Excel 10
W7751H Smart VAV Actuator

|
SPECIFICATION DATA |

FEATURES
- Uses Echelon® LonWorks® network (E-Bus) protocol.
- Free Topology Tranceiver (FTT) high-speed 78 kilobit communications network.
- Compliant with VAV Device Object Type number 8010 functional LonMark® profile.
- Capable of stand-alone operation, but can also use E-Bus network communications.
- 120 controllers per Q7750A Excel 10 Zone Manager.
- Designed for Pressure Independent or Pressure Dependent Single or Dual Duct Variable Air Volume (VAV) control.
- Uses a Microbridge air flow sensor with patented dual integral restrictor design.
- Easy user access to air flow sensor inputs.
- Provides Proportional Integral Derivative (PID) temperature control.
- Floating hot water, two-stage electric or modulating hot water heat.
- Provides patented nonlinear floating algorithm for velocity control loops.
- Individual zone pressurization for supply and exhaust control.
- Factory configured via EEPROM with critical user parameter default values.
- Supports motion sensor interface, via network, for enhanced energy savings.
- Supports Terminal Regulated Air Volume (TRAV) concept.
- Supports pressurize and depressurize, night purge, and morning warmup sequences.
- Actuator included in W7751H mounts directly onto VAV box damper shaft and has up to 35 lb. in. torque, 90 degree stroke,
and 90 sec. timing at 60 Hz.
- Both controller housing and actuator are UL plenum rated.
GENERAL
The W7751H Smart VAV Actuator is a factory-integrated
Variable Air Volume (VAV) Box Controller and a 90 second
ML6161B Direct-Coupled Actuator in the Excel 10 family product
line. This VAV Box Controller provides Pressure Independent air
flow control and Pressure Dependent damper control. VAV
systems generally provide cool air only to the zones. The
W7751H Controller provides two additional outputs that control a
fan or VAV box reheat coils. The heaters can be staged electric
or modulating hot water. Supply and exhaust pressurization
control are provided on a zone basis.
|
DESCRIPTION
The W7751H Smart VAV Actuator is a factory-integrated Variable Air
Volume (VAV) Box Controller and a 90 second ML6161B Direct-Coupled
Actuator in the Excel 10 family product line. This VAV Box Controller
provides Pressure Independent air flow control and Pressure Dependent
damper control. VAV systems generally provide cool air only to the zones.
The W7751H Controller provides two additional outputs that control a fan
or VAV box reheat coils. The heaters can be staged electric or
modulating hot water. Supply and exhaust pressurization control are
provided on a zone basis.
Control techniques supported (heating and cooling):
Up to two stages of electric or hot water heat.
Floating hot water heat.
Pulse width modulated heat.
Floating damper output.
Additional control features:
OccupiedNormal hours or if bypass invoked from a wall module during unoccupied hours.
Unoccupied - Off hours.
Supply and exhaust pressurization control are provided on a zone basis.
Occupancy sensor override and window open override (only via the network). |
SPECIFICATIONS
Model
W7751G
The W7751H Smart VAV Actuator assembly is field mounted to the VAV box damper shaft similar to the mounting of a standard actuator.
Field wiring 14 to 22 AWG (2.0 to 0.34 mm 2 ) passes through conduit connecting to screw terminals, located under a snap-on cover, on the
bottom of the controller.
Input/Output
The W7751H is a NEC Class 2 rated device. This listing makes sure that the power consumed by the W7751H or devices it directly controls
must be limited to a sum total of 100 VA. (Any devices connected to the controller must obtain power from the same transformer.) Any
hardware that will be driven by the Triac outputs must have a minimum current draw, when energized, of 25 mA at 20 Vac and a maximum
current draw of 400 mA at 30 Vac.
Inputs:
Space temperature sensor.
Remote wall module setpoint input or duct air temperature sensor.
Remote wall module override.
Air flow sensor.
Outputs:
Internally wired VAV actuator (floating +).
Internally wired VAV actuator (floating -).
Floating heat (+) or stage 1 heat.
Floating heat (-) or stage 2 heat.
Power Supply
24 Vac with a valid range of 20 to 30 Vac at 50/60 Hz.
Power Consumption
6 VA maximum at both 50 and 60 Hz.
Hardware
CPU:
Motorola or Toshiba 3150 Neuron® processor, containing three eight bit CPUs. Each Neuron has a unique 48-bit network identification
number.
Memory Capacity:
The W7751H Smart VAV Actuator uses a 64K by 8 ROM/PROM, 512 bytes of EEPROM and 2K of RAM.
Differential Pressure Range
0 to 2.0 inw (0 to 0.5 kPa) maximum for the onboard flow sensor. Specified Sensing Temperature Range 20 Kohm NTC sensor temperature
range of 45 to 99°F (7 to 37°C) with an allowable control setpoint range from 50 to 90°F (10 to 32°C) when initiated from the network and 55 to
85°F (13 to 29°C) when configured and connected to a T7770 Wall Module, T7780A Digital Display Wall Module (DDWM) or C7770A Air
temperature Sensor.
Status Information
See Table 1.
Table 1. W7751G Controller LED Status Information.
LED Status |
Controller Status |
Off |
No power to processor. |
On |
No operational or (not configured) |
Slow Blink |
Operational (communicating in normal state) |
Fast Blink |
An alarm is present or in (Manual Test Mode) |

Fig. 1. Functional profile of LonMarkâ VAV object details
(variables not implemented in Excel 10 Smart VAV II
Actuator are greyed, or are in bold print in
Configuration Properties).
Communications
The W7751H uses an FTT transformer-coupled communications port with manchester encoded data presented to controllers and devices on
the E-Bus at 78 kilobits per second (kbs) via Echelon® communication protocol. Using the transformer-coupled communications interface
offers a much higher degree of common mode-noise rejection while assuring dc isolation. The E-Bus is insensitive to polarity, eliminating
installation errors due to miswiring.
The maximum E-Bus network length up to 5000 ft (1524m). For E-Bus network lengths greater than 5000 ft (1524m), see form 74-2865 E-Bus
Wiring Guidelines. The maximum number of nodes per E-Bus segment is 60. Approved cable types for E-Bus communications wiring is Level
IV 22 AWG (0.34mm 2 ) plenum or nonplenum rated unshielded, twisted pair, solid conductor wire.
Damper Shaft Mounting
The actuator on the W7751H mounts directly onto the VAV box damper shaft and has up to 35 lb. in. torque, 90 degree stroke, and 90 sec.
timing at 60 Hz. The actuator is suitable for mounting onto a 3/8 in. (10 mm) square or round VAV box damper shaft, using the included
201391 Shaft Adapter, or onto a 1/2 in. (13 mm) square or round VAV box damper shaft. The minimum VAV box damper shaft length is 1-3/4
in. (45 mm). The W7751H is designed for vertical or horizontal mounting options with the exception that the wiring compartment may not be on
top; these mounting options allow adequate air flow to keep the wiring compartmentbelow 140°F (60°C).
LonMark® Functional Profile
W7751H Controller supports the LonMark® Functional Profile number 8010 VAV Controller, version 1.0 (see Fig. 1).
Dimensions (H/W/D)
W7751H: 5-7/8 x 4-1/16 x 3-3/4 in. (149 x 103 x 95 mm).
Environmental Ratings
Operating Temperature: 32 to 125°F (0 to 50°C).
Shipping Temperature: -40 to 150°F (-40 to 65.5°C).
Relative Humidity
5% to 95% noncondensing.
Vibration
V2 level.
Corrosion
Office environment.
Approval Bodies
The W7751H is listed under UL 916 (E87741) and is also listed under cUL (E87741). The W7751H meets FCC part 15 Class B
requirements. The W7751H conforms to requirements per European Consortium standards EN50081-1 (CISPR 22 Class B) and EN 50082-1
(IEC 801-2, IEC 801-3 and IEC 801-4) for CE mark labeling.
Accessories
Excel 10 T7770 Wall Modules.
T7780A DDWM.
Excel 10 C7770A Air Temperature Sensor.
Excel 10 Q7750A Zone Manager.
Excel 10 Q7751A,B Router.
Excel 10 Q7752A,B Serial Interface Adapter.
Excel 10 Connector Cable 205979 from the Excel 10 Q7752A Serial Interface Adapter to Excel 10 Controller or Wall Module.
209541B Excel 10 Termination Module.
201052A,B,C Auxiliary Switches (one, two or three switches).
® U.S. Registered Trademark
Copyright ©1995 Honeywell Inc. - All Rights Reserved. |

|
Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis, Minnesota 55408-0524 |
Home and Building Control
Honeywell Limited-Honeywell Limitée
155 Gordon Baker road
North York, Ontario
M2H 3N7 |
Home and Building Control
Honeywell AG
Böblinger Strasse 17
D-71101 Schönaich
Phone (49-7031) 637-01
Fax (49-7031) 637-493 |
74-2953 J.D. 8/97 |
|
Helping You Control Your World® |