D570 and D580
Combination Fire/Smoke Dampers |
|
General
The D570 and D580 Low-Leakage, Fire/Smoke
Combination Dampers ("Dampers") are parallel-blade dampers designed for use in
conventional air handling systems to control the spread of fire and smoke during emergency
operation. The Dampers are leakage-rated and classified under Underwriters' Laboratories
(UL) Standards 555 and 555S (Class I, II, and III) for use in fire and smoke control
systems. The Dampers also meet NFPA 90A requirements.
The D570 Damper has a one-time fusible
link. The D580 Damper has a resettable link.
Features
Silicone rubber blade seals and side
seals for reduced leakage (Class I and II)
Galvanized steel construction for reduced corrosion
Jackshafted for positive blade action
Description
The D570 and D580 Low-Leakage, Fire/Smoke
Combination Dampers ("Dampers") are parallel-blade dampers designed for use in
conventional air handling systems to control the spread of fire and smoke during emergency
operation. The Dampers are leakage-rated and classified under Underwriters' Laboratories
(UL) Standards 555 and 555S (Class I, II, and III) for use in fire and smoke control
systems. The Dampers also meet NFPA 90A requirements. The D570 Damper has a one-time
fusible link. The D580 Damper has a resettable link.
Specifications
Models:
- D570 Damper with one-time fusible link
- D580 Damper with resettable link
Single Section Sizes:
NOTE: Dimension A is the nominal frame
dimension along the blade length. Dimension B is the nominal frame dimension perpendicular
to Dimension A.
Damper Dimensions for UL
Standard 555S, Classes I, II, and III.
Multisection Dampers:
Maximum dimensions for vertical damper
orientation (A = Dimension A, B = Dimension B): A 120 x B 30 in. (A 3048 x B 762 mm) or A
72 x B 84 in. (A 1829 x B 2137 mm)
NOTE: Maximum dimensions in these two
ranges are allowable. However, both Dimensions A and B must be equal to or less than their
respective limits. For example, if Dimension A = 80 in. (less than the 120-in. limit in
the first range), Dimension B cannot exceed 30 in. (the other limit in the first range);
if Dimension A = 70 in. (less than the 72-in. limit in the second range), Dimension B
cannot exceed 84 in. (the other limit in the second range).
Maximum dimensions for horizontal damper
orientation: 52 x 42 in. (1321 x 1067 mm)
NOTE: UL Standard 555 limits multisection
Dampers to four sections.
Maximum Approach Velocity:
Finish:
Galvanized frame and blades
Frame Construction:
Roll-formed 16-gage galvanized steel, one piece, notched and joined at one corner
Blades:
Roll-formed 22-gage galvanized steel
Double 90-degree bend in blade tips
Double-wrapped edges and centers
Die-crimped blade corners to seal blade/frame joint
External Drive Axles:
1/2-in. (13-mm) diameter zinc-coated
steel
External drive axles extend 6 in. (153 mm)
beyond frame
Blade Seals:
High-temperature, silicone rubber
(Class I and II only)
Bearings:
Formed from blade and rolled into frame
D570 Fuse Link and D580 Resettable Link
Ratings:
Standard: 165F (74C)
Optional: 212F (100C) or 286F (141C)
Hardware:
14-gage linkage bracket on both ends of
blade, two sections linked together if driven by one actuator along "A"
dimension
Blade Orientation:
Horizontal
Damper Mounting:
Vertical or horizontal plane
Maximum Static Pressure:
4 in. wc
Actuator Mounting:
External
Actuators:
Pneumatic MP909D, E, and MP918A, B
Factory or field mounted
Actuator Sizing:
Max. of 2 Damper sections joined along
the "A" dimension actuated by one MP909E or MP918A, B
Temperature Range:
40 to 250F (40 to 121C)
NOTE: Low temperature limit depends on
actuator specifications. See MP909D Pneumatic Damper Actuator Specification Data 77-9870,
MP909E Pneumatic Damper Actuator Specification Data 77-9030, or MP918A and B Pneumatic
Damper Actuator Specification Data 77-3080.
Pressure Drop:
0.03 in. wc at 1000 ft/min (5 m/s),
full open, typical
Options:
Position indicator switch
Round or oval transition
Factory sleeving:
14 gage by 18 in. (457 mm)
18 gage by 18 in. (457 mm)
Listing:
NOTE: Listings apply only when Dampers
are used with UL-Listed Honeywell damper actuators intended for D570 and D580 Dampers, and
when Dampers and actuators are installed according to instructions provided with product
shipment.
UL Standard 555 1-1/2 hour rating
UL Standard 555S as follows:
77-4017
Commercial Bldg Group
MLF TAB: II. E. 2
7-91

Helping You Control Your World
Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis, Minnesota 55408-0524Honeywell
Latin American Region
480 Sawgrass Corporate Parkway
Suite 200
Sunrise, FL 33325
Home Building Control
Honeywell Limited - Honeywell Limitée
155 Gordon Baker Road
North York, Ontario, M2H 3N7
Honeywell Europe S.A.
3 Avenue du Bourget
B-1140 Brussels
Belgium
Honeywell Asia Pacific Inc.
Room 3213-3225
Sun Hung Kai Centre
No. 30 Harbour Road
Wanchai, Hong Kong |