| ControlsControl Sequences of Operation Common to Both VAV and CV Units
Ventilation override (VOM)
Ventilation override allows an external system to assume
control of the unit for the purpose of exhaust or pressurization. There are two inputs
associated with ventilation override, the initiate input and the select input. When the
UCP senses a continuous closed condition on the initiate input at the low voltage terminal
board the unit will begin ventilation override depending on the condition of the select
input. The default condition of the select input is exhaust (input open). A closed select
input will yield pressurization. The component state matrix for ventilation override is as
follows:
| System Component |
Exhaust |
Pressurization |
| Heat/Cool |
off |
off |
| IGV |
closed |
open |
| Supply Fan |
off |
on |
| Exhaust Fan |
on |
off |
| Outside Air Damper |
closed |
open |
| Return Air Damper |
open |
closed |
| VAV Boxes |
n/a |
open |
Coil Freeze Protection FROSTAT
The FROSTAT system eliminates the need for hot gas bypass
and adds a suction line surface temperature sensor to determine if the coil is in a
condition of impending frost. If impending frost is detected primary cooling capacity is
shed as necessary to prevent icing. All compressors are turned off after they have met
their minimum 3 minute on times. The supply fan is forced on until the FROSTAT device no
longer senses a frosting condition or for 60 seconds after the last compressor is shut
off, whichever is longer.
Occupied/Unoccupied Switching
There are 3 ways to switch Occupied/Unoccupied:
1
NSB Panel
2
Electronic time clock or field-supplied contact closure
3
TRACER
Night Setback Sensors
Tranes night setback sensors are programmable with a
time clock function that provides communication to the rooftop unit through a 2-wire
communications link. The desired transition times are programmed at the night setback
sensor and communicated to the unit.
Night setback (unoccupied mode) is operated through the
time clock provided in the sensors with night setback. When the time clock switches to
night setback operation, the outdoor air dampers close and heating/cooling can be enabled
or disabled. As the building load changes, the night setback sensor communicates the need
for the rooftop heating/cooling (if enabled) function and the evaporator fan. The rooftop
unit will cycle through the evening as heating/cooling (if enabled) is required in the
space. When the time clock switches from night setback to occupied mode, all
heating/cooling functions begin normal operation.
When using the night setback options with a VAV
heating/cooling rooftop, airflow must be maintained through the rooftop unit. This can be
accomplished by electrically tying the VAV boxes to the VAV heat relay contacts on
the Low voltage terminal board or by using changeover thermostats. Either of these
methods will assure adequate airflow through the unit and satisfactory temperature control
of the building.
Timed override ActivationICS
When this function is initiated by pushing the override
button on the ICS sensor, TRACER will switch the unit to the occupied mode. Unit
operation (occupied mode) during timed override is terminated by a signal from TRACER.
Timed override ActivationNon-lCS
When this function is initiated by the push of an override
button on the programmable zone sensor, the unit will switch to the occupied mode.
Automatic Cancellation of the Timed override Mode occurs after three hours of operation.
Comparative Enthalpy Control of Economizer
The Unitary Economizer Module (UEM) receives inputs from
optional return air humidity and temperature sensors and determines whether or not it is
feasible to economize. If the outdoor air enthalpy is greater than the return air enthalpy
then it is not feasible to economize and the economizer damper will not open past its
minimum position.
Fan Failure Switch
The fan failure switch will disable all unit functions and
"flash" the Service LED on the zone sensor.
Emergency Stop Input
A binary input is provided on the UCP for installation of
field provided switch or contacts for immediate shutdown of all unit functions. The binary
input is brought out to Low Voltage Terminal Board One (LTB1). |