UniTrane Fan-Coil - Page 27
UniTrane Fan-Coil
| Electrical Data Low Vertical Free Discharge Motors (115 Volt)
Note: Actual rpm will vary with application and configuration. Decimal to Fractional HP(kW) Conversion
Note: Values for fractional HPs(kWs) are approximate values and not necessarily the actual HP(kW). Minimum Circuit Ampacity(MCA) and Maximum Fuse Size(MFS) Calculations for Fan-Coils:(Motors only, No Electric Heat) MCA =(1.25) x [Largest Motor Amperes(FLA)] + Second Motor Amperes(FLA) (Size 10 and 12 only) MFS or HACR* Type Circuit Breaker = 15 Amps for all Fan-Coils without Electric Heat (See previous Electrical Data for units with Electric Heat.) * HACR (Heating, Air-Conditioning and Refrigeration) type circuit breakers are required in the branch circuit wiring for all size 10 and 12 fan-coils. |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||