74-2772: XBS-XLS LAN Interface. CSI 3-Part Specifications.
|
XBS-XLS LAN Interface
14006098-646100 SERIES

|
SPECIFICATION DATA |

GENERAL
The Excel Building SupervisorExcel Life Safety Local Area Network
Interface (XBSXLS LAN Interface) allows any XBS workstation to display
and command Excel Life Safety 1000 (XLS1000) system points via a
dedicated industry standard Ethernet or Token Ring LAN.
The XBSXLS LAN Interface consists of multiple microprocessor-based,
real time function boards assembled within a chassis which mounts
inside an XLS1000 enclosure. The XBSXLS LAN Interface receives 24V
dc power directly from the XLS panel so no separate power supplies or
battery backup are necessary (required for UL864 listing). 100-240 Vac
power models are also available. A RS-232 port interfaces to the XLS
panel CPU and a Network Interface Card (NIC) provides a LAN
connection. A second RS-232 port interfaces to a PC to accomplish
configurations and upgrades.
The XBSXLS LAN Interface supports communications for up to 32
XLS200/1000 panels for up to 40,000 points. The XLS panels connect to
the XBSXLS LAN Interface via the XLS high speed peer network. Points
from an XLS panel can be used as initiators for event-initiated actions
within the XBS. These actions can command points in other XBS
subsystems, such as Excel Plus, Excel 500, and FS90 through the XBS
workstation. |
FEATURES
- XBS workstation connection for XLS points via LAN
- One XBS-XLS LAN interface serves entire XLS200/1000 subsystem:
- XLS system point display and command from any XBS workstation
- Up to 40,000 points available from 32 XLS nodes
- XLS points served via XLS high speed peer network
- Meets requirements of UL864 UOJZ for fire alarm control unit
- Communications via industry standard TCP/IP protocol sets:
- Allows other XBS subsystems to coexist on the LAN
- Programming contained in self-contained, non-volatile solid-state
memory
- 24 volt dc power supplied directly from XLS1000 (24 volt dc models only)
|
SPECIFICATIONS
Model:
- 14006098-646100 XBSXLS LAN Interface chassis with 24 Vdc power converter and 14507614-002 Token Ring
NIC.
- 14006098-646110 XBSXLS LAN Interface chassis with 24 Vdc power converter and 14507615-001 Ethernet NIC.
- 14006098-646120 XBSXLS LAN Interface chassis with 100-240 Vac power supply and 14507614-002 Token Ring
NIC.
- 14006098-646130 XBSXLS LAN Interface chassis with 100-240 Vac power supply and 14507615-001 Ethernet
NIC.
Mounting Space:
One XLS1000 chassis space
LAN Wiring:
Per IEEE 802.3 Ethernet or 802.5 Token Ring Standards |
Electrical Characteristics:
Power Supply Input: 24
Vdc or 100-240V ac, 50-60
Hz
Operating Voltage: 24 Vdc
from XLS1000
Operating Standby
Current: 600 mA
Operating Alarm Current:
600 mA
1.20A (rms) for 115 Vac
input
0.70A (rms) for 230 Vac
input
Communications:
Interface to XLS1000: RS-232
LAN: Ethernet or Token Ring
Environmental Operating
Limits:
Temperature: 32 to 120°F (0 to 49°C)
Humidity: 10 to 90% rh noncondensing
Finish:
Galvanized CRS
Shipping Weight:
9.0 lb (4.0 kg)
Approvals:
UL864 UOJZ, UL1076 APOU
|
|
|

Typical XBSXLS LAN Interface Block Diagram.
Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis, Minnesota 55408-0524
Honeywell Latin American Division
480 Sawgrass Corporate Parkway
Suite 20
Sunrise FL 33325 |
Home Building Control
Honeywell Limited - Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
M2H 3N7
Honeywell Europe S.A.
3 Avenue du Bourget
B-1140 Brussels
Belgium |
Honeywell Asia Pacific Inc.
Room 3213-3225
Sun Hung Kai Centre
No. 30 Harbour Road
Wanchai
Hong Kong |
74-2772 L.A. 11-97 |
|
www.honeywell.com |