Single & Dual Duct VAV Terminal Units
Single & Dual Duct VAV Terminal Units - Page 17
Single & Dual Duct VAV Terminal Units
| Performance Data Static
Pressure Requirements Chart P-1 - Model VCCE Outlet - Straight Flanged or Slip and Drive
Chart P-2 - Model VCWE Outlet - Straight
Flanged or Slip and Drive
Chart P-3 - Model VCWE Outlet - Straight
Flanged or Slip and Drive
Notes: 1. The solid portion of each curve represents the acceptable range for minimum and maximum cfm setting for pressure independent applications. The dotted portion of the curve may be used for pressure dependent applications. 2. Units utilizing VAV UCM control (DDC) may have different pressure independent flow setting guidelines than those represented by the solid portion of the curves. For more information on the cfm setting range guidelines, see the General Data Section of this catalog. 3. The charts on this page do not include downstream static pressure losses. 4. The charts on this page assume outlet connection code FL or SD. For integral outlet connection codes A through J, add the pressure drop from the above chart to the integral outlet static pressure requirements from Table P-1. 5. When an aspirating thermostat is used, minimum inlet static pressure is 0.5 inches w.g., plus 0.05 inches w.g. per foot of connecting tube. |