Honeywell Inc. 77-6238: Automatic Fire Detectors, Model #T4010A. CSI 3-Part Specifications.
Honeywell
FIRE/SECURITY SYSTEMS |
Automatic
Fire Detectors |
General
The ceiling mounted sensors are designed
for use with Fire Detection and Alarm Control
Panels, and contain terminals, terminal block,
fusible element, and switch contact. They are
listed by Underwriters’ Laboratories, Inc. and
approved by Factory Mutual System. |


T4010 APPROXIMATE DIMENSIONS IN INCHES (MILLIMETERS)
|
Features
- Easily replaceable fusible element.
- A standard 3-l/4 or 4 in. (83 or 102mm)
octagonal outlet box with accessory
mounting plate may be used.
Knockouts are provided in plastic base
for use with exposed wiring (A model
only).
|
Specifications
MODELS
T4010A Fire Sensor with spst
switching.
T4010C Fire Sensor with dpst
switching with No. 803257
mounting plate.
RATING IN AMPERES
6to 125 volts ac .......... .6.0
6 to 28 volts dc . . . . . . 3.0
125 volts dc . . . . . . . . 1.0
250 volts dc . . . . . . . .. 0.3
|
SWITCHING
Normally open contacts T4010A (SPST,N.O.) and T4010C (DPST, N.0.) close on temperature increase above
fixedtemperature setting.
REPLACEMENT FUSIBLE ELEMENT
1. 803007A -135F (57C).
2. 8030078 - 200F (93C).
WIRING TERMINALS
Double terminals at each connection to facilitate supervised loop wiring.
|
COVERAGE
1. 135F (57C) element - 900 sq. ft. (83.5 sq. meters); spacing 30 ft. (9 meters) centers with no more than 15 ft. (4.6 meters) from
wall or partition (U.L.,F.M.).
2. 200F (93C) element - 225 sq. ft. (21 sq. meters); spacing 15 ft. (4.6 meters) centers with no more than 7.5 ft. (2.29 meters)
from wall or partition (F.M.)
3. 200F (93C) element - 900 sq. ft. (83.5 sq. meters); spacing 30 ft. (9 meters) centers with no more than 15 ft. (4.6 meters) from
wall or partition (U.L.).
|
FIXED TEMPERATURE SETTING
1 3 5 F (57C) or 2 0 0 F (93C). Interchangeable without removing sensor base.
SAMPLE SPECIFICATION
Thermal detectors shall be (Honeywell T 4 0 1 0 )
fixed-temperature with replaceable fusible element.
FINISH
White plastic.
|