Description
The T4057A and B Automatic Fire Detectors are used with Fire
Detection and Alarm System Panels to provide positive, rapid fire
detection. They are low profile ceiling mounted devices that serve as
temperature actuated switches to initiate an audible alarm signal or
other alarm output.
Specifications
Models:
- T4057A Automatic Fire Detector: Combination rate-of-rise
and fixed temperature
- T4057B Automatic Fire Detector: Fixed temperature only
Electrical Ratings:
3A, 6 to 125V ac
lA, 6 to 28V dc
0.3A, 125V dc
0.1 A, 250V dc
Switching:
Available with either one or two sets of normally open
(n.o.) contacts. Contacts on temperature rise.
Dimensions In Inches (Millimeters):

|
Wiring Terminals:
Double screw terminals at each connection to facilitate loop wiring
Finish:
Flat white paint
Rate-Of-Rise Setting:
Approximately 15F (9C) per minute
Maximum Coverage:
T4057A: 2500 sq ft (232 sq m); spacing 50 ft (15m) centers;
25 ft (7.6m) to side wall or partition
T4057B: 625 sq ft (58 sq m); spacing 25 ft (7.6m) centers;
12.5 ft (3.8m) to side wall or partition
Fixed-Temperature Setting:
135F (57C) or 200F (93C)
Detector Identification:
Temperature
Setting |
Type |
Identification
Mark |
135F (57C)
135F (57C)
200F (93C)
200F (93C) |
Combination
None
Fixed
temperature
Combination
Fixed
temperature |
None
Gray spot
Gray ring
Gray spot and ring |
|