| Search |
|
|
|
| |
| Site Navigation |
|
|
|
| News / Publications |
|
|
|
| Jobs | |
|
|
| Service |
|
|
|
|
|


|
| |
|
| |
Trane Company (The) UniTrane Fan-Coil UniTrane Fan-Coil - Page 20
| Performance Data Hot Water Reheat CoilThe following performance
data represents the 1-row hot water and steam reheat coils that are available on fan-coil
units in conjunction with a 2, 3 or 4-row cooling coil. Heating performance is based on 70
F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 20 F
(-7 C) delta T.
All performance measured on high
speed tap, 115 V, zero ESP, with a throwaway filter. See page 14 for performance
groupings.
Table PD-15 Free Discharge Motor,Group 1
|
Main Coil |
TMBH |
|
GPM |
WPD |
| FC |
Rows |
(TkW) |
Q/ITD |
(L/s) |
(Pa) |
|
2 |
2.9(.8) |
0.03 |
0.3(.02) |
0.01(30) |
| 02 |
3 |
2.8(.8) |
0.03 |
0.3(.02) |
0.01(30) |
|
4 |
2.7(.8) |
0.02 |
0.3(.02) |
0.01(30) |
|
2 |
4.1(1.2) |
0.04 |
0.4(.03) |
0.02(60) |
| 03 |
3 |
4.0(1.2) |
0.04 |
0.4(.03) |
0.02(60) |
|
4 |
3.8(1.1) |
0.04 |
0.4(.03) |
0.02(60) |
|
2 |
5.6(1.6) |
0.05 |
0.6(.04) |
0.04(120) |
| 04 |
3 |
5.6(1.6) |
0.05 |
0.6(.04) |
0.04(120) |
|
4 |
5.3(1.6) |
0.05 |
0.5(.03) |
0.03(90) |
|
2 |
9.3(2.7) |
0.09 |
0.9(.06) |
0.10(299) |
| 06 |
3 |
9.3(2.7) |
0.09 |
0.9(.06) |
0.10(299) |
|
4 |
8.9(2.6) |
0.08 |
0.9(.06) |
0.09(269) |
|
2 |
12.5(3.7) |
0.11 |
1.2(.08) |
0.18(538) |
| 08 |
3 |
11.9(3.5) |
0.11 |
1.2(.08) |
0.17(508) |
|
4 |
11.4(3.3) |
0.10 |
1.1(.07) |
0.16(478) |
|
2 |
16.1(4.7) |
0.15 |
1.6(.10) |
0.32(957) |
| 10 |
3 |
16.2(4.7) |
0.15 |
1.6(.10) |
0.32(957) |
|
4 |
15.6(4.6) |
0.14 |
1.6(.10) |
0.30(897) |
|
2 |
18.8(5.5) |
0.17 |
1.9(.12) |
0.45(1350) |
| 12 |
3 |
18.5(5.4) |
0.17 |
1.8(.11) |
0.44(1320) |
|
4 |
17.8(5.2) |
0.16 |
1.8(.11) |
0.40(1200) |
Table PD-16
Free Discharge Motor,Group 2
|
Main Coil |
TMBH |
|
GPM |
WPD |
| FC |
Rows |
(TkW) |
Q/ITD |
(L/s) |
(Pa) |
|
2 |
2.7(.8) |
0.03 |
0.3(.02) |
0.01(30) |
| 02 |
3 |
2.6(.8) |
0.02 |
0.3(.02) |
0.01(30) |
|
4 |
2.5(.7) |
0.02 |
0.3(.02) |
0.01(30) |
|
2 |
3.8(1.1) |
0.03 |
0.4(.03) |
0.02(60) |
| 03 |
3 |
3.7(1.1) |
0.03 |
0.4(.03) |
0.02(60) |
|
4 |
3.6(1.1) |
0.03 |
0.4(.03) |
0.02(60) |
|
2 |
5.3(1.6) |
0.05 |
0.5(.03) |
0.03(90) |
| 04 |
3 |
5.2(1.5) |
0.05 |
0.5(.03) |
0.03(90) |
|
4 |
5.0(1.5) |
0.05 |
0.5(.03) |
0.03(90) |
|
2 |
8.8(2.6) |
0.08 |
0.9(.06) |
0.09(269) |
| 06 |
3 |
8.7(2.5) |
0.08 |
0.9(.06) |
0.09(269) |
|
4 |
8.5(2.5) |
0.08 |
0.8(.05) |
0.08(239) |
|
2 |
11.7(3.4) |
0.11 |
1.2(.08) |
0.17(508) |
| 08 |
3 |
11.2(3.3) |
0.10 |
1.1(.07) |
0.15(448) |
|
4 |
10.9(3.2) |
0.10 |
1.1(.07) |
0.15(448) |
|
2 |
15.2(4.5) |
0.14 |
1.5(.09) |
0.29(867) |
| 10 |
3 |
15.2(4.5) |
0.14 |
1.5(.09) |
0.29(867) |
|
4 |
14.8(4.3) |
0.13 |
1.5(.09) |
0.27(807) |
|
2 |
17.7(5.2) |
0.16 |
1.8(.11) |
0.40(1200) |
| 12 |
3 |
17.4(5.1) |
0.16 |
1.7(.11) |
0.39(1170) |
|
4 |
16.9(5.0) |
0.15 |
1.7(.11) |
0.37(1110) |
Note:
- Medium and low speed capacities are approximately 80 percent and 60 percent respectively
of the high speed capacity.
- Q/ITD = MBH (kW)/(Entering water temperature -Entering air temperature) when delta T and
GPM (L/s) remain constant. To determine heating capacities at a different entering water
temperature or entering air temperature, compute the new ITD and multiply it by the Q/ITD
shown.
Table PD-17 Free Discharge Motor, Group 3
|
Main Coil |
TMBH |
|
GPM |
WPD |
| FC |
Rows |
(TkW) |
Q/ITD |
(L/s) |
(Pa) |
|
2 |
2.6(.8) |
0.02 |
0.3(.02) |
0.01(30) |
| 02 |
3 |
2.5(.7) |
0.02 |
0.3(.02) |
0.01(30) |
|
4 |
2.4(.7) |
0.02 |
0.3(.02) |
0.01(30) |
|
2 |
3.6(1.1) |
0.03 |
0.4(.03) |
0.02(60) |
| 03 |
3 |
3.6(1.1) |
0.03 |
0.4(.03) |
0.02(60) |
|
4 |
3.5(1.0) |
0.03 |
0.4(.03) |
0.01(30) |
|
2 |
5.1(1.5) |
0.05 |
0.5(.03) |
0.03(90) |
| 04 |
3 |
5.0(1.5) |
0.05 |
0.5(.03) |
0.03(90) |
|
4 |
4.9(1.4) |
0.04 |
0.5(.03) |
0.03(90) |
|
2 |
8.4(2.5) |
0.08 |
0.8(.05) |
0.08(239) |
| 06 |
3 |
8.3(2.4) |
0.08 |
0.8(.05) |
0.08(239) |
|
4 |
8.1(2.4) |
0.07 |
0.8(.05) |
0.08(239) |
|
2 |
11.2(3.3) |
0.10 |
1.1(.07) |
0.15(448) |
| 08 |
3 |
10.8(3.2) |
0.10 |
1.1(.07) |
0.15(448) |
|
4 |
10.5(3.1) |
0.10 |
1.1(.07) |
0.14(419) |
|
2 |
14.5(4.2) |
0.13 |
1.5(.09) |
0.26(777) |
| 10 |
3 |
14.6(4.3) |
0.13 |
1.5(.09) |
0.27(807) |
|
4 |
14.2(4.2) |
0.13 |
1.4(.09) |
0.25(748) |
|
2 |
17.0(5.0) |
0.15 |
1.7(.11) |
0.37(1110) |
| 12 |
3 |
16.7(4.9) |
0.15 |
1.7(.11) |
0.36(108) |
|
4 |
16.3(4.8) |
0.15 |
1.6(.10) |
0.34(1020) |
Note:
- Medium and low speed capacities are approximately 80 percent and 60 percent respectively
of the high speed capacity.
- Q/ITD = MBH (kW)/(Entering water temperature - Entering air temperature) when delta T
and GPM (L/s) remain constant. To determine heating capacities at a different entering
water temperature or entering air temperature, compute the new ITD and multiply it by the
Q/ITD shown.
|
Copyright © 19962009 AECinfo.com
|
|