USG Cavity Wall Shaft Systems Page 8

 

 

usg.JPG (5275 bytes)

USG Cavity Shaft Wall Systems


usgca08a.JPG (15672 bytes)

usgca08b.JPG (9059 bytes)
usgca08c.JPG (17646 bytes)

usgca08d.JPG (12999 bytes)

usgca08e.JPG (19455 bytes)

Air Handling Systems
Gypsum shaft walls have been used for many years to house all types of ducts in the shaft area. Their fire-resistant features plus economical dry construction make them ideal for this use. Today shaft walls are used successfully without a metal liner for handling return air in HVAC systems. To function properly, shaft wall systems should be designed with the following performance provisions.

  1. Gypsum board surface temperature does not exceed 125°F
  2. Air stream dew point temperatures are maintained below gypsum board surface temperature.
  3. The assembly is constructed to withstand sustained design uniform air pressure loads not exceeding 10 psf.
    Start up surge loads should not be greater than 1 -1 /2 times the design static load. (See table below for limiting heights).
  4. Separate approved liners should be installed in areas subject to continuous moisture overspray, condensation
    or air stream temperature over 125°F
  5. To ensure airtight construction, select appropriate sealants and apply where required.

Limiting Heights--Unlined Return Air Shafts

 

Sustained pressure load-psf

2 hr Fire-rated
system

1 hr Fire-rated
system

Stud type & size

Desig-
nation

Stud
Spcg

Allow.
defl.

5

10

5

10

2-1/2" C-H
Studs
usgca06f.JPG (2975 bytes)

212CH25

24"

L/120

10'5"

7'5"

10'5"*

6'0"*

L/240

10'5"

7'5"

8'6"

6'0"*

L/360

9'3"

7'5"

7'5"

5'11"*

212CH22

24"

L/120

14'8"

10'5"

14'8"

10'5"

L/240

13'0"

10'4"

11'11"

9'5"

L/360

11'5"

9'0"

10'5"

8'3"

212CH20

24"

L/120

15'9"

11'2"

15'4"

11'2"*

L/240

13'4"

10'7"

12'2"

9'8"

L/360

11'7"

9'3"

10'8"

8'3"

4" C-H
Studs
usgca06g.JPG (2301 bytes)

400CH25

24"

L/120

13'10"

9'8"*

13'9"*

6'11"*

L/240

13'10"

9'8"*

13'4"

6'11"*

L/360

12'5"

9'8"*

11'8"

6'11"

400CH20

24"

L/120

20'0"

15'0"*

19'3"

15'0"*

L/240

15'10"

12'7"

15'3"

12'2"*

L/360

13'10"

11'0"

13'4"

10''7"*

6" C-H
Studs

600CH20

24"

L/120

27'7"

18'0"*

26'8"*

13'6"*

L/240

21'11"

17'5"*

21'2"'

13'6"*

L/360

19'2"

15'2"

18'6"

13'6"*

Double 6"
E-Studs
usgca06h.JPG (3534 bytes)

600ES25

24"

L/120

18'9"

9'3"

18'9"

9'3"

L/240

18'9"

9'3"

18'9"

9'3"

L/360

18'9"

9'3"

18'9"

9'3"

600ES20

24"

L/120

28'0"

20'0"*

28'0"

20'0"*

L/240

26'3"

20'0"*

24'9"

20'0"*

L/360

23'0"

18'3"*

21'9"

17'3"*

Important:  Runner fasteners should withstand 193lb. single shear and 200 lb. bearing force; attachment spacing should not exceed 24" o.c.  *Use JR20 runner for heights with asterisk.

 

*Request for Information / Request a Catalog
 
 
 
To request more information from United States Gypsum Company USG, please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2008 AECinfo.com