SPECIFICATIONS
Model:
- 14507532-001 XLS200/1000 F&S Bus Interface.
Mounting:
In CAB7 Lobby Enclosure or RCC7 Remote Closet Cabinet or larger, F&S Bus Interface board occupies a full
footprint.
In CAB5 Lobby Enclosure, F&S Bus Interface board
mounts to inside of inner dead-front door using 14507606-001 Mounting Bracket.
Capacities:
29 panel addresses per F&S bus.
1500 points total per F&S bus.
Maximum of one XLS200/1000 panel reporting through the F&S Bus Interface.
Maximum of 967 points per XLS1000 (same as to FS90 Plus).
Addressable loops on the XLS panel are limited to 100 sensors and 99 modules, and devices that can be
mapped over to the workstation.
Connections:
RS-232 connection for XLS panel CPU.
RS-485 redundant connection for F&S Bus.
Power connection to XLS panel power supply.
Wiring:
Terminal Wiring Gage: 18 to 14 AWG (0.8 to 2.0 mm 2
Class A or B.
Electrical Characteristics:
Operating Voltage: 24V dc at 75 mA
Operating Standby Current: 75 mA
Operating Alarm Current: 75 mA
Maximum F&S Bus Circuit Ratings:
Resistance: 50 ohm max
Capacitance: 0.1 max |