 68 + 1 = 67 F. A psychrometric chart can be used to more accurately determine the mixture temperature to the evaporator coil. Step 4 Determine total required unit cooling capacity: Required capacity = total peak load + O.A. load + supply air fan motor heat. From Figure 16-1, the supply air fan motor heat for 7.27 bhp = 20.6 MBh. Capacity = 321 + 18.23 + 20.6 = 359.8 MBh (30 tons) Step 5 Determine unit capacity: From Table 18-2 unit capacity at 81.5 DB. 67 WB entering the evaporator, 12000 supply air cfm, 95 F entering the condenser is 361 MBh (30.1 tons) 279 sensible MBh. Step 6 Determine leaving air temperature: Unit sensible heat capacity, corrected for supply air fan motor heat 279 - 20.6 = 258.4 MBh. Supply air dry bulb temperature difference = 258.4 MBh ÷ (1.085 x 12,000 cfm) = 19.8 F. Supply air dry bulb: 81.5 - 19.8 = 61.7. Unit enthalpy difference = 361 ÷ (4.5 x 12,000) = 6.7 Btu/lb leaving enthalpy = h (ent WB) = 31.62 Leaving enthalpy = 31.62 Btu/lb -6.7 Btu/lb = 24.9 Btu/lb. From Table 17-1, the leaving air wet bulb temperature corresponding to an enthalpy of 24.9 Btu/lb = 57.5. Leaving air temperatures = 61.7 DB/57.5 WB |




