Johns Manville 3CLN-W/3PLN-W. CSI 3-Part Specifications.
 |
APP Modified Bitumen Specifications |
|
Specification 3CLN-W/3PLN-W |
Three Ply Heat
Welded Modified Bitumen Mineral Surfaced Roofing System. For use over approved lightweight
insulating fill decks on inclines up to 3" per foot (250 mm/m).
For Regions 1*, 2 and 3 |

General
This specification is for use over any type of approved
lightweight insulating fill deck
(without insulation) which can receive and adequately retain mechanical fasteners that may
be recommended by the deck manufacturer. Examples of these decks are lightweight
insulating concrete, either cellular-type or aggregate-type. Ventsulation venting base
felt is recommended over any wet fill deck, and may be required as a condition of
guarantee. JM also recommends the use of FP-10 One-Way Roof Vents over some types of wet fill decks.
* In Region 1, contact a JM Technical Service Specialist
for written approval when using this specification over lightweight insulating
concrete.
Design and installation of the deck and/or roof
substrate must result in the
roof draining freely, to outlets numerous enough and so located as to remove water
promptly and completely. Areas where water ponds for more than 24 hours are unacceptable
and will not be eligible for a JM
Roofing System Guarantee.
Note: This specification is also for use
with JM PAO (Classic) products.
All general instructions contained in the current JM Commercial/Industrial Roofing Systems Manual shall be considered
part of this specification.
Flashings
Flashing details can be found in the "Bituminous
Flashings" section of the JM Commercial/Industrial Roofing Systems
Manual.
Application
Using one of the base plies listed, start with a piece 26 1 /4" (665 mm) wide. The remaining plies are to
be applied full width with 3" (76 mm) side and 4" (102 mm) end laps over the
preceding sheets. Using an approved light-weight insulating fill fastener, nail the laps
at 9" (229 mm) centers, and down the longitudinal center of each felt ply, place two
rows of nails, with the rows spaced approximately 11" (279 mm) apart, and nails
staggered on approximately 18" (457 mm) centers. Use nails or fasteners appropriate
to the type of deck, with 1" (25 mm) minimum diameter caps. For additional fastener
information, refer to the fastener data in the "Roof Decks" section of the
current JM Commercial/Industrial Roofing Systems Manual.

Over the fastened base ply, heat weld a half width 19 3 /4" (502 mm) piece of one of the intermediate
plies listed with 4" (102 mm) side and 6" (152 mm) end laps. The remaining plies
are to be full width, in the same manner, with 4" (102 mm) side and 6" (152 mm) end laps over the preceding
sheets.
Heat weld a full width piece of one of the cap sheets
listed so that it is firmly and
uniformly set. Subsequent sheets are to be applied in the same manner, with 4" (102
mm) side and 6" (152 mm) end laps over the preceding sheets. All laps must be rolled
with a 3" (76 mm) rounded edge roller. A 1/8" to 3/8" (3 mm to 10 mm)
bleedout of APP compound shall be visible at the edge of all seams. All laps must be checked for good adhesion.
Preparation of the 6" (152 mm) end lap requires
scuffing away all loose
granules. Heat and embed all remaining granules. Apply heat to the roll being seamed while
making sure both have a good compound flow to adhere the two surfaces. End laps must be
checked for proper adhesion.
Application of JM APP/PAO Modified Bitumen Products
may require the use of an open
flame propane torch. Improper use of these materials and application equipment can result
in severe burns, and/or other physical injury, as well as damage to property. In order to
prevent these situations the mechanic must install the materials using the techniques
recommended by JM and those found in "A Guide to Safety: Torch-On Modified
Bitumens" available from the Asphalt Roofing Manufacturers Association. These
techniques have been endorsed by the National Roofing Contractors Association and the
United Union of Roofers, Waterproofers and Allied Workers.
For special precautions for heat weld
application of JM Classic (PAO) products, refer to
Paragraph 7B.6.6.
For cold weather application techniques, refer to Paragraph
7B.14.
Steep Slope Requirements
Special procedures are required on inclines over 2 1 /2" per foot (208 mm/m). Refer to Paragraph 7B.12.
Surfacing
No additional surfacing is required.
Note: When using metric and English sized
sheets in the same system, care must be taken to avoid lap over lap
configurations.
For an identical copy
of this specification, ask for RS-4348.