| Electrical Data Low Vertical Free Discharge Motors (115 Volt)
| FC |
FLA |
HP (kW) |
RPM |
| 03 |
0.7 |
.03(0) |
H |
1090 |
| |
|
|
M |
770 |
| |
|
|
L |
560 |
| 04 |
0.8 |
.03(0) |
H |
1090 |
| |
|
|
M |
750 |
| |
|
|
L |
560 |
| 06 |
1.1 |
.03(0) |
H |
1115 |
| |
|
|
M |
760 |
| |
|
|
L |
560 |
Note:
Actual rpm will vary with application and configuration.
Decimal to Fractional HP(kW) Conversion
| FC |
Decimal |
Fraction |
| 02 |
.03 |
1/30 |
| |
.07 |
1/15 |
| 03 |
.04 |
1/25 |
| |
.05 |
1/20 |
| |
.08 |
1/12 |
| 04 |
.05 |
1/20 |
| |
.06 |
1/16 |
| |
.10 |
1/10 |
| |
.13 |
1/8 |
| 06 |
.07 |
1/15 |
| |
.12 |
1/8 |
| |
.16 |
1/6 |
| |
.24 |
1/4 |
| 08 |
.12 |
1/8 |
| |
.13 |
1/8 |
| |
.24 |
1/4 |
| 10 |
.05 |
.07 |
1/20 |
1/15 |
| |
.06 |
.12 |
1/16 |
1/8 |
| |
.10 |
.16 |
1/10 |
1/6 |
| |
.13 |
.24 |
1/8 |
1/4 |
| 12 |
.05 |
.12 |
1/20 |
1/8 |
| |
.06 |
.13 |
1/16 |
1/8 |
| |
.10 |
.24 |
1/10 |
1/4 |
| |
.13 |
.24 |
1/8 |
1/4 |
| Low Vertical 03, 04, 06 |
.03 |
1/30 |
Note:
Values for fractional HPs(kWs) are approximate
values and not necessarily the actual HP(kW).
Minimum Circuit Ampacity(MCA) and Maximum Fuse
Size(MFS) Calculations for Fan-Coils:(Motors only, No Electric Heat)
MCA =(1.25) x [Largest Motor Amperes(FLA)] + Second Motor
Amperes(FLA) (Size 10 and 12 only)
MFS or HACR* Type Circuit Breaker = 15 Amps for all
Fan-Coils without Electric Heat
(See previous Electrical Data for units with Electric
Heat.)
* HACR (Heating, Air-Conditioning and Refrigeration) type
circuit breakers are required in the branch circuit wiring for all size 10 and 12
fan-coils. |