Performance Adjustment Factors

Table 17-1— Enthalpy of Saturated AIR

Wet Bulb Temperature Btu Per Lb.
40 15.23
41 15.70
42 16.17
43 16.66
44 17.15
45 17.65
46 18.16
47 18.68
48 19.21
49 19.75
50 20.30
51 20.86
52 21.44
53 22.02
54 22.62
55 23.22
56 23.84
57 24.48
58 25.12
59 25.78
60 26.46
61 27.15
62 27.85
63 28.57
64 29.31
65 30.06
66 30.83
67 31.62
68 32.42
69 33.25
70 34.09
71 34.95
72 35.83
73 36.74
74 37.66
75 38.61

Table 17-2 — Cooling Capacity Altitude CorrectionFactors

 

Altitude (Ft.)

  Sea Level 1000 2000 3000 4000 5000 6000 7000
Cooling Capacity Multiplier 1.00 0.99 0.99 0.98 0.97 0.96 0.95 0.94
KW Correction Multiplier (Compressors) 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07
SHR Correction Multiplier 1.00 .98 .95 .93 .91 .89 .87 .85
Maximum Condenser Ambient 115F 114F 113F 112F 111F 110F 109F 108F

Note:

SHR = Sensible Heat Ratio

 

Air Density Ratio
(Density at New Air
Density Condition Std.)

Figure 17-1 — Air Density Ratios

Table 17-3 — Gas Heating Capacity Altitude Correction Factors

 

Altitude (Ft.)

Sea Level To 2000 2001 To 2500 2501 To 3500 3501 To 4500 4501 To 5500 5501 To 6500 6501 To 7500
Capacity Multiplier 1.00 .92 .88 .84 .80 .76 .72

Note:

Correction factors are per AGA Std 221.30 — 1964, Part VI, 6.12. Local codes may supersede.