 4210 SERIES MASTER UNITS
Pull (hinge) side mounting Rigid Slide Arm and
Track
Mater Units with Integral Smoke Detector
Series 4210MPDI: Infinite Hold-Open
Series 4210MPDS: Selective Hold-Open
Executive Door Holder/Release
Series 4210RFI: Infinite Hold-Open
Series 4210RFS: Selective Hold-Open

Single Doors
Master Units with Integral Smoke Detector: Both
Series 4210MPDI and series 4210MPDS are self-contained and can be installed to control a
single door.
Executive Door Holder/Release: Both
Series 4210RFI and 4210RFS are self-contained and can be installed to control a
single door.
Pairs of Doors
Master Units x Slave Unit: Smoke Detector
in the Master Unit controls its own closer-holder solenoid and the solenoid in the Slave
Unit.
Master Unit x Tandem Unit: Smoke Detector
in the Master Unit signals conditions (stand-by, Trouble / Alarm) to an alarm systems
panel. This panel controls the signal to the hold-open solenoids in both the Master Unit
and the Tandem Unit.
Executive Door Holder x Slave Unit: Consult
the factory for details of this installation.
These Closer-Holders are surface mounted to the pull
(hinge) side frame face. These units require a minimum ceiling clearance of 4"
(102mm) and a maximum frame reveal of 1/8" (3mm). + The slide track mounts directly
to the door. Units can be installed as shipped to accommodate doors opening to 180º with
a maximum hold-open point of 175º. The buffer block assembly in the track will
accommodate doors opening to 125º. An auxiliary door stop is required for doors opening
beyond 125º.
+Double Egress Frames (Deep Reveals):
Where the pull (hinge) side frame reveal exceeds 1/8" (3mm), a special slide arm is
available to order. This arm will accommodate frame reveals in excess of 1/8" (3mm)
up to 3"(76mm) with a maximum allowable door swing of 110º. Order Series 4250MPDI,
4250MPDS, 4250RFI or 4250RFS.


Door Sizes and List Numbers
| MAXIMUM* DOOR SIZE FT.IN. (METERS) |
YALE LIST NUMBER |
| MASTER UNIT CLOSER-HOLDER |
EXECUTIVE DOOR HOLDER/RELEASE |
| INFINITE HOLD-OPEN |
SELECTIVE HOLD-OPEN |
INFINITE HOLD-OPEN |
SELECTIVE HOLD-OPEN |
| 3'-4" (1.00) |
4213MPDI |
4213MPDS |
4213RFI |
4213RFS |
| 3"8" (1.10) |
4214MPDI |
4214MPDS |
4214RFI |
4214RFS |
| 4"-0"(1.20) |
4215MPDI |
4215MPDS |
4215RFI |
4215RFS |
*Minimum door size is 2'-4" (.70M).
Electrical Data Master Units
| MASTER UNIT LIST
NUMBER |
NUMBER POWER INPUT
LINES* (PAIRS) |
OPERATING VOLTAGE
(INPUT) |
AMPERAGE DRAW
(AMPERES) |
(CAN BE) USED IN
CONJUNCTION WITH |
| SMOKE DETECTOR |
SOLENOID COIL |
| STANDBY |
ALARM |
| 4210MPDI-24 4210MPDS-24 |
1 1 |
4213MPDS |
.016@ 24VDC |
.035@ 24VDC |
.070@ 24VDC |
Slave Unit 4210MPSI-24 Slave Unit 4210MPSS-24 |
| 4210MPDI-120 4210MPDS-120 |
1 1 |
4214MPDS |
.070@ 24VDC |
Slave Unit 4210MPSI-24 Slave Unit 4210MPSS-24 |
| 4210MPDI-240x120 4210MPDS-240x120 |
2 2 |
24VAC/DC for Detection Input.
AND 120VAC for Solenoid Coil Input |
.035@ 24VDC |
Tandem Unit 4210MPTI-120 Tandem Unit 4210MPTS-120 |
Electrical Data Door Holder/Release
| EXECUTIVE DOOR HOLDER/RELEASE
LIST NUMBER |
NUMBER POWER INPUT LINE*
(PAIRS) |
OPERATING VOLTAGE (INPUT) 24VDC |
AMPERAGE DRAW (AMPERES) |
| SOLENOID COIL |
INTERRUPTING SWITCH |
| 4210RFI-120 |
1 |
120VAC |
.070@ 24VDC |
.015 @ 210VAC |
| 4210RFS-120 |
1 |
*Pairs of input lines required to supply Operating Voltage
or Voltages to the unit. Pairs listed do not include signal wires to Alarm Panels nor
control wires to other units' solenoids. Maximum / Minimum Operating Voltage Parameters:
+10%; -15%.
 |
| Rigid Slide Arm |
 |
| Double Egress
Arm(Handed) |
|