 |
Wheatland TUBE COMPANY DIVISION OF JOHN MANEELY COMPANY |
Use of Wheatland Electrical Metallic Tubing in Conformance
to the 1990 National Electrical Code
ARTICLE 348-ELECTRICAL METALLIC TUBING
Use (348-1 )-The use of electrical metallic
tubing shall be permitted for both exposed and concealed work. Electrical metallic tubing
shall not be used: (1) where, during installation or afterward, it will be subject to
severe physical damage; (2) where protected from corrosion solely by enamel; (3) in cinder
concrete or cinder fill where subject to permanent moisture unless protected on all sides
by a layer of noncinder concrete at least 2 inches thick or unless the tubing is at least
18 inches under the fill. Where practicable, dissimilar metals in contact anywhere in the
system shall be avoided to eliminate the possibility of galvanic action. Exception:
Aluminum fittings and enclosures shall be permitted to be used with steel electrical
metallic tubing.
Ferrous or nonferrous electrical metallic tubing, elbows, couplings
and fittings shall be permitted to be installed in concrete, in direct contact with the
earth, or in areas subject to severe corrosive influences when protected by corrosion
protection and judged suitable for the condition.
Wet Locations (348-4)-All supports, bolts, straps,
screws, etc., shall be of corrosion-resistant materials or protected against corrosion by
corrosion-resistant metals.
Size (348-5)
(a) Minimum. Tubing smaller than ½ inch electrical
Trade size shall not be used. Exception No. 1: For under plaster extensions as
permitted in Section 344-2. Exception No. 2: For enclosing the leads of motors as
permitted in Section 430-145(b).
(b) Maximum. The maximum size of tubing
shall be the 4-inch electrical Trade size.
Number of Conductors in Tubing (348-6)-The number
of conductors in a single tubing shall not exceed the percentage fill specified in the
N.E.C. (See N.E.C. code for specific number of conductors permitted in each tube size.)
Threads (348-7)-Electrical metallic tubing
shall not be threaded. Where integral couplings are utilized, such couplings shall be
permitted to be factory threaded..
Couplings and Connectors (348-8)- Couplings and connectors
used with tubing shall be made up tight. Where buried in masonry or concrete, they shall
be concrete-tight type. Where installed in wet location, they shall be the raintight type.
Bends-How Made (348-9)-Bends in the tubing
shall be so made that the tubing will not be injured and that the internal diameter of the
tubing wilt not be effectively reduced. The radius of the curve of the inner edge of any
field bend shall not be less than shown in Table 346-10 (See Page 5 of this brochure.)
Exception: For field bends made with a bending machine
designed for the purpose, the minimum radius shall not be less than indicated in the
following table.
Table 346-10 Exception Radius of Conduit Bends (Inches)
| Size of Conduit (In.) |
Radius to Centre of Conduit
(In.) |
| ½ ¾
1
1¼
1½
2
2½
3
3½
4 |
4 4½
5¾
7¼
8¼
9½
10½
13
15
16 |
For SI units: (Radius) one inch
= 25.4 millimeters.
Bends-Number in One Run (348-10)- A run of
electrical metallic tubing between outlet and outlet, fitting and fitting or outlet and
fitting shall not contain more than the equivalent of four quarter bends (360 degrees,
total) including those bends located immediately at the outlet or fitting.
Reaming (348-11)-All cut ends of electrical
metallic tubing shall be reamed or otherwise finished to remove rough edges.
Supports (348-12)-Electrical metallic tubing
shall be installed as a complete system as provided in Article 300 and shall be securely
fastened in place at least every 10 feet and within 3 feet of each outlet box, junction
box, cabinet or fitting.
Splices and Taps (348-14)-Splices and taps shall be
made only in junction boxes, outlet boxes or conduit bodies. See Article 370.
General (348-15)-Electrical metallic tubing shall comply with
(a) through (c) below.
(a) Cross Section. The tubing, and elbows and bends
for use with the tubing, shall have a circular cross section.
(b) Finish. Tubing shall have such a finish or
treatment of outer surfaces as will provide an approved durable means of readily
distinguishing it, after installation, from rigid metal conduit.
(c) Connectors. Where the tubing is coupled
together by threads, the connector shall be so designed as to prevent bending of the
tubing at any part of the thread.
|