C7770A Air Temperature Sensor

|
FEATURES
- Primary and/or secondary sensor for use with electronic control
systems.
- Integral 20K ohm NTC nonlinearized sensor.
- Operating range of 45 to 99°F (7.2 to 37.2°C).
- Mounts on a flat duct or plenum surface or, for a plenum-rated
application, in a standard utility conduit box.
- Probe length of 6-1/2 (165 mm) and a nominal
sensorresistance of 8000 ohms at 77°F (25°C).
- Rugged aluminum insertion probe.
|
GENERAL
The C7770A Air Temperature Sensor is a direct wired temperature sensor that is used to sense discharge or return air in a duct that may be
controlled by an Excel 10 Controller. The C7770A Sensor contains a temperature sensitive 20K ohm NTC nonlinearized thermistor.
DESCRIPTION
The C7770A Air Temperature Sensor is a direct wired temperature sensor that is used to sense discharge or return air in a duct that may be
controlled by an Excel 10 Controller. The C7770A Sensor contains a temperature sensitive 20K ohm NTC nonlinearized thermistor.
SPECIFICATIONS
Model:
C7770A Air Temperature Sensor.
Operating Range
45 to 99°F (7.2 to 37.2°C).
Temperature Sensor Accuracy:
The C7770A is furnished with a 20K ohm nonlinear NTC temperature sensor that follows a specific temperature-resistance curve. See Fig. 1.
Honeywell controllers used with the C7770A employ an algorithm that provides readings close to the actual temperature. Table 2 summarizes
the C7770A nonlinearized sensor accuracy for normal operating temperatures. Across the range of 41 to 99°F (5 to 37°C) the accuracy is
better than ±0.75°F (±0.42°C).


Input Rating:
0.5 mA pulsed constant current.
Mounting Options:
Mounts on flat duct or plenum surface or, for a plenum-rated applications, in a standard utility conduit box.
Dimensions:
Probe Length(including mechanical strain relief): 6-1/2 in. (165 mm).
Probe Diameter: 3/8 in. (13 mm). Mechanical strain relief on the flange end of probe is 1/2 in. (13 mm) diameter.
Flange Height: 7/8 in. (22 mm).
Flange Width: 2 in. (51 mm).
Environmental Ratings:
Operating Temperature: 45° to 99°F (7.2° to 37.2°C).
Shipping Temperature: 40° to 150°F (-40° to 65°C).
Relative Humidity: 5% to 95% noncondensing.
Vibration: V2 level.
Corrosion: Office environment.
Approvals:
NEC Class II.
Home and Building Control Honeywell Inc.
Honeywell Plaza P.O. Box 524 Minneapolis,
MN 55408-0524 |
Home and Building Control Honeywell
Limited-Honeywell Limitee 155 Gordon
Baker Road North York, Ontario M2H 3N7 |
Home and Building Control Products
Honeywell AG
Boblinger Strabe 17
D-71101 Schomaich
Phone (49-7031) 637-01
Fax (49-07031) 637-493 |