  Trane Company (The)   Single & Dual Duct VAV Terminal Units  

Single & Dual Duct VAV Terminal Units - Page 11

   

Single & Dual Duct VAV Terminal Units

Application Considerations

Table G-3 - Primary Air Control VCCE, VCWE, VDDE CFM Setting Guidelines

 

Control Type

Valve Size Nominal CFM Maximum Setting Minimum Setting Constant Volume

Pneumatic With Volume Regulator
and
Pressure Independent Electronic

03 300 135-415 CFM 60-220 CFM 60-415
06 600 215-650 CFM 90-340 CFM 90-650
11 1100 400-1200 CFM 170-640 CFM 170-1200
17 1700 650-1930 CFM 270-1020 CFM 270-1930
24 2400 930-2800 CFM 390-1480 CFM 390-2800
32 3200 1270-3800 CFM 530-2000 CFM 530-3800
42 4200 1660-5000 CFM 700-2630 CFM 700-5000

UCM - Direct Digital

03 300 150-315 CFM 60-300 CFM  
06 600 300-630 CFM 90-600 CFM  
11 1100 550-1155 CFM 165-1100 CFM  
17 1700 850-1785 CFM 255-1700 CFM  
24 2400 1200-2520 CFM 360-2400 CFM  
32 3200 1600-3360 CFM 480-3200 CFM  
42 4200 2100-4410 CFM 630-4200 CFM  

Table G-3 - Primary Air Control VCCE, VCWE, VDDE L/s Setting Guidelines (Metric)

Control Type

Valve Size Nominal CFM Maximum Setting Minimum Setting Constant Volume

Pneumatic With Volume Regulator
and
Pressure Independent Electronic

03 142 64-196 28-104 28-196
06 283 101-307 42-160 42-307
11 519 189-566 80-302 80-566
17 802 307-911 127-481 127-911
24 1 133 439-1 321 184-698 184-1 321
32 1 510 599-1 793 250-944 250-1 793
42 1 982 783-2 360 330-1 241 330-2 360

UCM - Direct Digital

03 142 71-149 28-142  
06 283 142-297 42-283  
11 519 260-545 78-519  
17 802 401-842 120-802  
24 1 133 566-1 189 170-1 133  
32 1 510 755-1 586 227-1 510  
42 1 982 991-2 081 297-1 982  

Table G-5 - VCEE - CFM Setting Guidelines

Valve Size Nominal CFM Control Type Minimum Settings Maximum
Settings
Constant
Volume
20% NOM. 30% NOM 40%NOM 50% NOM
03 300 PNEUMATIC/PI
UCM
60-220
60-300
90-220
90-300
120-220
120-300
150-220
150-300
135-415
150-315
60-415
06 600 PNEUMATIC/PI
UCM
120-340
120-600
180-340
180-600
240-340
240-600
300-340
300-600
215-650
300-630
120-650
11 1100 PNEUMATIC/PI
UCM
220-640
220-1100
330-640
330-1100
440-640
440-1100
550-640
550-1100
400-1200
550-1155
220-1200
17 1700 PNEUMATIC/PI
UCM
340-1020
340-1700
510-1020
510-1700
680-1020
680-1700
850-1020
850-1700
650-1930
850-1785
340-1930
24 2400 PNEUMATIC/PI
UCM
480-1480
480-2400
720-1480
720-2400
960-1480
960-2400
1200-1480
1200-2400
930-2800
1200-2520
480-2800
32 3200 PNEUMATIC/PI
UCM
640-2000
640-3200
960-2000
960-3200
1280-2000
1280-3200
1600-2000
1600-3200
1270-3800
1600-3460
640-3800
42 4200 PNEUMATIC/PI
UCM
840-2630
840-4200
1260-2630
1260-4200
1680-2630
1680-4200
2100-2630
2100-4200
1660-5000
2100-4410
840-5000

Table G-5 - VCEE - CFM Setting Guidelines

Valve Size Nominal CFM Control Type Minimum Settings Maximum
Settings
Constant
Volume
20% NOM. 30% NOM 40%NOM 50% NOM
03 142 PNEUMATIC/PI
UCM
28-104
28-142
42-104
42-142
57-104
57-142
71-104
71-142
64-196
71-149
28-196
06 283 PNEUMATIC/PI
UCM
57-160
57-283
85-160
85-283
113-160
113-283
142-160
142-283
101-307
142-297
57-307
11 519 PNEUMATIC/PI
UCM
104-302
104-519
156-302
156-519
208-302
208-519
260-302
260-519
189-566
260-545
104-566
17 802 PNEUMATIC/PI
UCM
160-481
160-802
241-481
241-802
321-481
321-802
401-481
401-802
307-911
401-842
160-911
24 1 133 PNEUMATIC/PI
UCM
227-698
227-1 133
340-698
340-1 133
453-698
453-1 133
566-698
566-1 133
439-1 321
566-1 189
227-1 321
32 1 510 PNEUMATIC/PI
UCM
302-944
302-1 510
453-944
453-1 510
604-944
604-1 510
755-944
755-1 510
599-1 793
755-1 633
302-1 793
42 1 982 PNEUMATIC/PI
UCM
396-1 241
396-1 982
595-1 241
595-1 982
793-1 241
793-1 982
991-1 241
991-1 982
783-2 360
991-2 081
396-2 360

 

Note:

1. Minimum flow and maximum flow settings must have at least a .05 delta P flow sensor signal difference.

2. Flow rings are provided with all unit sizes.

3. A minimum flow setting of zero is permissible, except for hot water and electric reheat.

4. UCM-DDC control - The minimum heating flow setting is factory set to 30% of nominal air valve flow. This is field   adjustable.

5. On Model VDDE - Constant Volume = (Heat Min + Cool Max = Heat Max + Cool Min.)

Example: Constant Volume = 1200 CFM

Heat Max = 800               Cool Max=1200

Heat Min= 0                     Cool Min=400

6. Minimum CFM's could increase due to KW requirements. Refer to Chart P-1 thru P-5 for guidelines.