DUCT SMOKE DETECTOR HOUSING
ACCESSORIES
Air Sampling Tubes
The Duct Detector Housing uses an air sampling inlet tube
and an exhaust tube. Air sampling tubes are available in
lengths from 8 in. (200 mm) to 10 feet (3m) and must be
ordered separately. The Duct Detector Housing includes a
6 in. (150 mm) exhaust tube.
Detector Mounting Bases
Each Duct Detector Housing requires a detector mounting
base (ordered separately) to accommodate the intelligent
smoke detector. Available mounting bases are as follows:
Standard Base SIGA-SB–
Basic mounting base; supports the SIGA-LED Alarm LED.
Relay Base SIGA-RB–
Mounting base with dry contact relay (normally open or
normally closed) controlled by the intelligent smoke detector.
The relay is rated for 1A @ 30 Vdc (pilot duty). The relay
position is supervised. The Relay Base does not support the
SIGA-LED Alarm LED.
The relay operates as follows:
- At system power-up or reset, the relay is de-energized
- On installation of an intelligent smoke detector in the
Relay Base with the power on, the relay energizes for
4 seconds, then de-energizes.
- On removal of an intelligent smoke detector from a Relay
Base with the power on, the relay is de-energized.
- When the detector enters the alarm state, the relay is energized.
Isolator Base SIGA-IB–
Mounting base with built-in line fault isolator. A detector must
be installed to operate the fault isolator. The integral isolator relay is controlled by
the detector or the loop controller. One loop can support a maximum of 96 Isolator
Base. The Isolator Base does not support the SIGA-LED Alarm LED.
Alarm LED Indicator
The SIGA-LED Alarm LED Indicator can be installed remotely or directly on the
SIGA-DH Duct Housing to provide indication for the associated intelligent duct
detector. Only the SIGA-SB Standard detector base can use the SIGA-LED Alarm
LED Indicator. The Alarm LED Indicator includes a red LED on a 1-gang plastic
plate. A maximum of 1 SIGA-LED can operate per each detector.
Air Velocity Test Kit
The 6263-SG Air Velocity Test Kit interfaces to the SIGA-DH Duct Housing and is
used to test or confirm the air velocity in HVAC ducts. |
SPECIFICATIONS
Intelligent Duct Smoke Detector Housing
Model:
- SIGA-DH Intelligent Duct Smoke Detector Housing. Includes 6 in. (150
mm) exhaust tube, gaskets, and self-adhesive drilling template for
mounting duct housing.
Air Velocity Range:
300 to 4000 ft/min. (1.5 to 20.3 m/sec) with XLS-PS and XLS-PHS Detectors
300 to 1000 ft/min. (1.5 to 5.0 m/sec) with XLS-IPHS Detector
Controller Compatibility:
SIGNATURE Loop Controller
Addressing Requirements:
One input device address
Dimensions:
7-3/8 in. (188 mm) wide x 7 in. (178 mm) high x 5 in. (127 mm) deep
Material and Finish:
16 gauge cold rolled steel
Red, baked enamel
Conduit Knockouts:
Combination 1/2 in. and 3/4 in.
Ship Weight:
6.5 lb (3 kg)
Standards:
International ISO 9001 Standards
Agency Approvals:
UL, CSFM
Options
Intelligent Duct Smoke Detectors:
- XLS-PS Intelligent Photoelectric Smoke Detector (with photoelectric
sensing element), .5 lb (.23 kg)
- XLS-PHS Intelligent 3D Multisensor Smoke Detector (with photoelectric
and heat sensing elements), .5 lb (.23 kg)
- XLS-IPHS Intelligent 4D Multisensor Smoke Detector (with ionization,
photoelectric, and heat sensing elements), .5 lb (.23 kg)
Detector Mounting Bases:
- SIGA-SB Standard Base, .2 lb (.09 kg)
- SIGA-RB Relay Base, .2 lb (.09 kg)
- SIGA-IB Isolator Base, .2 lb (.09 kg)
|