| Performance Data Table 21-1 Electric Heat Air Temperature Rise
Notes: 1. Air temperature rise = (KW x 3413)/(scfm x 1.085). 2. All heaters on constant volume units provide 2 increments of capacity. All VAV units provide 1 step of heating capacity. 3. Air temperature rise in this table are based on heater operating at 240, 480 or 600 volts. Table 21-2 Available Electric Heat KW Ranges
Notes: 1. KW ranges in this table are based on heater operating at 208, 240, 480, and 600 volts. 2. For other than rated voltage, KW = (Applied Voltage/Rated Voltage)2 x Rated KW. 3. Electric heaters up to 54 KW are single element heaters, those above 54 KW are dual element heaters. Table 21-3 Natural Gas Heating Capacities
Note: 1. Second stage is total heating capacity. Second Stage/First Stage. |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||