Trane Company (The)
Single & Dual Duct VAV Terminal Units
Single & Dual Duct VAV Terminal Units - Page 11
Single & Dual Duct VAV Terminal Units
| Application Considerations Table G-3 - Primary Air Control VCCE, VCWE, VDDE CFM Setting Guidelines |
Control Type |
Valve Size | Nominal CFM | Maximum Setting | Minimum Setting | Constant Volume |
Pneumatic
With Volume Regulator |
03 | 300 | 135-415 CFM | 60-220 CFM | 60-415 |
| 06 | 600 | 215-650 CFM | 90-340 CFM | 90-650 | |
| 11 | 1100 | 400-1200 CFM | 170-640 CFM | 170-1200 | |
| 17 | 1700 | 650-1930 CFM | 270-1020 CFM | 270-1930 | |
| 24 | 2400 | 930-2800 CFM | 390-1480 CFM | 390-2800 | |
| 32 | 3200 | 1270-3800 CFM | 530-2000 CFM | 530-3800 | |
| 42 | 4200 | 1660-5000 CFM | 700-2630 CFM | 700-5000 | |
UCM - Direct Digital |
03 | 300 | 150-315 CFM | 60-300 CFM | |
| 06 | 600 | 300-630 CFM | 90-600 CFM | ||
| 11 | 1100 | 550-1155 CFM | 165-1100 CFM | ||
| 17 | 1700 | 850-1785 CFM | 255-1700 CFM | ||
| 24 | 2400 | 1200-2520 CFM | 360-2400 CFM | ||
| 32 | 3200 | 1600-3360 CFM | 480-3200 CFM | ||
| 42 | 4200 | 2100-4410 CFM | 630-4200 CFM |
Table G-3 - Primary Air Control VCCE, VCWE, VDDE L/s Setting Guidelines (Metric)
Control Type |
Valve Size | Nominal CFM | Maximum Setting | Minimum Setting | Constant Volume |
Pneumatic
With Volume Regulator |
03 | 142 | 64-196 | 28-104 | 28-196 |
| 06 | 283 | 101-307 | 42-160 | 42-307 | |
| 11 | 519 | 189-566 | 80-302 | 80-566 | |
| 17 | 802 | 307-911 | 127-481 | 127-911 | |
| 24 | 1 133 | 439-1 321 | 184-698 | 184-1 321 | |
| 32 | 1 510 | 599-1 793 | 250-944 | 250-1 793 | |
| 42 | 1 982 | 783-2 360 | 330-1 241 | 330-2 360 | |
UCM - Direct Digital |
03 | 142 | 71-149 | 28-142 | |
| 06 | 283 | 142-297 | 42-283 | ||
| 11 | 519 | 260-545 | 78-519 | ||
| 17 | 802 | 401-842 | 120-802 | ||
| 24 | 1 133 | 566-1 189 | 170-1 133 | ||
| 32 | 1 510 | 755-1 586 | 227-1 510 | ||
| 42 | 1 982 | 991-2 081 | 297-1 982 |
Table G-5 - VCEE - CFM Setting Guidelines
| Valve Size | Nominal CFM | Control Type | Minimum Settings | Maximum Settings |
Constant Volume |
|||
| 20% NOM. | 30% NOM | 40%NOM | 50% NOM | |||||
| 03 | 300 | PNEUMATIC/PI UCM |
60-220 60-300 |
90-220 90-300 |
120-220 120-300 |
150-220 150-300 |
135-415 150-315 |
60-415 |
| 06 | 600 | PNEUMATIC/PI UCM |
120-340 120-600 |
180-340 180-600 |
240-340 240-600 |
300-340 300-600 |
215-650 300-630 |
120-650 |
| 11 | 1100 | PNEUMATIC/PI UCM |
220-640 220-1100 |
330-640 330-1100 |
440-640 440-1100 |
550-640 550-1100 |
400-1200 550-1155 |
220-1200 |
| 17 | 1700 | PNEUMATIC/PI UCM |
340-1020 340-1700 |
510-1020 510-1700 |
680-1020 680-1700 |
850-1020 850-1700 |
650-1930 850-1785 |
340-1930 |
| 24 | 2400 | PNEUMATIC/PI UCM |
480-1480 480-2400 |
720-1480 720-2400 |
960-1480 960-2400 |
1200-1480 1200-2400 |
930-2800 1200-2520 |
480-2800 |
| 32 | 3200 | PNEUMATIC/PI UCM |
640-2000 640-3200 |
960-2000 960-3200 |
1280-2000 1280-3200 |
1600-2000 1600-3200 |
1270-3800 1600-3460 |
640-3800 |
| 42 | 4200 | PNEUMATIC/PI UCM |
840-2630 840-4200 |
1260-2630 1260-4200 |
1680-2630 1680-4200 |
2100-2630 2100-4200 |
1660-5000 2100-4410 |
840-5000 |
Table G-5 - VCEE - CFM Setting Guidelines
| Valve Size | Nominal CFM | Control Type | Minimum Settings | Maximum Settings |
Constant Volume |
|||
| 20% NOM. | 30% NOM | 40%NOM | 50% NOM | |||||
| 03 | 142 | PNEUMATIC/PI UCM |
28-104 28-142 |
42-104 42-142 |
57-104 57-142 |
71-104 71-142 |
64-196 71-149 |
28-196 |
| 06 | 283 | PNEUMATIC/PI UCM |
57-160 57-283 |
85-160 85-283 |
113-160 113-283 |
142-160 142-283 |
101-307 142-297 |
57-307 |
| 11 | 519 | PNEUMATIC/PI UCM |
104-302 104-519 |
156-302 156-519 |
208-302 208-519 |
260-302 260-519 |
189-566 260-545 |
104-566 |
| 17 | 802 | PNEUMATIC/PI UCM |
160-481 160-802 |
241-481 241-802 |
321-481 321-802 |
401-481 401-802 |
307-911 401-842 |
160-911 |
| 24 | 1 133 | PNEUMATIC/PI UCM |
227-698 227-1 133 |
340-698 340-1 133 |
453-698 453-1 133 |
566-698 566-1 133 |
439-1 321 566-1 189 |
227-1 321 |
| 32 | 1 510 | PNEUMATIC/PI UCM |
302-944 302-1 510 |
453-944 453-1 510 |
604-944 604-1 510 |
755-944 755-1 510 |
599-1 793 755-1 633 |
302-1 793 |
| 42 | 1 982 | PNEUMATIC/PI UCM |
396-1 241 396-1 982 |
595-1 241 595-1 982 |
793-1 241 793-1 982 |
991-1 241 991-1 982 |
783-2 360 991-2 081 |
396-2 360 |
| Note: 1. Minimum flow and maximum flow settings must have at least a .05 delta P flow sensor signal difference. 2. Flow rings are provided with all unit sizes. 3. A minimum flow setting of zero is permissible, except for hot water and electric reheat. 4. UCM-DDC control - The minimum heating flow setting is factory set to 30% of nominal air valve flow. This is field adjustable. 5. On Model VDDE - Constant Volume = (Heat Min + Cool Max = Heat Max + Cool Min.) Example: Constant Volume = 1200 CFM Heat Max = 800 Cool Max=1200 Heat Min= 0 Cool Min=400 6. Minimum CFM's could increase due to KW requirements. Refer to Chart P-1 thru P-5 for guidelines. |