L/LS/GA REINFORCING AND
SKEWABLE ANGLES
|


The GA Gusset Angles' embossed bend section provides added
strength. Staggered nail pattern reduces splitting and allows back-to-back installation.
L--Staggered nail pattern reduces the possibility for
splitting and allows installation on both sides of a member. LS--Field-adjustable angles
attach members intersecting at angles.
MATERIAL: L--16 gauge; GA and LS--18 gauge
FINISH: Galvanized
INSTALLATION:
- Use all specified fasteners; see General Notes.
- LS--field skewable; bend one time only.
- Joist must be constrained against rotation (for example,
with solid blocking) when using a single LS per connection.
CODES: BOCA, ICBO, SBCCI NER-413, NER-443;
ICBO 5357; City of L.A. RR 25119 and RR 25149.
| Model
No. |
L |
Fasteners
|
Down
Avg Ult |
Allowable
Loads1,2,3 |
| Floor (100) |
Roof (125) |
| GA1 |
2-3/4 |
4-10d |
612 |
185 |
185 |
| GA2 |
3-1/4 |
6-10d |
1600 |
335 |
415 |
| L30 |
3 |
4-10d |
758 |
220 |
240 |
| L50 |
5 |
6-10d |
1983 |
335 |
420 |
| L70 |
7 |
8-10d |
1983 |
445 |
555 |
| L90 |
9 |
10-10d |
4667 |
555 |
695 |
| LS30 |
3-3/8 |
6-10d |
1933 |
335 |
395 |
| LS50 |
4-7/8 |
8-10d |
2180 |
450 |
560 |
| LS70 |
6-3/8 |
10-10d |
4233 |
560 |
700 |
| LS90 |
7-7/8 |
12-10d |
3233 |
670 |
840 |
- GA and L angles--loads are for condition F1 or F2; LS
angles--loads are for condition F1 only.
- GA1 and GA2 angles--loads for F2 are 220 and 335 lbs (100)
and 280 and 415 lbs (125), respectively.
- Roof loads are 125% of floor loads unless limited by other
criteria; floor loads may be adjusted for other load durations according to the
code, provided they do not exceed those in the roof column.
- Loads are for one part only.
- Use a minimum lumber thickness of 1-3/4" For
1-1/2" lumber, use 0.81 of table load, except GA1 in F1 direction, use 185 lbs.
- Nail the L angle's wider leg into the joist to ensure table
loads and allow correct nailing, as shown in the illustration.

STC/STCT/DTC ROOF TRUSS CLIPS

For alignment control between a roof truss and nonbearing
walls; the 1-1/2" slot permits vertical truss chord movement when loads are applied.
MATERIAL:18 gauge
FINISH: Galvanized
INSTALLATION:
- Use all specified fasteners; see General Notes.
- Use STC or DTC depending on required loads. STC, installed
with Drywall Stop (DS), helps prevent fasteners tearing through the ceiling sheetrock (see
illustration).
- Use STCT where truss or rafter is separated from the top
plate of the nonbearing wall.
- Install slot nails in the middle of the slot.
| Model
No. |
Dimensions
|
Fasteners
|
Allowable
Loads1(133 & 160) |
| Plate
Base |
Vertical
Leg |
Base |
Slot |
Without
Gap2 |
With1/4"
Gap3 |
| F1 |
F2 |
F1 |
F2 |
| STC |
1-1/4x1-7/8 |
1-1/4x2-3/4 |
2-8d |
1-8d |
85 |
50 |
35 |
35 |
| STCT |
1 -1/2x 1-1/4 |
1-1/4X4-1/4 |
2-8d |
1-8d |
-- |
-- |
-- |
-- |
| DTC |
2-1/2x1-7/8 |
2-1/2X2-3/4 |
4-8d |
2-8d |
125 |
210 |
85 |
135 |
- Loads may not be increased for short-term loading.
- Truss or rafter must be bearing on top plate to achieve the
allowable loads under "WITHOUT GAP."
- Installed with maximum 1/4" space between rafter or
truss and top plate under "WITH 1/4 GAP." Where loads are not required, space is
not limited to 1/2".
|