 4220/4230 SERIES SLAVE/TANDEM UNITS
Push (Stop) Side Mounting Double Lever Arm
Slave Units Controlled by Master Units Smoke
Detector
Slave Unit Series 4220MPSI/4230MPSI: Infinite
Hold-Open
Slave Unit Series 4220MPSS/4230MPSS: Selective Hold-Open
Tandem Units Controlled by Signal from Alarm Panel
Tandem Unit Series 4220MPTI/4230MPTI: Infinite
Hold-Open
Tandem Unit Series 4220MPTS/4230MPTS: Selective Hold-Open

Pairs of Doors
Master Units x Slave Unit: Smoke Detector
in the Master Unit controls the closer-holder solenoids in the the Master Unit and Slave
Unit.
Master Unit x Tandem Unit: Smoke Detector
in the Master Unit signals conditions (stand-by, Trouble / Alarm) to an alarm systems
panel. This panel controls the signal to the closer-holder solenoids in both the Master
Unit and the Tandem Unit.
These Closer-Holders are surface mounted to the push (stop)
side frame face. The standard mounting for these units require a minimum ceiling clearance
of 3-1/2" (89mm). Where ceiling clearance is between 2" and 3-1/2" (51mm
and 89mm) , the standard backplate for the 4220 Series or 4230 Series can be inverted to
allow for a drop application. Use of a No. 4299 decorative backplate is recommended to
conceal the exposed mounting holes on the standard backplate. Different mounting
dimensions are required for the drop application. The double lever arm mounts directly to
the door,. These units can be installed to accommodate door openings to 180º with a 170º
maximum hold-open point.


Door Sizes and Catalog Numbers
| MAXIMUM* DOOR SIZE
FT.IN. (METERS) |
YALE LIST NUMBER |
MAXIMUM DEGREE OF
DOOR OPENING |
REVEAL RANGE
INCHES (MILLIMETERS) |
| SLAVE UNITS |
TANDEM UNITS |
| INFINITE HOLD-OPEN |
SELECTIVE HOLD-OPEN |
INFINITE HOLD-OPEN |
SELECTIVE HOLD-OPEN |
| 3"-6" (1.10) |
4223MPSI |
4223MPSS |
4223MPTI |
4223MPTS |
180º |
2-3/4-4 (70-102) |
| 165º |
4-7 (102-179) |
| 4233MPSI |
4233MPSS |
4233MPTI |
4233MPTS |
180º |
4-7 (102-179) |
| 4"-0"(1.20) |
4224MPSI |
4224MPSS |
4224MPTI |
4224MPTS |
180º |
2-3/4-4 (70-102) |
| 165º |
4-7 (102-179) |
| 4234MPSI |
4234MPSS |
4234MPTI |
4234MPTS |
180º |
4-7 (102-179) |
Electrical Data
| TYPE OF UNIT & LIST NUMBER |
NUMBER POWER INPUT LINES (PAIRS) |
OPERATING VOLTAGE (INPUT) |
AMPERAGE DRAW SOLENOID COIL (AMPERES) |
(CAN BE) USED IN CONJUNCTION WITH MASTER
UNIT |
| SLAVE 4220MPSI
SLAVE 4230MPSI |
1 |
24VDC (ONLY) SUPPLIED FROM
MASTER UNIT |
.070 @ 24VDC |
4220MPDI-24 4230MPDI-24 |
| 4220MPDI-120 4230MPDI-120 |
| SLAVE 4220MPSS
SLAVE 4230MPSS |
4220MPDS-24 4230MPDS-24 |
| 4220MPDS-120 4230MPDS-120 |
| TANDEM 4220MPTI TANDEM 4230MPDI |
1 |
24VAC |
.035 @ 24VDC |
4220MPDI-240x120 4230MPDI-240x120 |
| TANDEM 4220MPTS TANDEM 4230MPTS |
4220MPDS-240x120 4230MPDS-240x120 |
Maximum / Minimum Operating Voltage Parameters: = 10%; -15%
| MINIMUM DOOR SIZE FT.
IN.(METERS) |
FOR DOOR OPENING OF |
| 2'4" (.70) |
100º |
| 2'-2" (.65) |
100º TO 180º |
|