Honeywell Inc. 74-2073: XLS100 Fire Alarm System. CSI 3-Part Specifications.

|
XLS100 Fire Alarm System

|
SPECIFICATION DATA |

|
Features
- Modular System Design for Small to Large Applications
- 168-Character Display Area for Automatic Display of System Messages
and Alarms
- Three-second Alarm Response Over Any Size Network
- Total Network Wiring Over 300,000 Feet (91,440 m)
- Eight Multiplexed Channels for Audio Source Selection on One Pair of
Wires
- Zoned Audio Amplifiers
- Slide-in LED and Switch Labels
- Support for a Wide Variety of Detectors and Modules
- Automatic Device and Panel Addressing
- 250 Devices Per Loop, 1250 Devices Per Node
- 750ms Signature Loop Alarm Response
- Device Circuit Mapping
- Proprietary and Local System Operations
- For Retrofit, Existing Wire may be used if Electrically Sound
|
GENERAL
The XLS1000 Fire Alarm System is an adaptable life safety system for a wide
range of building sizes from small to large. It is modularly designed to fit
stand-alone, single-node systems as well as multi-node networks. XLS1000
Systems can also incorporate audio functions that use the same
fundamental components as the fire alarm functions to simplify system
layouts.
System Definition Utility software helps define custom system operations
quickly and easily. Virtually all XLS1000 operating features are
software-controlled to provide for site customization and the ability to quickly
implement future operational changes and upgrades.
|
|
DESCRIPTION
The XLS1000 Fire Alarm System is modularly designed for easy customization to
fit stand-alone, single-node systems as well as multi-node networks. To simplify
system layouts, XLS1000 Systems also integrate audio functions using the same
fundamental components as the fire alarm functions. To provide for site
customization and the ability to quickly implement future operational changes and
upgrades, virtually all XLS1000 operating |
features are software-controlled. System Definition Utility software helps define
flexible system operations quickly and easily.
System Components:
The XLS1000 is housed in a wall box that can contain a variety of system
components arranged as shown in the following diagram. |

System Components.
The housing can be mounted flush (set back within a wall), semi-flush (partially set
into a wall), or on a wall surface. The Chassis and Local Rail Modules provide a
base for the installation of one or modules (Control Display Modules) such as a
Main Display Interface module and a system of generic modules that maximize
design flexibility for custom systems. The Inner Door Cover and Outer Door Cover
protect the components and provide an attractive finish to the system. |
Main Display Interface Module:
The Main Display Interface module provides simple-to-understand lights (LEDs) and
switches to help emergency operators execute system commands with
confidence. Common control switches and LEDs include (at minimum) a Reset
switch and LED; Alarm Silence switch and LED; Panel Silence switch and LED;
and Drill switch and LED. Eight lines of 21 characters (168 characters total) display
emergency information in a useful text format. The following figure illustrates the
layout of the module. |

Optional Main Display Interface Module and Display Module Panel.
The eight-line text display area shows current date, current time, and number of
alarms on the first line. The next lines show the first highest priority event, the last
highest priority event, and other information as applicable, so that operators can
view alarm data without opening the door of the XLS1000. Note that a Main Display
Interface module is not required in remote nodes with no user interface
requirements.
The Main Display Interface also provides a Command Menu for maintenance
functions such as disabling alarms or generating reports for use by staff or service
personnel.
Display Modules:
Generic control/display modules provide membrane switches with positive tactile
feedback and colored LEDs to give the emergency user the simplest of interfaces.
To maximize system layout flexibility, Control/Display module locations are
independent of the underlying connection hardware to the local rail module. The
LCD area displays custom event messages of up to 42 characters.
Panel Capacities:
XLS1000 facilitates isolation of field wiring with building wiring terminations made to
removable terminal blocks on the local rail modules. XLS1000 local rail modules
include zone amplifiers, Loop Controllers, conventional hardwired modules, and the
main CPU module. System design allows convenient separation of high voltage
from power-limited wiring. |
XLS1000 supports both single-node and multiple-node single network systems. As
a stand-alone panel (or single node), up to four power supplies provide 28A of power
with space available for 5 to 21 local rail modules. A single panel supports up to five
Loop Controllers (250 devices per loop, 1250 points total per node). With only
conventional circuits, panel capacity is up to 15 local rail modules which support
120 conventional zones. Up to half of the conventional circuits can be Notification
Appliance Circuits. A Main Display Interface module and 19 Control Display module
configurations are available.
Networks:
XLS1000 operates on a multi-priority peer-to-peer token ring network. The
multi-priority token ring gives XLS1000 an exceptional alarm response time of less
than 3 seconds across the network, virtually independent of the total number of
nodes. XLS1000 token ring network configuration also affords long distances
between nodes. The distance between panels on 14 AWG (2.087 sq. mm) wire is
5000 ft (1524 m). With 64 nodes supported on a network, total network length is in
excess of 300,000 ft (91,440 m).
Network communication is via RS-485 serial ports. This two-wire circuit supports
Class A or B. The XLS1000 network meets NFPA style 7 communications
standards in Class A configuration. |
The XLS1000 uses distributed database technology designed to survive the rigors of
fire and fire fighting. In a Class B configuration, a single break or short on the
network wiring isolates the system into two groups of panels, each with one or
more nodes. Each group of panels re-configures into a peer-to-peer subnetwork,
working with their combined databases. In Class A, a single break or short on the
network wiring causes the system to isolate the fault. Network communication
continues uninterrupted. If multiple faults occur, the network re-configures into
multiple networks and functions as described for Class B. The system continues to
respond to operations at every node able to receive network messages with those
nodes always executing the local response.
Audio Functionality:
XLS1000 integrates audio components in its standard fire alarm cabinet
assemblies. XLS1000 uses intelligent zone amplifiers to reduce wire runs and
space needs at a central location. Audio control equipment and zone amplifiers use
the same system power supplies as the fire alarm components. All these
components use a common standby battery. For multiple-node systems, a single
pair of wires carries eight channels of digital audio data between nodes. The
system can deliver up to eight messages and/or signals simultaneously, so
signaling messages to occupants are never interrupted. This feature eliminates
confusion if the emergency user requires an audio channel with zone-specific
messages.
The XLS1000 provides simple paging controls. ALL CALL operation selects all
paging zones for message delivery. Page to EVACUATION operation automatically
selects all areas in evacuation. Similarly, the user can Page to ALERT. Zoned
paging requires the user to simply select a zone paging switch. After the user
completes a page delivery, signaling automatically restores after the user releases
the microphone talk key. |
Audio system amplifiers can operate 25 Vrms or 70.4 Vrms speakers. The system
provides simultaneous page, alert, and evacuation signaling. The system provides
the followingpaging common controls and indicators (at a minimum):
- Ready to page LED
- VU display of paging output level
- Single switch function for paging to all - Alert zones, Evacuation zones, or
areas not programmed for signaling.
Alarm Annunciation:
XLS1000 provides Alarm, Supervisory, Trouble, and Monitor operations.
Annunciation is through the use of LED display strips complete with custom labels
for each LED as to its function. Where applicable, control of remote smoke control
devices is available at the control center. Switches with LEDs provide positive feed
back to the operator of remote equipment status. See the Optional Main Display
Interface Module and Display Module Panel figure for an example.
Support for a Wide Variety of Fire Alarm Equipment: XLS1000 supports a
variety of conventional smoke detectors with a single universal module. It also
supports polarized bells, horns, and strobes, as well as hardwired supervisory and
monitor functions with latching or non-latching operations. Any circuit located
anywhere on the network can display on any LCD or LED annunciator.
Battery Options:
Available cabinet room allows for system batteries up to 17 Ah. One 24V backup
battery supports up to four power supplies. The power supplies are arranged in
parallel to ensure optimization of the full capacity each power supply. Each supply
provides up to 7A of current, therefore, with four supplies, 28A of current is
available, all backed up by one battery. A single panel or node supports batteries
up to 65 Ah to give XLS1000 initial system cost savings, as well as continuing cost
saving benefits in system maintenance. |
TYPICAL WIRING

ORDERING
Loop Controller
Catalog Number |
Description |
3-DSDC |
Dual SIGA Data Controller with one SIGA Data Board. Mounts to Local Rail. |
Modules, Amplifiers, Power Supplies, and Boards
Catalog Number |
Description |
3-LDSM |
LED Display Support Module |
3-24R |
24 Red LED Display Module |
3-24Y |
24 Yellow LED Display Module |
3-24G |
24 Green LED Display Module |
3-12SR |
12 switches with 12 Red LED Display/Control Module |
3-12SY |
12 switches with 12 Yellow LED Display/Control Module |
3-12SG |
12 switches with 12 Green LED Display/Control Module |
3-12RY |
12 Red LED and 12 Yellow LED Display Module |
3-12/2Y |
12 groups of two Yellow LED Display Module |
3-12/RY |
12 groups of one Red and one Yellow LED Display Module |
3-12/S1GY |
12 switches with one Green and one Yellow LED per switch Display/Control Module |
3-12/S1RY |
12 switches with one Red and one Yellow LED per switch Display/Control Module |
3-ZA15 |
15W Zoned Amplifier Selectable for 70 or 25Vrms operation |
3-ZA30 |
30W Zoned Amplifier Selectable for 70 or 25 Vrms operation |
3-PPS/M |
Primary Power Supply with local rail module 120V 50/60 Hz |
3-BPS/M |
Booster Power Supply with local rail module 120V 50/60 Hz |
3-PPS/M-230 |
Primary Power Supply with local rail module 230V 50/60Hz |
3-BPS/M-230 |
Booster Power Supply with local rail module 230V 50/60 Hz |
3-IDC8/4 |
Initiating Device Circuit Module |
3-OPS |
Off Premises Signaling module |
3-ASUFT |
Audio Source Unit with local microphone and Firefighters Telephone |
3-ASU |
Audio Source Unit with Local Microphone. Provides four local rail spaces. |
3-ASUMX |
Audio Source Unit Memory Expansion. Provides 36 minutes of message time. |
3-CPU |
Main Panel Processor |
3-XMEM |
Memory Expansion Board |
3-RS485 |
Network Communication Board |
3-RS232 |
RS-232 Communication Board |
Lobby Enclosures - Outer doors with Viewing Window
3-CAB5 |
Cabinet w/Wallbox and door |
5 local rail modules
One footprint and
1/2 footprint module |
two - 12V10A |
3-CAB7 |
Wallbox only
|
1- Chassis |
two - 12V17A |
3-CAB7D |
Inner door and outer doors
for 3-CAB7B |
N/A |
N/A |
3-CAB14B |
Wallbox only |
2 Chassis |
two - 12V17A |
3-CAB14D |
Inner door and outer doors
for 3-CAB14B |
N/A |
N/A |
3-CAB21B |
Wallbox only |
3 Chassis |
two - 12V17A |
3-CAB21D |
Inner door and outer doors
for 3-CAB21B |
N/A |
N/A |
Remote Chassis Enclosure - No viewing window
3-RCC7 |
Wallbox with outer louvered cover |
1 Chassis |
two - 12V17A |
3-RCC14 |
Wallbox with outer louvered cover |
2 Chassis |
two - 12V17A |
3-RCC21 |
Wallbox with outer louvered cover |
3 Chassis |
two - 12V17A |
Chassis Assemblies
3-CHASS |
Chassis Assembly - Takes one Chassis space in wallbox, no local rail module mounting, Space for up to two power supplies and a
1/2 footprint module. |
3-CHAS7 |
Chassis Assembly - Takes one Chassis space in wallbox, provides 7 local rail module spaces, space for up to two power supplies
and a 1/2 footprint module. |
3-CHAS4 |
Chassis Assembly - Takes one Chassis space in wallbox, provides 4 local rail module spaces, provides space for a Audio source
card, paging common control and four local rail modules. |
Battery Cabinet
3-BC |
Space for two 20 to 65 Ah batteries. Provision for remote temperature monitoring. Provides terminals for up to four Power Supplies. |
Accessories
3-TAMP |
Tamper switch for 3-CAB series cabinets. Mounts to side of cabinet. |
3-LCD |
Main Display Interface /w LCD |
NOTE: All cabinets and doors have a textured white enamel finish, doors are available as red by adding the suffix -R to catalog number, for example, CAB7D-R.
SPECIFICATIONS
Model:
- XLS1000 Fire Alarm System
Power Input:
Each XLS1000 can support up to 4 power supplies, depending on the cabinet
configuration. There can be only one 3-PPS/M primary power supply, and up to
three 3-BPS/M booster power supplies.
3-PPS/M or 3-BPS/M
3.0A, 50-60 Hz.
3-PPS/M-230 or 3-BPS/M-230
1.5A, 50-60 Hz. |
120 VAC +10%, -15%,
230 VAC +10%, -15%, |
Operating Environment:
32 Deg. F (0 Deg. C) to 120 Deg. F (49 Deg. C), 93% RH, non-condensing |
Electrical Characteristics:
Operating Voltage: 24Vdc
Operating Alarm Current: 7.0 A max./power supply

This product must be installed and operated within its environmental,
mechanical, and electrical specifications as contained in this
document. In case of service, use only listed/approved replacement
parts ordered directly from the manufacturer. Failure to do so can
result in loss of safety function, degraded operation, or damage to
this product.
|
Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis, Minnesota 55408-0524
Honeywell Latin American Region
480 Sawgrass Corporate Parkway
Suite 200
Sunrise, FL 33325 |
Home Building Control
Honeywell Limited - Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
M2H 3N7
Honeywell Europe S.A.
3 Avenue du Bourget
B-1140 Brussels
Belgium |
Honeywell Asia Pacific Inc.
Room 3213-3225
Sun Hung Kai Centre
No. 30 Harbour Road
Wanchai
Hong Kong |
74-2073---2 T.M. Rev. 2-98 |
|
www.honeywell.com |
Products: Honeywell Inc. Product Specs