USG Cavity Shaft Wall Systems


Elevator Door Frame Assemblies
Typically, for buildings of four stories or more, building codes require a 1-1/2-hour "B" rating for elevator entranceways in a 2-hour rated shaft wall. Certain firms have conducted fire tests with their door and frame assemblies in USG Cavity Shaft Walls—UL Design U438 rated 2 hours. These door assemblies comply with the safety code for elevators and dumbwaiters ANSI A17.1 and have been tested per ASTM E152. Specific door jamb studs, jamb struts and installation methods are required for fire-rated construction. See entrance manufacturer for details. When specifying door frame assemblies, also specify installation in the shaft wall in which assemblies were performance-tested.

There have been many successful UL tests on door assemblies in USG Cavity Shaft Walls. In every successful test, the interface between the entranceway and shaft wall was constructed with a 20 ga. jamb strut having a 3 in. leg, installed at the door jamb.

Both the 20 ga. thickness and the 3 in. leg length in the jamb strut are required to achieve tested performance.

Shaft Wall Entranceway Assemblies–    1-1/2 hr. Fire Rated

Manufacturer

Maximum opening size

Door type

UL file no.

Otis

42"x84"

center opening

R7416

Otis

48"x100-1/2"

two-speed slide

R7416

Otis

48"x102"

center opening

R7416

Westinghouse

48"x102"

center opening

R8176

Dover

42"x"6"

single slide

R6155

Dover

48"x"6"

center opening

R6155

Tyler

42"x102"

single slide

R6403

Tyler

60"x108"

center opening

R6403

D A Matot

48"x78"

dumbwaiter

R6748

Hauenstein & Burmeister

48"x108"

center opening

R4153

Courion Industries

48"x84"

dumbwaiter

R2317

General Elevator

48"x84"

center opening

R10483

Columbia

42"x108"

single slide

R9642

Columbia

48"x108"

center opening

R9642

Columbia

48"x120"

single slide

R9642

Columbia

72"x120"

center opening

R9642

Columbia

96"x96"

multipaneled

R9642

Note: Entranceways tested with UL Design U438 shaft wall and achieved a 11/2-hour "B’’ rating.
Apparent duplications are a result of tests involving different types or styles of either frames or doors.

usgca09a.JPG (30517 bytes)

usgca09b.JPG (32776 bytes)

 

Request for Information / Request a Catalog from United States Gypsum Company USG
 
 
 
To request more information from United States Gypsum Company USG, please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2008 AECinfo.com