| Search |
|
|
|
| |
| Site Navigation |
|
|
|
| News / Publications |
|
|
|
| Jobs | |
|
|
| Service |
|
|
|
|
|


|
| |
|
| |
United States Gypsum Company USG USG Cavity Shaft Wall Systems USG Cavity Wall Shaft Systems Page 3

USG Cavity Shaft Wall Systems
Test Data
Fire-rated Construction |
Fire
Rating |
Detail &
Physical Data |
1 hr. |

|
|
Description & Test No.
Cavity Shaft Wall Gypsum Drywall—5/8" SHEETROCK brand gypsum panels, FIRECODE core, one side—1" SHEETROCK
brand gypsum liner panels set betw USG steel C-H studs 24" o.c.—panels appl to side opp liner panels & screw att—joints
fin—fire rating also applies with IMPERIAL FIRECODE base and veneer finish surface or THERMAFIBER in cavity—UL Des
U469
Acoustical Performance
STC |
Description
& Test No. |
System
Reference |
N/A |
|
A |
|
Fire-rated Construction |
Fire
Rating |
Detail &
Physical Data |
2 hr. |

|
|
Description & Test No.
Cavity Shaft Wall Gypsum Drywall—2 layers 1/2" SHEETROCK brand gypsum panels, FIRECODE C core, one side—1"
SHEETROCK brand liner panels set betw USG steel 25 ga. C-H studs 24" o.c.—joints fin—rating also applies with IMPERIAL
FIRECODE C base and veneer finish surface or THERMAFIBER in cavity—UL Des U438. Rating also applies to 5/8"
Sheetrock brand gypsum panels, Firecode Core, and 5/8" IMPERIAL FIRECODE Base.
Acoustical Performance
STC |
Description
& Test No. |
System
Reference |
39
47 |
USG-750302
Based on 1"
Thermafiber SAFB—
BBN-750706 |
B |
|
Fire-rated Construction |
Fire
Rating |
Detail &
Physical Data |
2 hr. |

|
|
Description & Test No.
Cavity Shaft Wall—1" SHEETROCK brand gypsum liner panels, set betw 4" USG steel C-H studs 24" o.c. one side—3/4"
SHEETROCK brand gypsum panels, Ultracode core, other side—3" THERMAFIBER SAFB—panels screw att 8" o.c. perim,
12" o.c. field—joints stag & fin—perimeter caulked—UL Des U492
Acoustical Performance
STC |
Description
& Test No. |
System
Reference |
52 |
SA-910913 |
C |
|
Fire-rated Construction |
Fire
Rating |
Detail &
Physical Data |
2 hr. |

|
|
Description & Test No.
Cavity Shaft Wall Cement Board/Gypsum Drywall—1/2" DUROCK cement board—5/8" SHEETROCK brand gypsum panels,
Firecode core—1" SHEETROCK brand gypsum liner panels set betw USG steel 20 ga. min C-H studs 24" o.c.—1-1/2"
THERMAFIBER SAFB—cement board screw att with 1-5/8" DUROCK steel screws and laminated to gypsum panel with 4"
strip DURABOND ceramic tile mastic applied with 3/4" notched trowel midway betw studs—joints fin—UL Des U459*
Acoustical Performance
STC |
Description
& Test No. |
System
Reference |
N/A |
N/A |
D |
|
Fire-rated Construction |
Fire
Rating |
Detail &
Physical Data |
2 hr. |

|
|
Description & Test No.
Cavity Shaft Wall Gypsum Drywall—1/2" SHEETROCK brand gypsum panels, FIRECODE C core, one side—1"
SHEETROCK brand gypsum liner panels set betw USG steel C-H studs 24" o.c. and 1/2" SHEETROCK brand Gypsum
Panels, FIRECODE core, other side—joints of gypsum panels stag on opp sides & fin—rating also applies with IMPERIAL
FIRECODE C base and veneer finish surface—UL Des U467. Rating also applies to 5/8" SHEETROCK brand panels,
FIRECODE Core, and 5/8" IMPERIAL FIRECODE Base.
Acoustical Performance
STC |
Description
& Test No. |
System
Reference |
N/A |
|
E |
|
Fire-rated Construction |
Fire
Rating |
Detail &
Physical Data |
2 hr. est |

|
|
Description & Test No.
Cavity Shaft Wall Gypsum Drywall—2 layers 1/2" SHEETROCK brand gypsum panels, FIRECODE C core, one side—1"
SHEETROCK brand gypsum liner panels set betw USG 25 ga. steel C-H studs 24" o.c.—RC-1 chan spaced 24" o.c.—1-1/2"
THERMAFIBER SAFB—panels & RC-1 chan screw att to side opp liner panels—base layer appl horiz—face layer appl
vert—joints fin—est. fire rating based on U of C 2-8-72 and U of C 6-23-75—rating also applies with IMPERIAL FIRECODE C
base and veneer finish
Acoustical Performance
STC |
Description
& Test No. |
System
Reference |
51 |
BBN-750412 |
F |
|
Fire-rated Construction |
Fire
Rating |
Detail &
Physical Data |
3 hr. |

|
|
Description & Test No.
Cavity Shaft Wall Gypsum Drywall—3 layers 3/4" SHEETROCK brand gypsum panels, ULTRACODE core—1st & 2nd layers
app vert or horiz over stl stds— if appl vert joints cntrd over stds, stag min 24", otherwise joints stag min 12"—3rd layer appl
vert over fur chan—Joints fin with paper tape & joint cmpd—UL Des U408
Acoustical Performance
STC |
Description
& Test No. |
System
Reference |
N/A |
|
G |
|
Fire-rated Construction |
Fire
Rating |
Detail &
Physical Data |
4 hr. |

|
|
Description & Test No.
Cavity Shaft Wall Gypsum Drywall—4 layers 3/4" SHEETROCK brand gypsum panels, ULTRACODE core—1st 3 layers appl
as for 3 hr rating—4th layer appl vert or horiz—if apply vert joints stag min 24" from 3rd layer—otherwise joints stag min
12"—joints fin with paper tape and joint compd—UL Des U408
Acoustical Performance
STC |
Description
& Test No. |
System
Reference |
N/A |
|
H |
|
|
Where thermal insulation is shown in assembly drawing, the specific product is required in the assembly to achieve the stated fire rating.
Fiberglass insulation cannot be substituted for THERMAFIBER Insulation.
Where RC-1 Resilient Channel is indicated, RC-1 or equivalent may be used.
* Use L/360 deflection criteria for limiting height/stud selection. Refer to SA932 DUROCK Multi-Purpose Cement Board Systems for more
information on cement board and related products.
Copyright © 1996-2008 AECinfo.com
|
|