| Performance Data VCWE Hot Water Unit
Heat Table P-15- Size 03, 06 (Metric)
| STANDARD CAPACITY |
HIGH CAPACITY |
| Air flow L/s |
L/s |
LAT (C) |
WTD (C) |
Coil Cap (kW) |
Coil Cap WPD (kPa) |
L/s |
LAT (C) |
WTD (C) |
Coil Cap (kW) |
WPD (kPa) |
47 |
0.03 |
52.6 |
17.9 |
2.3 |
1.45 |
0.06 |
61.0 |
10.9 |
2.8 |
1.16 |
| |
0.06 |
58.2 |
10.3 |
2.6 |
5.49 |
0.13 |
66.1 |
6.1 |
3.1 |
4.34 |
| |
0.13 |
61.7 |
5.6 |
2.8 |
21.68 |
0.25 |
69.2 |
3.2 |
3.3 |
17.63 |
| |
0.16 |
62.4 |
4.5 |
2.9 |
33.81 |
0.32 |
69.8 |
2.6 |
3.3 |
27.46 |
71 |
0.03 |
44.6 |
21.4 |
2.8 |
1.45 |
0.06 |
53.2 |
13.7 |
3.5 |
1.16 |
| |
0.06 |
50.3 |
12.7 |
3.3 |
5.49 |
0.13 |
59.0 |
7.8 |
4.0 |
4.34 |
| |
0.13 |
54.0 |
7.0 |
3.6 |
21.68 |
0.25 |
62.8 |
4.2 |
4.4 |
17.63 |
| |
0.16 |
54.9 |
5.7 |
3.7 |
33.81 |
0.32 |
63.6 |
3.4 |
4.4 |
27.46 |
94 |
0.03 |
39.3 |
23.8 |
3.1 |
.1.45 |
0.06 |
47.6 |
15.7 |
4.0 |
1.16 |
| |
0.06 |
44.8 |
14.4 |
3.7 |
5.49 |
0.13 |
53.7 |
9.2 |
4.7 |
4.34 |
| |
0.13 |
48.6 |
8.1 |
4.2 |
21.68 |
0.25 |
57.8 |
5.1 |
5.2 |
17.63 |
| |
0.16 |
49.5 |
6.7 |
4.3 |
33.81 |
0.32 |
58.7 |
4.1 |
5.3 |
27.46 |
142 |
0.03 |
32.8 |
27.1 |
3.5 |
.1.45 |
0.06 |
40.3 |
18.6 |
4.8 |
1.16 |
| |
0.06 |
37.9 |
16.9 |
4.4 |
5.49 |
0.13 |
46.4 |
11.4 |
5.9 |
4.62 |
| |
0.13 |
41.5 |
9.7 |
5.0 |
21.68 |
0.25 |
50.9 |
6.4 |
6.7 |
17.63 |
| |
0.16 |
42.4 |
8.0 |
5.2 |
33.81 |
0.32 |
51.9 |
5.3 |
6.8 |
27.63 |
189 |
0.03 |
29.0 |
29.1 |
3.8 |
1.45. |
0.06 |
35.8 |
20.7 |
5.4 |
1.16 |
| |
0.06 |
33.6 |
18.7 |
4.8 |
5.49 |
0.13 |
41.8 |
13.1 |
6.7 |
4.62 |
| |
0.13 |
36.9 |
10.9 |
5.6 |
21.68 |
0.25 |
46.3 |
7.6 |
7.8 |
17.63 |
| |
0.16 |
37.8 |
9.1 |
5.6 |
33.81 |
0.32 |
47.4 |
6.3 |
8.1 |
27.63 |
236 |
0.03 |
26.4 |
30.7 |
4.0 |
1.45. |
0.06 |
32.6 |
22.3 |
5.8 |
1.16 |
| |
0.06 |
30.6 |
20.1 |
5.2 |
5.49 |
0.13 |
38.3 |
14.4 |
7.4 |
4.62 |
| |
0.13 |
33.8 |
11.9 |
6.1 |
21.68 |
0.25 |
42.9 |
8.5 |
8.8 |
17.63 |
| |
0.16 |
34.6 |
9.8 |
6.3 |
33.81 |
0.32 |
44.1 |
7.1 |
9.1 |
27.63 |
283 |
0.03 |
24.6 |
31.9 |
4.1 |
1.45. |
0.06 |
30.2 |
23.6 |
6.1 |
1.16 |
| |
0.06 |
28.4 |
21.1 |
5.4 |
5.49 |
0.13 |
35.7 |
15.5 |
8.0 |
4.62 |
| |
0.13 |
31.4 |
12.6 |
6.5 |
21.68 |
0.25 |
40.2 |
9.3 |
9.6 |
17.63 |
| |
0.16 |
32.2 |
10.5 |
6.8 |
34.10 |
0.32 |
41.4 |
7.8 |
10.0 |
27.46 |
Notes :
1. Coils air pressure drop is included in static pressure
requirement charts.
2. Coils are leak tested at 31.3 kPa air pressure under
water.
3. Capacities based on 82.2º entering air
temperature, 55°C entering air temperature, and 0.00025 fouling factor. See capacity
correction factors for different entering temperatures.
4. The following equations may be used in calculating
Leaving Air Temperature (LAT) and Water Temperature Difference (WTD) :
LAT = EAT + (KW x 824.6 / Airflow L/s)
WTD = EWT - LWT = (MBH x .244 /L/s)
Table P-16- Temperature Correction Factor for
Water Pressure Drop (WPD)
| Average Water Temperature (C) |
93 |
88 |
82 |
77 |
71 |
66 |
60 |
54 |
49 |
43 |
38 |
| Correction Factor |
0.97 |
0.985 |
1.0 |
1.015 |
1.030 |
1.050 |
1.075 |
1.100 |
1.125 |
1.150 |
1.180 |
Note :
1. Multiply water pressure drop from Hot Water Coil Capacity
Table by correction factor to get MBH at various entering air and water temperatures.
Table P-17Temperature Difference
Correction Factors
| Entering Water Minus Entering Air (F) |
25 |
31 |
36 |
42 |
47 |
53 |
58 |
64 |
69 |
75 |
81 |
| Correction Factor |
0.34 |
0.42 |
0.50 |
0.58 |
0.67 |
0.75 |
0.83 |
0.92 |
1.00 |
1.08 |
1.16 |
Note :
1. Multiply KW from Hot Water Coil Capacity Table by
correction factor to get KW at various entering air and water temperatures. |