Willamette StrucJoist SJ-15-25-35 StrucJoist - Page 4
| TABLE III |
DESIGN PROPERTIES |
| Joist Series |
Joist
Depth (inches) |
Joist wt. Ibs/ft |
Allow-
able
Moment (ft-lbs) |
Max. Shear &
End
Reaction
For 4"
Long Bearing |
Max. End Reaction For 1-3/4" Bearing |
Max. Interm-
ediate
Reaction (lbs) |
Nail Only El (x 106) |
Glue-
Nailed El (x 106) |
K (x 106)
|
| No Web Stiffeners |
With Web Stiffe-
ners(7) |
| SJ-15 |
9-1/2" |
1.90 |
2770 |
1125 |
975 |
1950 |
2440 |
176 |
199 |
4.94 |
| 11-7/8" |
2.10 |
3710 |
1425 |
975 |
1950 |
2440 |
304 |
340 |
6.18 |
| SJ-25 |
9-1/2" |
2.11 |
3260 |
1125 |
1060 |
2120 |
2570 |
204 |
227 |
4.94 |
| 11-7/8" |
2.37 |
4360 |
1425 |
1060 |
2120 |
2570 |
350 |
387 |
6.18 |
| 14" |
2.60 |
5360 |
1550 |
1060 |
2120 |
2570 |
520 |
570 |
7.28 |
| 16" |
2.82 |
6300 |
1550 |
1060 |
2120 |
2570 |
716 |
781 |
8.32 |
| SJ-35 |
11-7/8" |
2.90 |
5810 |
1425 |
1250 |
2500 |
2950 |
452 |
489 |
6.18 |
| 14" |
3.07 |
7130 |
1550 |
1250 |
2500 |
2950 |
667 |
718 |
7.28 |
| 16" |
3.25 |
8390 |
1550 |
1250 |
2500 |
2950 |
913 |
979 |
8.32 |
Notes:
- Design properties are based on 2.2E StrucLam LVL flanges.
- Glue-nailed El values are for 12" oc spacing and
increase for wider joist spacing. Glue-nailed El values apply to floor use only.
- Both bending and shear deformations shall be considered when
computing deflections. For bending deflection, use standard engineering formulae. For
shear deflection use 8x bending moment/K.
EXAMPLE: Uniformly distributed load on a simple span joist.
Deflection = 5wl4/384EI + 8M/K = 5wl4/384EI +
wl2 /K
w = uniform load in pounds per linear inch
I = effective span in inches
- The allowable moment, shear and reactions are for normal
duration loading and can be increased in accordance with the code for load duration.
- Moment values shown are for non-repetitive use. For joist
spacing of 24" o.c. or less, values may be increased 4%.
- 1-3/4" minimum bearing required at joist ends.
3-1/2" minimum bearing required at intermediate supports.
- Option - 5-1/4" bearing without web stiffeners.
- Design properties limited to untreated, dry conditions of
use and assume lateral support full length of the compression flange.


TABLE IV
Duct Hole Chart Maximum
duct hole length
| Joist Series |
Joist Depth |
JOIST SPACING
(in. o.c.) |
| 12 |
16 |
19.2 |
24 |
| SJ-15 |
All Depths |
12" |
8" |
6" |
6" |
| SJ-25 |
9-1/2" & 11-7/8" |
13" |
9" |
8" |
8" |
| 14" & 16" |
9" |
8" |
8" |
8" |
| SJ-35 |
All Depths |
15" |
12" |
10" |
8" |
Notes:
- Do not cut or damage flanges.
- Duct holes must be located at center of span.
- Duct hole is only allowed in longest span of multiple span
joists.
- This table is valid for residential spans that meet the
floor span tables in this product guide.
- Other holes are not allowed within three times the duct hole
length.
- Allowable depth of hole is depth of web minus 1/4".
- Do not over cut corners of holes.
TABLE V
| ROUND HOLE
CHART Minimum distance from face of nearest support to center of hole. |
| JOIST |
HOLE
DIAMETER |
| SERIES |
DEPTH |
3" |
4" |
5" |
6" |
6-1/4" |
7" |
8" |
8-5/8" |
9" |
10" |
10-3/4" |
12" |
12-3/4" |
| SJ-15 |
9-1/2" 11-7/8" |
2'-0" 1'-0" |
3'-0" 1'-6" |
4'-6" 2'-6" |
6'-0" 4'-0" |
6'-6" 4'-6" |
5'-6" |
7'-6" |
8'-6" |
|
|
|
|
|
| SJ-25 |
9-1/2" 11-7/8"
14"
16" |
3'-0" 1'-0"
1'-0"
1'-0" |
4'-0" 2'-0"
1'-0"
1'-0" |
5'-0" 3'-6"
2'-0"
1'-6" |
6'-6" 5'-0"
3'-6"
3'-0" |
7'-0" 5'-6"
4'-0"
3'-6" |
6'-6" 5'-0"
4'-6" |
8'-6" 7'-0"
6'-0" |
10'-0" 8'-0"
7'-0" |
8'-6"
8'-0" |
10'-0"
9'-6" |
12'-0"
10'-6" |
13'-0" |
15'-0" |
| SJ-35 |
11-7/8" 14"
16" |
3'-0" 1'-0"
1'-6" |
4'-0" 2'-0"
3'-0" |
5'-6" 3'-6"
4'-0" |
7'-0" 5'-0"
5'-6" |
7'-0" 5'-6"
6'-0" |
8'-6" 7'-0"
7'-0" |
10'-6" 8'-6"
8'-6" |
11'-6" 9'-6"
9'-6" |
10'-6" 10'-0" |
12'-6" 11'-6" |
14'-0" 12'-6" |
15'-6" |
17'-0" |
Notes:
- Do not cut or damage flanges.
- The clear distance between holes must equal or exceed twice
the diameter of the largest hole, or three times the longest side of a rectangular hole.
- Except as noted in 1 and 2 above, a 2" diameter hole is
permitted to be drilled anywhere.
- The longest side of a rectangular hole shall not exceed
three-fourths of the allowable round hole diameter.
- This table is applicable only for uniformly loaded
StrucJoist designed using the roof and floor span tables in this Installation Guide.
Contact Willamette Industries for other applications.
|