| StrucLam
Design Stresses1 |
LVL Grade
|
Modulus of Elasticity (x106psi) |
Flexure2
Fb (psi) |
Tension Ft (psi) |
Compression
(psi) |
Horizontal Shear Fv (psi) |
| FcII |
Fcl |
| 2.0E 1.8E |
2.00 1.80 |
2950 2600 |
1900 1700 |
2750 2400 |
700 700 |
285 285 |
- Adjustments to allowable design stresses, except for E and Fc
l are permitted in accordance with the applicable code.
- Flexural Stress must be modified by the depth effect
formula: Cd=12/d 1/7.5 d=depth, 3-1/2" minimum
| 2.0E
StrucLam Design Properties Table 1-3/4" Width |
| Depth In. |
Weight PLF |
Allowable Shear Lbs |
Allowable Moment Ft-lbs |
El |
| (x106) |
| 100% |
115% |
125% |
100% |
115% |
125% |
In2
Ib. |
| 7-1/4" |
3.30 |
2411 |
2773 |
3014 |
4030 |
4635 |
5038 |
111 |
| 9-1/4" |
4.22 |
3076 |
3537 |
3845 |
6352 |
7304 |
7939 |
231 |
| 9-1/2" |
4.33 |
3159 |
3633 |
3949 |
6676 |
7677 |
8345 |
250 |
| 11-1/4" |
5.13 |
3741 |
4302 |
4676 |
9153 |
10526 |
11441 |
415 |
| 11-7/8" |
5.41 |
3948 |
4540 |
4935 |
10125 |
11644 |
12657 |
488 |
| 14" |
6.38 |
4655 |
5353 |
5819 |
13767 |
15833 |
17209 |
800 |
| 16" |
7.29 |
5320 |
6118 |
6650 |
17665 |
20315 |
22081 |
1195 |
| 18" |
8.20 |
5985 |
6883 |
7481 |
22008 |
25309 |
27510 |
1701 |
1.8E
StrucLam 1-3/4" Width |
| Depth In. |
Weight PLF |
Allowable
Shear Lbs |
Allowable
Moment Ft-lbs |
El (x106)
In2 Ib.
|
| 100% |
115% |
125% |
100% |
115% |
125% |
| 7-1/4" |
3.30 |
2411 |
2773 |
3014 |
3552 |
4085 |
4440 |
100 |
| 9-1/4" |
4.22 |
3076 |
3537 |
3845 |
5598 |
6438 |
6998 |
208 |
| 9-1/2" |
4.33 |
3159 |
3633 |
3949 |
5884 |
6767 |
7355 |
225 |
| 11-1/4" |
5.13 |
3741 |
4302 |
4676 |
8067 |
9277 |
10084 |
374 |
| 11 -7/8" |
5.41 |
3948 |
4540 |
4935 |
8924 |
10263 |
11155 |
440 |
| 14" |
6.38 |
4655 |
5353 |
5819 |
12134 |
13954 |
15168 |
720 |
| 16" |
7.29 |
5320 |
6118 |
6650 |
15569 |
17904 |
19461 |
1075 |
| 18" |
8.20 |
5985 |
6883 |
7481 |
19397 |
22307 |
24246 |
1531 |
Maximum Resistive Moment Values have been modified by the
depth effect formula Cd shown above.
| Connections
For Multiple StrucLam1 |
| Capacity (plf) for Side
Loaded Beams3,6 (See note 2 for Top Loaded Beams) |
| |
Nailed Connection |
Through Bolted Connection |
| No. of pieces |
2 rows 16d common wire at 12" o.c. |
3 rows 16d common wire at 12" o.c. |
2 rows 1/2" bolts at 24" o.c.
staggered |
2 rows 1/2" bolts at 12" o.c.
staggered |
2 rows 1/2" bolts at 6" o.c.
staggered |
| 2 3 |
560 420 |
840 630 |
600 450 |
1200 900 |
2400 1800 |
| 4 |
Not
Recommended |
Should only
be used when loads are applied to both sides of the members. |
| |
400 |
800 |
1600 |
1. Table values are based on 1 3/4" thick StrucLam. Verify the adequacy of the beam
to support imposed loads.
2. Minimum connection requirements. Use for top loaded
beams.
11- 7/8" deep (Maximum).
Minimum of 2 rows 16d common at 12" o/c.
14", 16" & 18" deep.
Minimum of 3 rows 16d common at 12" o/c.
3. Values listed are for 100% load duration.
Increase 15% for snow loaded roof conditions; 25% for non-snow roof conditions.
4. For 3 piece members, nailing specified is
for both sides.
5. Bolt holes should be drilled 1/32"
(min.) to 1/16" (max.) larger than the bolt diameter. Locate bolts a minimum 2"
from the top and bottom of the beam.
6. Table values assume uniform loads to
multiple members. Concentrated loads from one side require additional considerations.
Contact Willamette Industries Technical Support. |