 4210 SERIES SLAVE/TANDEM UNITS
Pull (Hinge) side mounting Rigid Slide Arm and
Track
Slave Units Controlled by Master Unit Smoke
Detector
Series 4210MPSI: Infinite Hold-Open
Series 4210MPSS: Selective Hold-Open
Tandem Units Controlled by Signal from Alarm Panel
Series 4210MPTI: Infinite Hold-Open
Series 4210MPTS: Selective Hold-Open

Pairs of Doors
Master Units x Slave Unit: Smoke Detector
in the Master Unit controls the closer-holder solenoids in the both the Master Unit and
the Slave Unit.
Master Unit x Tandem Unit: Smoke Detector
in the Master Unit signals conditions (stand-by, Trouble / Alarm) to an alarm systems
panel. This panel controls the signal to the hold-open solenoids in both the Master Unit
and the Tandem Unit.
These Closer-Holders are surface mounted to the pull
(hinge) side frame face. These units require a minimum ceiling clearance of 4"
(102mm) and a maximum frame reveal of 1/8" (3mm). + The slide track mounts directly
to the door. Units can be installed as shipped to accommodate doors opening to 180º with
a maximum hold-open point of 175º. The buffer block assembly in the track will
accommodate doors opening to 125º. An auxiliary door stop is required for doors opening
beyond 125º.
+Double Egress Frames (Deep Reveals):
Where the pull (hinge) side frame reveal exceeds 1/8" (3mm), a special slide arm is
available to order. This arm will accommodate frame reveals in excess of 1/8" (3mm)
up to 3"(76mm) with a maximum allowable door swing of 110º. Order Series 4250MPSI OR
4250MPSS Slave Units; Series 4250MPTI or 4250MPTS Tandem Units.


Door Sizes and List Numbers
| MAXIMUM* DOOR SIZE FT.IN. (METERS) |
YALE LIST NUMBER |
| MASTER UNIT CLOSER-HOLDER |
TANDEM UNITS |
| INFINITE HOLD-OPEN |
SELECTIVE HOLD-OPEN |
INFINITE HOLD-OPEN |
SELECTIVE HOLD-OPEN |
| 3'-4" (1.00) |
4213MPSI |
4213MPSS |
4213MPTI |
4213MPTS |
| 3"8" (1.10) |
4214MPSI |
4214MPSS |
4214MPTI |
4214MPTS |
| 4"-0"(1.20) |
4215MPSI |
4215MPSS |
4215MPTI |
4215MPTS |
*Minimum door size is 2'-4" (.70M).
Electrical Data
| TYPE OF UNIT & LIST NUMBER |
NUMBER POWER INPUT LINE*
(PAIRS) |
OPERATING VOLTAGE |
AMPERAGE DRAW SOLENOID
COIL (AMPERES) |
(CAN BE) USED IN CONJUNCTION
WITH MASTER UNIT |
| SLAVE 4210MPSI |
1 |
(INPUT) 24VAC/DC for Detection Input. AND
120VAC for Solenoid Coil Input |
.070 @ 24VDC |
4210MPDI-24 4210MPDI-120 4210MPDS-24
4210MPDS-120 |
| SLAVE 4210MPSS |
1 |
120VAC |
.035 @ 24VDC |
4210MPDI-240x120 4210MPDS-240x120 |
Maximum / Minimum Operating Voltage Parameters: = 10%; -15%
 |
| Rigid Slide Arm |
 |
| Double Egress
Arm(Handed) |
|