Trane Company (The)
Single & Dual Duct VAV Terminal Units
Single & Dual Duct VAV Terminal Units - Page 21
Single & Dual Duct VAV Terminal Units
| Performance Data VCEE Electric Unit
Heat Table P-6- Size 06 (Metric )
Notes : 1. Coils available with electric, electric with mercury contactors, pneumatic-electric switches, and pneumatic-electric switches with mercury contactors. 2. Available kW increments are by 0.5 kw from 0 to 8.0 kw by 1.0 kw by 1.0 kw from 9.0 to 17.0 kw, and by 2.0 kw from 18.0-26.0 kw. 3. Each electric actuator draws 1.0 amp. 4. Each heat output draws a maximum of 0.5 amp. 5. On three-phase heaters the lineload is unbalanced. 6. Adequate airflow over heater is necessary to dissipate heat. As kw requirements increase, so must minimum airflow. Above chart indicates the minimum Cfm required for each KW range. Example : A Model VCEE, electric unit heat size 11 terminal unit has 480V/3 phase 5.0 kw electric heat with 3 stages.
Useful Formulas
|




