  Trane Company (The)   Single & Dual Duct VAV Terminal Units  

Single & Dual Duct VAV Terminal Units - Page 30

   

Single & Dual Duct VAV Terminal Units

Performance Data   VCWE Hot Water Unit Heat

Table P-21- Size 11 (Metric)

STANDARD CAPACITY HIGH CAPACITY
Air flow L/s   LAT (C) WTD (C) Coil Cap (kW) WPD (kPa)   LAT (C) WTD (C) Coil Cap (kW) WPD (kPa)

71

0.03

46.5

22.8

2.9

0.29

0.13

65.2

8.9

4.6

2.31

 

0.13

58.3

7.7

4.0

5.49

0.25

69.0

4.8

4.9

8.67

 

0.22

60.8

4.7

4.2

16.76

0.32

69.9

3.9

5.0

13.29

 

0.32

61.9

3.3

4.3

33.52

0.44

70.9

2.8

5.1

25.72

94

0.03

40.9

25.3

3.3

0.29

0.13

60.3

10.7

5.5

2.31

 

0.13

52.7

9.0

4.6

5.49

0.25

64.7

5.9

6.0

8.67

 

0.22

55.3

5.5

5.0

16.76

0.32

65.8

4.8

6.2

13.29

  0.32 56.5 3.9 5.1 33.52 0.44 67.0 3.5 6.3 25.72

118

0.03

36.9

27.1

3.5

.0.29

0.13

56.2

12.2

6.3

2.31

 

0.13

48.3

10.1

5.2

5.49

0.25

61.0

6.8

7.0

8.67

 

0.22

51.1

6.2

5.6

16.76

0.32

62.2

5.6

7.2

13.29

 

0.32

52.3

4.4

5.7

33.52

0.44

63.6

4.1

7.4

25.72

142

0.03

33.9

28.4

3.7

.0.29

0.13

52.8

13.6

7.0

2.31

 

0.13

44.9

10.9

5.6

5.49

0.25

57.9

7.7

7.9

8.67

 

0.22

47.6

6.8

6.1

16.76

0.32

59.2

6.3

8.1

13.29

 

0.32

48.9

4.9

6.3

33.81

0.44

60.7

4.7

8.4

25.72

189

0.03

29.8

30.5

4.0

0.29

0.13

47.5

15.7

8.1

2.31

 

0.13

39.9

12.2

6.3

5.49

0.25

53.0

9.1

9.3

8.67

 

0.22

42.5

7.7

6.9

16.76

0.32

54.3

7.5

9.7

13.29

 

0.32

43.7

5.6

7.2

33.81

0.44

56.0

5.6

10.0

26.01

236

0.03

27.0

32.0

4.1

0.29

0.13

43.8

17.5

9.0

2.31

 

0.13

36.3

13.3

6.9

5.49

0.25

49.5

10.4

10.7

8.67

 

0.22

38.9

8.4

7.6

16.76

0.32

50.9

8.6

11.1

13.29

 

0.32

40.1

6.2

7.9

33.81

0.44

52.7

6.4

11.6

26.01

283

0.03

25.1

33.1

4.3

0.29

0.13

40.9

19.0

9.8

2.31

 

0.13

33.7

14.2

7.3

5.49

0.25

46.6

11.4

11.8

8.67

 

0.22

36.1

9.1

8.1

16.76

0.32

48.1

9.6

12.3

13.29

  0.32 37.3 6.7 8.6 33.81 0.44 50.1 7.2 13.0 26.01

330

0.03

23.6

34.0

4.4

0.29

0.13

38.5

20.3

10.5

2.31

 

0.13

31.6

14.9

7.7

5.49

0.25

44.3

12.4

12.8

8.67

 

0.22

33.9

9.6

8.6

16.76

0.32

45.8

10.4

13.4

13.29

 

0.32

35.1

7.1

9.1

33.81

0.44

47.7

7.9

14.2

26.01

378

0.03

22.4

34.7

4.5

0.29

0.13

36.5

21.4

11.0

2.31

 

0.13

29.9

15.5

8.0

5.49

0.25

42.2

13.3

13.7

8.67

 

0.22

32.2

10.0

9.0

16.76

0.32

43.8

11.2

14.4

13.29

 

0.32

33.2

7.4

9.5

33.81

0.44

45.8

8.5

15.4

26.01

425 .03 21.6 35.3 4.6 .29 .13 34.8 22.3 11.5 2.31
  .13 27.4 16.5 8.5 5.49 .25 38.9 14.8 15.2 8.67
  .22 30.7 10.4 9.4 16.76 .32 42.1 11.9 15.3 13.29
  .32 31.7 7.7 9.9 33.81 .44 44.1 9.1 16.4 26.01
472 .03 20.8 35.9 4.7 .29 .13 33.4 23.2 12.0 2.31
  .13 27.4 16.5 8.5 5.49 .25 38.9 14.8 15.2 8.67
  .22 29.4 10.8 9.7 16.76 .32 40.5 12.5 16.1 13.29
  .32 30.4 8.0 10.3 33.81 .44 42.6 9.6 17.3 26.01
519 .03 20.2 36.3 4.7 .29 .13 32.1 23.9 12.4 2.31
  .13 26.4 16.9 8.7 5.49 .25 37.6 15.4 15.9 8.67
  .22 28.4 11.1 10.0 16.76 .32 39.2 13.1 16.9 13.29
  .32 29.4 8.3 10.6 33.81 .44 41.2 10.1 18.2 26.01

Notes :

1. Coils air pressure drop is included in static pressure requirement charts.

2. Coils are leak tested at 31.3 kPa air pressure under water.

3. Capacities based on 82.2º C entering air temperature, 12.8º C entering air temperature, and 0.00025 fouling factor. See capacity correction factors for different entering temperatures.

4. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD) :

LAT = EAT + (KW x 824.6 / Airflow L/s)

WTD = EWT - LWT = (MBH x .244 /L/s)

Table  P-22- Temperature Correction Factor for Water Pressure Drop (WPD)

Average Water Temperature (C) 93 88 82 77 71 66 60 54 49 43 38
Correction Factor 0.97 0.985 1.0 1.015 1.030 1.050 1.075 1.100 1.125 1.150 1.180

Note :

1. Multiply water pressure drop from Hot Water Coil Capacity Table by correction factor to get water pressure drop  at various entering air and water temperatures.

Table P-23—Temperature Difference Correction Factors

Entering Water Minus Entering Air (F) 25 31 36 42 47 53 58 64 69 75 81
Correction Factor 0.34 0.42 0.50 0.58 0.67 0.75 0.83 0.92 1.00 1.08 1.16

Note :

1. Multiply KW from Hot Water Coil Capacity Table by correction factor to get KW at various entering air and water temperatures.