Performance Data

Table 22-1 — Supply Fan Performance — 27.5 - 35 Ton

Static Pressure (in. wg)1

0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25
SCFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
8000 341 1.39 401 1.85 451 2.30 501 2.84 552 3.45 599 4.11 644 4.80 686 5.51 726 6.24
8500 355 1.60 412 2.08 462 2.58 508 3.09 556 3.71 602 4.38 646 5.09 688 5.83 728 6.59
9000 368 1.84 423 2.35 473 2.88 516 3.39 561 4.00 606 4.68 649 5.41 691 6.16 730 6.94
9500 382 2.10 435 2.64 484 3.20 526 3.73 568 4.32 611 5.00 653 5.74 694 6.51 732 7.31
10000 396 2.39 448 2.96 495 3.53 537 4.12 576 4.69 616 5.36 657 6.11 697 6.89 735 7.71
10500 410 2.71 461 3.31 506 3.89 549 4.53 585 5.10 623 5.76 662 6.50 701 7.30 738 8.13
11000 425 3.07 474 3.68 518 4.29 560 4.95 597 5.57 631 6.20 668 6.93 705 7.73 742 8.58
11500 440 3.46 488 4.08 530 4.72 571 5.39 608 6.08 641 6.71 676 7.41 711 8.20 747 9.06
12000 455 3.89 501 4.52 542 5.19 582 5.86 619 6.60 652 7.27 684 7.95 718 8.73 752 9.57
12500 470 4.34 515 4.98 555 5.69 593 6.38 630 7.13 664 7.87 694 8.55 726 9.30 758 10.14
13000 485 4.84 528 5.47 569 6.23 605 6.94 641 7.69 675 8.49 706 9.21 734 9.93 765 10.76
13500 501 5.36 542 6.00 582 6.79 617 7.54 652 8.29 686 9.12 717 9.91 745 10.65 774 11.43
14000 516 5.91 555 6.58 595 7.40 630 8.18 664 8.95 697 9.78 729 10.64 757 11.42 784 12.19
14500 532 6.51 570 7.20 609 8.04 643 8.85 676 9.65 708 10.48 740 11.38 768 12.22 795 13.02

Notes:

1. Fan performance table includes internal resistances of cabinet, and 2" standard filters. For other components refer to component static pressure drop table. Add the pressure drops from any additional components to the duct (external) static pressure, enter the table, and select motor bhp.

2. The pressure drop from the supply fan to the space cannot exceed 2.25".

3. Maximum air flow for 27.5 ton — 12,100 cfm, 30 ton — 13,200 cfm, 35 ton — 14,400 cfm.

4. Maximum motor horsepower for 27.5 ton — 10 hp, 30 ton — 10 hp, 35 ton — 15 hp.

 

Request for Information / Request a Catalog from Trane Company (The)
 
 
 
To request more information from Trane Company (The), please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2009 AECinfo.com