 SPECIFICATIONS / FINISHES
Suggested Specification
Closer for ------------------ door shall be
electromechanical closerholder. Hold-open to be achieved by electric solenoid locking of
the closer arm slide in its track, Track, arm, slide (and) solenoid (and integral smoke
detector) to be contained in a single aluminum extrusion 1-1/2" (38mm) high,
1-1/2" (38mm) deep. Closer shall be door mounted. Track and hold-open mechanism shall
be surface mounted to the frame face for application on the pull side of the door and
frame soffit mounted for application on the push side of the door.
Single point Hold-Open shall be selective through a range
of 85º to 110º. Hold-Open point to be achieved by adjustment of a telescoping closer
arm.
Closer shall be hydraulic with full rack and pinion
enclosed in a cast aluminum alloy shell. Hydraulic fluid shall be non-gumming and
non-freezing. Closer shall have two non-critical valves to independently regulate sweep
speed and latch speed. It shall have an adjustable backcheck cushioning valve (and an
adjustable backcheck positioning valve). All valves shall be adjustable with a hex-key.
(Closer shall have spring power adjustment to permit 50% increase in closing power.)
Closer to be enclosed in a molded (Full) (Slim Style) Cover.
(Master units to have an integral smoke detector with dual
ionization chamber. Master units integral smoke detector shall have latching alarm and
reset switch.) (Slave units to be controlled by the master unit.) (Support units to be
controlled by U.L.Listed Smoke Detection Equipment.) Units to be fail safe and close the
door during any interruption to the electrical power. The hold-open solenoid coil shall
have a maximum amperage draw of (.090 Amps at 24 volts) (.035 Amps at 120 volts.) Unit
shall have a switch to permit testing of the releasing device function without alarming
the system.
All wiring connections shall be made without the need of
wire nuts or soldering.
(Maser unit(s) shall require a (24VAC-DC) (120VAC, 60Hz.)
(24VAC-DC & 120VAC, 60Hz.) power input.) (Slave unit(s) shall require a 24 Volt power
input from the Master Unit.) (Support unit(s) shall require a (24VAC-DC) (120VAC,
60Hz.) power input.) Supplier to coordinate electrical requirements with electrical and
alarm system engineers. Wiring (and conduit) by others.
Electromechanical Closer-Holders to be Yale Power Track
[(P)400(PT)(PTD)(PTS)] [(P)3200(PT)(PTD)(PTS)]
[(P)3300(PT)(PTD)(PTS)] [(P)3400(PT)(PTD)(PTS)]
[(P)3500(PT)(PTD)(PTS)] Series.
Suggested Specification (Cont.)
Executive Door Holder-Release "PT-RF"
Power input to unit shall be 120 Volts AC at 60 Hz. Unit
hall have an integral radio frequency receiver. When the door is held open, the signal
from a (hand-held) (desk mounted) transmitter shall interrupt power to the unit and
release the door from hold open. Power to the transmitter shall provided by a standard 9
Volt alkaline battery. [(P)400PT-RF] [(P)3200PT-RF]
[(P)3300PT-RF] [(P)3400PT-RF] [(P)3500PT-RF].
Finishes
Sprayed Finishes - All Yale Power Track
400 Series/ 3000 Series Electromechanical Closer-Holders are available in the following
sprayed finishes. Order sprayed finishes by the Yale Symbol.
Finish
Description |
BHMA
Symbol |
Yale
Symbol |
| Silver Bronze
(Alum.) |
689 |
SB |
| Dull Bronze |
691 |
BL |
| Black |
693 |
315 |
| Gold |
696 |
GB |
| Dark Statuary Bronze |
690 |
STAT |
| To Complement Duradonic |
| Medium Amber |
694 |
312 |
| Dark Amber |
695 |
313 |
| Black |
693 |
315 |
| Corrosion Inhibitor |
| Beige Prime Coat* |
600 |
SRI |
* Available at extra cost. Closer-Holders
can be ordered prime coated only, i.e. (SRI), or prime coated with finish coat, i.e. (SRI)
x (DB). |