IEC Hi-Performance
Fan Coil Units
HHY - Horizontal Hideaway
- 600 to 2000 CFM
- Designed to meet the many varied requirements for a ceiling
hideaway installation where there is a ducted, high-static application
- Standard with a galvanized finish
HPY - Horizontal Hideaway with Plenum
- 600 to 2000 CFM
- The same basic features of the HHY, plus a return-air plenum
- Shipped complete, ready for installation with the plenum
section in place
- No field fabrication is required
- Standard with a galvanized finish
HLY - Horizontal Cabinet, Low Static

- 600 to 2000 CFM
- Cabinet unit for exposed under-ceiling applications where
high capacities are required without ducting
- Supplied with integrated double-deflection discharge grille
and a bar-type return-air grille with a throwaway filter
- Standard cabinet with durable powder-paint finish
HXY - Horizontal Cabinet High-Static
- 600 to 2000 CFM
- For above or below the ceiling
- For high-static ducted applications where high output is
required
- Standard units are of galvanized finish
VEY - Vertical Closet
- 600 to 2000 CFM
- For floor-mounted, vertical, ducted applications
- Normally installed behind partition walls or located in
closets, utility rooms, or other concealed locations
- Units have a removable front-access panel for complete
access to coil and motor-blower sections
- The top panel has a one-inch duct flange
- Standard with a galvanized finish
ARI RATINGS*- HI-PERFORMANCE
SERIES - 60hz
(Performance Ratings at Standard ARI Conditions)
(For 50 Hz unit information, please
contact the factory.)
*Hi-Performance Series units are certified in
compliance with the Air Conditioning and Refrigeration Institute (ARI), Industry Standard
440-89 for room fan coil units. Approved standard ratings are tabulated below.
| Models |
Nom. CFM |
Coil |
Total
BTUH |
Sensible
BTUH |
| HHY |
600 |
B |
18,100 |
13,700 |
| HLY |
800 |
B |
23,400 |
17,600 |
| HLY |
1000 |
B |
33,300 |
24,000 |
| HLY |
1200 |
B |
41,800 |
30,200 |
| HLY |
1400 |
B |
48,900 |
34,000 |
1. Based on 80° DB and 67° WB EAT, 45° F EWT, 10° F
temperature rise, high fan speed. Motor voltage 115/1/60. Air flow under dry coil
conditions. Ducted models tested @ 0.05 external static pressure.
Product information is for advertising purposes only and
is subject to change. Please consult the factory or your authorized IEC representative for
actual information before ordering. |