APP Modified Bitumen Specifications |
|
Specification 3CBN-W/3PBN-W |
Three Ply Heat Welded, Base Sheet Fastened Modified
Bitumen Mineral Surfaced Roofing System. For use over Johns Manville (JM) insulation,
approved substrate or other approved insulations on inclines up to 6" per foot (500
mm/m).
For Regions 1, 2 and 3 |

General
This specification is for use over any type of approved
structural deck
with insulation
or approved substrate which is suitable to receive a mechanical fastener and which
provides an acceptable surface to receive the roof.
Specific written approval is required for
any roof insulation that is not supplied by JM. Insulation shall be installed in
accordance with the appropriate JM Insulation
Specification detailed in the JM Commercial/Industrial Roofing Systems Manual. This
specification can also be used
in certain reroofing situations. Refer to the "Reroofing" section of the JM
Commercial/Industrial Roofing Systems Manual. This specification is not to be used over
gypsum, either poured or pre-cast, or lightweight insulating concrete decks or fills.
Design and installation of the deck and/or roof
substrate must result in
the
roof draining freely, to outlets numerous enough and so located as to remove water
promptly and completely. Areas where water ponds for more than 24 hours are unacceptable
and will not be eligible for a JM
Roofing System Guarantee.
Note: This specification is also for use
with JM PAO (Classic) products.
All general instructions contained in the current JM Commercial/Industrial Roofing Systems Manual shall be considered
part of this specification.
Flashings
Flashing details can be found in the "Bituminous
Flashings" section of the
JM Commercial/Industrial Roofing Systems Manual.
Application
Using one of the base plies listed, mechanically fasten
with an approved
JM insulation
fastener and plate, a 26 1/4" (665 mm) wide piece of base ply through the insulation.
The remaining base plies are to be applied full width with 3" (76 mm) side and
4" (102 mm) end laps over the preceding sheets. Fasten the laps at 9" (229 mm)
centers, and down the longitudinal center of each felt ply, place two rows of fasteners,
with the rows spaced approximately 11" (279 mm) apart, and fasteners staggered on
approximately 18" (457 mm)
centers. Use fasteners appropriate to the insulation and deck. For additional fastener information, refer to the
fastener data in the "Roof Decks" section of the current JM
Commerical/Industrial Roofing Systems
Manual.

Over the fastened base ply, heat
weld a 19 3/4" (500 mm) piece of one of the intermediate plies listed with a 4"
(102 mm) side and 6" (152 mm) end laps. The remaining plies are to be applied full
width, in the same manner, with
4" (102 mm) side and 6" (152 mm) end laps over the preceding sheet.
Over the existing two plies, heat weld a full width piece
of one of the cap
sheets listed.
Subsequent sheets are to be applied in the same manner, with a 4" (102 mm) side and
6" (152 mm) end laps over the preceding sheets.
Heat weld all plies so that they are firmly and uniformly
set. All laps must
be rolled
with a 3" (76 mm) rounded edge roller. A 1/8" to 3/8" (3 mm - 10 mm)
bleedout of APP compound shall be visible at the edge of all seams. All laps must be checked for good adhesion.
Preparation of the 6" (152 mm) end lap requires
scuffing away all loose
granules. Heat and embed all remaining granules. Apply heat to the roll being seamed while
making sure both have a good compound flow to adhere the two surfaces. End laps must be
checked for proper adhesion.
Application of JM APP/PAO
Modified Bitumen Products may require the use of an open flame propane torch. Improper use
of these materials and application equipment can result in severe burns, and/or other
physical injury, as well as damage to property. In order to prevent these situations the
mechanic must install the materials using the techniques rec-ommended by JM and those
found in "A Guide to Safety: Torch-On Modified Bitumens" available from
the Asphalt Roofing Manufacturers Association. These techniques have been endorsed by the
National Roofing Contractors Association and the United Union of Roofers, Waterproofers and Allied Workers.
For special precautions for heat weld application of JM
Classic (PAO) products, refer to Paragraph 7B.6.6.
For cold weather application techniques, refer to Paragraph
7B.14.
Steep Slope Requirements
Special procedures are required on inclines over 2 1/2" per foot (208 mm/m). Refer to Paragraph 7B.12.
Surfacing
No additional surfacing is required.
Note: When using metric and English sized
sheets in the same system,
care should be taken to avoid lap over lap
configurations.
For an identical copy of this
specification, ask for RS-4346.