| Performance Data
ARI
ARI cooling performance is based on 80/67 F (27/19 C)
entering air temperature, 45 F (7 C) entering chilled water temperature wit a 10 F (5.5 C)
delta T.
Heating performance is based on 70 F (21 C) entering air
temperature, 180 F (82 C) entering hot water temperature with a 30 F (17 C) delta T.
All performance measured on high speed tap, 115 V,
0.2" zero ESP, with a throwaway filter. See page 14 for performance groupings.
Table PD-3 - Free Discharge
Motor, Two-Pipe, Group 3
| |
|
|
|
Cooling |
|
|
|
|
Heating |
|
|
|
|
| |
|
CFM |
TMBH |
SMBH |
GPM |
WPD |
TMBH |
|
GPM |
VVPD |
115V |
230V |
277V |
| FC |
Coil |
(L/s) |
(TkW) |
(SkW) |
(L/s) |
(kPa) |
(TkW) |
QATD |
(L/s) |
(kPa) |
Watt |
Watt |
Watt |
| 2 |
2CH |
198 (93) |
4.8 (1.4) |
3.7 (1.1) |
1.00 (0.06) |
5.7 (17.1) |
13.8 (4.1) |
.13 |
0.92 (0.06) |
3.8 (11.3) |
60 |
95 |
65 |
| |
3CH |
188 (90) |
6.5 (1.9) |
4.5 (1.3) |
1.34 (0.08) |
14.4 (43.1) |
16.7 (4.9) |
.15 |
1.11 (0.07) |
8.0 (23.8) |
60 |
95 |
65 |
| |
4CH |
177 (84) |
6.5 (1.9) |
4.5 (1.3) |
1.34 (0.08) |
3.5 (10.4) |
17.3 (5.1) |
.16 |
1.16 (0.07) |
2.2 (6.4) |
60 |
95 |
65 |
| 3 |
2CH |
262 (124) |
6.1 (1.8) |
4.6 (1.3) |
1.28 (0.08) |
9.7 (29.1) |
18.3 (5.4) |
.17 |
1.22 (0.08) |
6.9 (20.6) |
70 |
80 |
83 |
| |
3CH |
260 (123) |
7.3 (2.1) |
5.4 (1.6) |
1.51 (0.10) |
3.7 (11.1) |
22.1 (6.5) |
.20 |
1.47 (0.09) |
2.9 (8.7) |
85 |
89 |
101 |
| |
4CH |
242 (114) |
8.8 (2.6) |
6.0 (1.8) |
1.82 (0.11) |
6.6 (19.6) |
23.7 (6.9) |
.22 |
1.58 (0.10) |
4.1 (12.3) |
85 |
89 |
101 |
| 4 |
2CH |
330 (156) |
7.8 (2.3) |
6.2 (1.8) |
1.63 (0.10) |
3.5 (10.4) |
22.8 (6.7) |
.21 |
1.52 (0.10) |
2.6 (7.7) |
95 |
96 |
104 |
| |
3CH |
320 (151) |
10.6 (3.1) |
7.4 (2.2) |
2.19 (0.14) |
8.2 (24.5) |
28.1 (8.2) |
.26 |
1.87 (0.12) |
5.1 (15.2) |
100 |
107 |
106 |
| |
4CH |
304 (144) |
12.0 (3.5) |
8.0 (2.3) |
2.47 (0.16) |
12.9 (38.7) |
30.3 (8.9) |
.28 |
2.02 (0.13) |
7.3 (21.9) |
100 |
107 |
106 |
| 6 |
2CH |
512 (242) |
13.5 (4.0) |
10.0 (2.9) |
2.77 (0.17) |
11.0 (32.9) |
35.8 (10.5) |
.33 |
2.38 (0.15) |
7.0 (21.0) |
110 |
154 |
165 |
| |
3CH |
508 (240) |
14.9 (4.4) |
11.1 (3.3) |
3.07 (0.19) |
4.1 (12.3) |
43.3 (12.7) |
.39 |
2.88 (0.18) |
3.3 (9.7) |
125 |
130 |
124 |
| |
4CH |
483 (228) |
17.7 (5.2) |
12.1 (3.5) |
3.62 (0.23) |
6.6 (19.7) |
47.2 (13.8) |
.43 |
3.14 (0.20) |
4.4 (13.3) |
125 |
130 |
124 |
| 8 |
2CH |
665 (314) |
14.7 (4.3) |
11.9 (3.5) |
3.04 (0.19) |
3.6 Ti o. 6-) |
5.0 (13.2) |
.41 |
3.00 (0.19) |
3.2 (9.4) |
135 |
150 |
159 |
| |
3CH |
623 (294) |
19.1 (5.6) |
13.5 (4.0) |
3.90 (0.25) |
7.1 (21.2) |
54.3 (15.9) |
.49 |
3.62 (0.23) |
5.5 (16.3) |
120 |
123 |
133 |
| 8 |
4CH |
596 (282) |
21.2 (6.2) |
14.3 (4.2) |
4.32 (0.27) |
10.3 (30.7) |
59.2 (17.3) |
.54 |
3.94 (0.25) |
7.5 (22.4) |
120 |
123 |
133 |
| 10 |
2CH |
829 (391) |
20.5 (6.0) |
15.7 (4.6) |
4.25 (0.27) |
7.3 (21.8) |
57.5 (16.9) |
.52 |
3.83 (0.24) |
5.5 (16.3) |
205 |
250 |
269 |
| |
3CH |
835 (394) |
26.4 (7.7) |
18.4 (5.4) |
5.43 (0.34) |
14.6 (43.7) |
72.9 (21.3) |
.66 |
4.86 (0.31) |
10.5 (31.2) |
225 |
237 |
230 |
| |
4CH |
796 (376) |
27.9 (8.2) |
18.6 (5.4) |
5.73 (0.36) |
19.5 (58.3) |
79.0 (23.1) |
.72 |
5.26 (0.33) |
14.4 (42.9) |
225 |
237 |
230 |
| 12 |
2CH |
940 (444) |
24.9 (7.3) |
18.4 (5.4) |
5.13 (0.32) |
11.1 (33.3) |
66.5 (19.5) |
.60 |
4.43 (0.28) |
7.6 (22.8) |
230 |
246 |
263 |
| |
3CH |
923 (436) |
29.1 (8.5) |
20.6 (6.0) |
5.96 (0.38) |
10.6 (31.7) |
80.6 (23.6) |
.73 |
5.37 (0.34) |
8.2 (24.6) |
220 |
230 |
239 |
| |
4CH |
876 (413) |
34.5 (10.1) |
22.5 (6.6) |
7.04 (0.44) |
14.7 (44.0) |
87.9 (25.8) |
.80 |
5.86 (0,37) |
9.4 (28.2) |
220 |
230 |
239 |
Table PD-4 -
Free Discharge Motor, Two-Pipe, Group 4
| Cooling |
Heating |
| |
|
CFM |
TMBH |
SMBH |
GPM |
WPD |
TMBH |
|
GPM |
WPD |
115V |
| FC |
Coil |
(L/s) |
(TkW) |
(SkW) |
(L/s) |
(kPa) |
(TkW) |
Q/ITD |
(L/s) |
(kPa) |
Watt |
| 3 |
2CH |
300 (142) |
6.8 (2.0) |
5.4 (1.6) |
1.36 (0.09) |
2.5 (7.5) |
21.2 (6.2) |
.19 |
1,41 (0.09) |
2.3 (6.7) |
86 |
| |
3CH |
270 (128) |
7.8 (2.3) |
5.5 (1.6) |
1.56 (0.10) |
4.5 (13.4) |
24.4 (7.1) |
.22 |
1.62 (0.10) |
3.9 (11.7) |
86 |
| 4 |
2CH |
380 (179) |
10.7 (3.1) |
7.7 (2.3) |
2.14 (0.13) |
6.9 (20.7) |
28.3 (8.3) |
.26 |
1.89 (0.12) |
4.6 (13.7) |
98 |
| |
3CH |
350 (165) |
10.0 (3.0) |
7.4 (2.2) |
2.00 (0.13) |
1.9 (5.5) |
31.5 (9.2) |
.29 |
2.10 (0.13) |
1.8 (5.4) |
98 |
| 6 |
2CH |
620 (293) |
13.6 (4.0) |
11.1 (3.3) |
2.71 (0.17) |
2.9 (8.6) |
42.8 (12.5) |
.39 |
2.85 (0.18) |
2.9 (8.6) |
105 |
| |
3CH |
570 (269) |
16.4 (4.8) |
11.7 (3.4) |
3.28 (0.21) |
5.2 (15.4) |
50.5 (14.8) |
.46 |
3.36 (0.21) |
4.8 (14.2) |
105 |
Note:
- CFM Cubic feet per minute
- TMBH = Total capacity (MBH)
- GPM = Gallons per minute
- WPD = Water pressure drop (feet of water)
- Q/ITD = MBH (kW)/(Entering water temperature - Entering air
temperature) when delta T and GPM (L/s) remain constant. To determine heating capacities
at a different entering water temperature or entering air temp, compute the new ITD and
multiply it by the Q/ITD shown.
- Medium and low speed capacities are approximately 80 percent
and 60 percent respectively of the high speed capacity.
|