Weights |
Table 34-1 Approximate Operating Weights
Lbs.2
| |
Basic UnitWeights (1) |
| Unit |
YC |
YC |
TC |
TE |
| Model |
Low Heat |
High Heat |
|
|
| **D330 |
3650 |
4012 |
3520 |
3553 |
| **H330 |
3650 |
4077 |
3565 |
3598 |
| **D360 |
3730 |
4092 |
3600 |
3633 |
| **H360 |
3730 |
4142 |
3600 |
3633 |
| **D420 |
3815 |
4177 |
3685 |
3718 |
| **H420 |
3815 |
4227 |
3685 |
3718 |
| **D480 |
4665 |
4785 |
4440 |
4475 |
| **H480 |
4690 |
4815 |
4440 |
4475 |
| **D600 |
4835 |
4955 |
4610 |
4645 |
| **H600 |
4860 |
4985 |
4610 |
4645 |
Notes:
1. Basic unit weight includes minimum HP Supply Fan motor.
2. Optional high static and high efficiency motor weights
are in
addition to the standard motor weight included in the basic
unit
weight.
Table 34-2 Point Loading Percentage of Total
Unit Weight1

| POINT LOADING-% OF TOTAL
UNIT WEIGHT |
| A |
B |
C |
D |
E |
F |
| 21 |
23 |
12 |
16 |
17 |
12 |
1. Point Loading is identified
with corner A being the corner with the compressors. As you move clockwise around the unit
as viewed from the top, mid-point B, corner C, corner D, mid-point E and corner F.
Table 34-3 Component Weights
Weights
of Optional Components |
| |
|
|
Hi-Static/ |
|
|
|
Variable
Frequency Drives(VFDs) |
|
|
|
Factory |
Roof Curb
Weights |
| |
|
|
Hi-Eff |
0-25% |
|
Inlet |
|
Thru-the |
Non-Fused |
GFI with |
| Unit |
Barometric |
Power |
Supply Fan |
Manual |
|
Guide |
Service |
Base |
Disconnect |
Disconnect |
| Model |
Relief |
Exhaust |
Motors(2) |
Damper |
Econo |
Vanes |
W/O Bypass |
With Bypass |
Valves |
Electric |
Switch |
Switch |
Lo |
Hi |
| **D330 |
110 |
165 |
120 |
50 |
260 |
55 |
85 |
115 |
11 |
6 |
30 |
85 |
310 |
330 |
| **H330 |
145 |
200 |
120 |
50 |
285 |
55 |
85 |
115 |
11 |
6 |
30 |
85 |
310 |
330 |
| **D360 |
110 |
165 |
120 |
50 |
260 |
55 |
85 |
115 |
11 |
6 |
30 |
85 |
310 |
330 |
| **H360 |
145 |
200 |
120 |
50 |
285 |
55 |
85 |
115 |
11 |
6 |
30 |
85 |
310 |
330 |
| **D420 |
110 |
165 |
120 |
50 |
260 |
55 |
115 |
150 |
11 |
6 |
30 |
85 |
310 |
330 |
| **H420 |
145 |
200 |
120 |
50 |
285 |
55 |
115 |
150 |
11 |
6 |
30 |
85 |
310 |
330 |
| **D480 |
110 |
165 |
125 |
50 |
290 |
70 |
115 |
150 |
18 |
6 |
30 |
85 |
365 |
| **H480 |
145 |
200 |
125 |
50 |
300 |
70 |
115 |
150 |
18 |
6 |
30 |
85 |
365 |
| **D600 |
110 |
165 |
125 |
50 |
290 |
70 |
115 |
150 |
18 |
6 |
30 |
85 |
365 |
| **H600 |
145 |
200 |
125 |
50 |
300 |
70 |
115 |
150 |
18 |
6 |
30 |
85 |
365 |
Table 34-4 Minimum Operating
Clearances for Unit Installation
| |
|
CondenserCoil2 |
ServiceSide |
| |
Econo/ExhaustEnd |
End/Side |
Access |
| SingleUnit1 |
6Feet |
8Feet/4Feet |
4Feet |
| MultipleUnit1,3 |
12Feet |
16Feet/8Feet |
8Feet |
Notes:
1. Horizontal and Downflow Units, all sizes.
2. Condenser coil is located at the end and side of the
unit.
3. Clearances on multiple unit installations are distances
between units. |