| Performance Data
VCWE Hot Water Unit Heat Table P-12- Size 03, 06
| STANDARD
CAPACITY |
HIGH
CAPACITY |
| Air flow CFM |
GPM |
LAT (F) |
WTD (F) |
Coil Cap (MBH) |
WPD (Ft) |
GPM |
LAT (F) |
WTD (F) |
Coil Cap(MBH) |
WPD (Ft) |
| 100 |
.5 |
126.7 |
32.3 |
7.9 |
.5 |
1.0 |
141.9 |
19.6 |
9.6 |
.4 |
| |
1.0 |
136.7 |
18.5 |
9.0 |
1.9 |
2.0 |
151.0 |
10.9 |
10.6 |
1.5 |
| |
2.0 |
143.0 |
10.0 |
9.7 |
7.5 |
4.0 |
156.5 |
5.7 |
11.2 |
6.1 |
| |
2.5 |
144.4 |
8.1 |
9.9 |
11.7 |
5.0 |
157.7 |
4.7 |
11.3 |
9.5 |
| 150 |
.5 |
112.2 |
38.6 |
9.5 |
.5 |
1.0 |
127.7 |
24.6 |
12.0 |
.4 |
| |
1.0 |
122.5 |
22.9 |
11.2 |
1.9 |
2.0 |
138.2 |
14.1 |
13.8 |
1.5 |
| |
2.0 |
129.2 |
12.6 |
12.3 |
7.5 |
4.0 |
145.0 |
7.6 |
14.9 |
6.1 |
| |
2.5 |
130.8 |
10.3 |
12.5 |
11.7 |
5.0 |
146.5 |
6.2 |
15.1 |
9.5 |
| 200 |
.5 |
102.7 |
42.9 |
10.5 |
.5 |
1.0 |
117.6 |
28.2 |
13.8 |
.4 |
| |
1.0 |
112.7 |
26.0 |
12.7 |
1.9 |
2.0 |
128.6 |
16.6 |
16.2 |
1.5 |
| |
2.0 |
119.5 |
14.6 |
14.2 |
7.5 |
4.0 |
136.0 |
9.2 |
17.9 |
6.1 |
| |
2.5 |
121.1 |
12.0 |
14.6 |
11.7 |
5.0 |
137.7 |
7.4 |
18.2 |
9.5 |
| 300 |
.5 |
91.1 |
48.7 |
11.9 |
.5 |
1.0 |
104.5 |
33.5 |
16.4 |
.4 |
| |
1.0 |
100.2 |
30.5 |
14.9 |
1.9 |
2.0 |
115.6 |
20.5 |
20.0 |
1.6 |
| |
2.0 |
106.7 |
17.5 |
17.1 |
7.5 |
4.0 |
123.6 |
11.6 |
22.7 |
6.1 |
| |
2.5 |
108.3 |
14.4 |
17.6 |
11.7 |
5.0 |
125.5 |
9.6 |
23.3 |
9.5 |
| 400 |
.5 |
84.2 |
52.4 |
12.9 |
.5 |
1.0 |
96.4 |
37.3 |
18.3 |
.4 |
| |
1.0 |
92.4 |
33.7 |
16.5 |
1.9 |
2.0 |
107.2 |
23.6 |
23.0 |
1.6 |
| |
2.0 |
98.5 |
19.7 |
19.2 |
7.5 |
4.0 |
115.4 |
13.7 |
26.6 |
6.1 |
| |
2.5 |
100.0 |
16.3 |
19.9 |
11.7 |
5.0 |
117.4 |
11.3 |
27.5 |
9.5 |
| 500 |
.5 |
79.6 |
55.2 |
13.6 |
.5 |
1.0 |
90.7 |
40.1 |
19.7 |
.4 |
| |
1.0 |
87.1 |
36.1 |
17.7 |
1.9 |
2.0 |
101.0 |
26.0 |
25.4 |
1.6 |
| |
2.0 |
92.8 |
21.4 |
20.9 |
7.5 |
4.0 |
109.3 |
15.3 |
29.9 |
6.1 |
| |
2.5 |
94.3 |
17.7 |
21.6 |
11.7 |
5.0 |
111.3 |
12.7 |
31.0 |
9.5 |
| 600 |
.5 |
76.3 |
57.4 |
14.1 |
.5 |
1.0 |
86.4 |
42.4 |
20.8 |
.4 |
| |
1.0 |
83.2 |
38.0 |
18.6 |
1.9 |
2.0 |
96.3 |
27.9 |
27.3 |
1.6 |
| |
2.0 |
88.6 |
22.7 |
22.2 |
7.5 |
4.0 |
104.4 |
16.7 |
32.7 |
6.1 |
| |
2.5 |
89.9 |
18.9 |
23.1 |
11.8 |
5.0 |
106.5 |
14.0 |
34.1 |
9.5 |
Notes :
1. Coils air pressure drop is included in static pressure
requirement charts.
2. Coils are leak tested at 300 psig air pressure under
water.
3. Capacities based on 180 degrees entering water
temperature, 55 degrees entering air temperature, and 0.00025 fouling factor. See capacity
correction factors for different entering temperatures.
4. The following equations may be used in calculating
Leaving Air Temperature (LAT) and Water Temperature Difference (WTD) :
LAT = EAT + (MBH x 921.7 / CFM)
WTD = EWT - LWT = (MBH x 2.04 /GPM)
Table P-13- Temperature Correction Factor for
Water Pressure Drop (WPD)
| Average Water Temperature (F) |
200 |
190 |
180 |
170 |
160 |
150 |
140 |
130 |
120 |
110 |
100 |
| Correction Factor |
0.97 |
0.985 |
1.0 |
1.015 |
1.030 |
1.050 |
1.075 |
1.100 |
1.125 |
1.150 |
1.180 |
Note :
1. Multiply water pressure drop from Hot Water Coil Capacity
Table by correction factor to get water pressure drop at various entering water
temperature.
Table P-14Temperature Difference
Correction Factors
| Entering Water Minus Entering Air (F) |
45 |
55 |
65 |
75 |
85 |
95 |
105 |
115 |
125 |
135 |
145 |
| Correction Factor |
0.34 |
0.42 |
0.50 |
0.58 |
0.67 |
0.75 |
0.83 |
0.92 |
1.00 |
1.08 |
1.16 |
Note :
1. Multiply MBH from Hot Water Coil Capacity Table by
correction factor to get MBH at various entering air and water temperatures. |