| Performance Data Table 25-1 Supply Air Fan Drive Selections
| |
7.5HP |
10HP |
15HP |
20HP |
| Nominal |
|
Drive |
|
Drive |
|
Drive |
|
Drive |
| Tons |
RPM |
No |
RPM |
No |
RPM |
No |
RPM |
No |
| |
550 |
A |
|
|
|
|
|
|
| |
600 |
B |
|
|
|
|
|
|
| 27.5T |
650 |
C |
|
|
|
|
|
|
| |
700 |
|
700 |
D |
|
|
|
|
| |
750 |
750* |
E |
|
|
|
|
|
| |
550 |
A |
|
|
|
|
|
|
| |
600 |
B |
|
|
|
|
|
|
| 30T |
650 |
C |
|
|
|
|
|
|
| |
700 |
|
700 |
D |
|
|
|
|
| |
750 |
|
750 |
E |
|
|
|
|
| |
600 |
B |
|
|
|
|
|
|
| |
650 |
|
650 |
C |
|
|
|
|
| 35T |
|
700 |
700 |
D |
|
|
|
|
| |
790 |
|
|
|
790** |
F |
|
|
| |
800 |
|
|
|
800* |
G |
|
|
| |
500 |
|
500 |
H |
|
|
|
|
| |
525 |
525 |
J |
|
|
|
|
|
| |
575 |
575 |
K |
|
|
|
|
|
| 40T |
625 |
|
|
625 |
L |
|
|
|
| |
675 |
|
|
675 |
M |
|
|
|
| |
725 |
|
|
725 |
N |
|
|
|
| |
525 |
|
525 |
J |
|
|
|
|
| |
575 |
|
575 |
K |
|
|
|
|
| 50T |
625 |
|
|
625 |
L |
|
|
|
| |
675 |
|
|
675 |
M |
|
|
|
| |
725 |
|
|
|
|
725 |
N |
|
Note:
*For YC gas/electrics only.
**For TC and TE Cooling only and with electric heat units
only.
Table 25-2 Power Exhaust Fan Performance
| Exhaust |
ExternalStaticPressureInchesofWater |
|
|
| Airflow |
HighSpeed |
MedSpeed |
LowSpeed |
| (Cfm) |
ESP |
ESP |
ESP |
| 3500 |
0.900 |
|
|
| 4000 |
0.860 |
|
|
| 4500 |
0.820 |
|
|
| 5000 |
0.780 |
|
0.400 |
| 5500 |
0.745 |
|
0.380 |
| 6000 |
0.700 |
|
0.360 |
| 6500 |
0.660 |
|
0.330 |
| 7000 |
0.610 |
0.400 |
0.300 |
| 7500 |
0.560 |
0.365 |
0.260 |
| 8000 |
0.505 |
0.330 |
0.215 |
| 8500 |
0.445 |
0.300 |
0.170 |
| 9000 |
0.385 |
0.255 |
0.120 |
| 9500 |
0.320 |
0.210 |
0.070 |
| 10000 |
0.255 |
0.165 |
0.020 |
| 10500 |
0.190 |
0.125 |
|
| 11000 |
0.125 |
0.060 |
|
| 11500 |
0.065 |
0.000 |
|
| 12000 |
0.005 |
|
|
Notes:
1. Performance in table is with both motors operating.
2. High speed = both motors on high speed. Medium speed is
one motor on high speed and one on low speed. Low speed is both motors on low speed.
3. Power Exhaust option is not to be applied on systems
that have more return air static pressure drop than the maximum shown in the table for
each motor speed tap. |